Roof Fans Ventilation Systems BelAir

Transcript

Roof Fans Ventilation Systems BelAir
Roof Fans
Ventilation Systems BelAir
Issue 5 EN
January 2014
We set benchmarks for the roofs of the world
RDA / RDM
FDA
RGA
The premium roof fan
line with high value
aluminium casing.
Easy to fit, easy to
maintain.
Vertical dis­charge,
The super attenuated
unit in a cubic design
– for low noise application.
Vertical discharge,
up to 33,000 m3/h.
The advanta­ge­ous
choice with rugged corrosion resistant cowl.
Horizontal discharge,
up to 35,000 m3/h.
up to 57,000 m3/h.
The consistent quality strategy of Nicotra Gebhardt has set a
benchmark for the world market – but this is just the beginning.
Today we offer roof fan systems in a range which always allows a
solutions for individual requirements.
• Perfect quality for every roof fan line
• A consistent accessory system for all ranges
• Highest flexibility for individual solutions
• Shortest delivery on the fan market
The Perfection in Tolerance Class 2
Tolerance classes according to DIN 24166
Deviations per Tolerance Class
Performance data
2
3
Flow rate
qV
±5 %
±10 %
Pressure increase
ΔΔp
±5 %
±10 %
Power-consumption
P
±8 %
±16 %
LWA
+4 dB
+6 dB
Noise level
Not only do we set standards in reliability and design, but also in
the customary high level of data quality of our roof ventilators. This
has given us an Tolerance Class 2 according to DIN 24166.
In stating this classification we are allowing for a reliable technical
comparison of our products. Not that you would expect anything
less from us as a premium quality supplier.
We will be happy to give you more detailed information about this.
The best way is to contact us by telephone.
Flow rate
Conveying medium
Speed control
Material
d
el
ste
nte
Pai
ised
van
Gal
stic
Pla
ium
min
rter
nve
e
ge
driv
Vol
ta
DC
r
nce
ATE
X
EX-
Alu
°C
°C
cha
rge
sile
al i
ern
Ext
ess
shl
Bru
ted
gra
Inte
Dis
120
60
°C
h
m³/
h
m³/
h
m³/
h
m³/
h
m³/
•
•
•
For some sizes
•
Horizontal
sizes
• For some types
•
•
•
•
•
•
•
•
• optional
•
Motor cowl
•
•
Vertical
FDA
• optional
•
•
• RDM 31-/32-....-.A
• ATEX
• RDM 32
Horizontaö
•
•
•
•
•
•
•
•
•
•
•
•
•
•
• optional
•
•
• RDA 32
Vertical
• For some types
RDA
RDM
Integrated back draught damper
40
000
57.
000
33.
000
13.
00
6.5
00
1.2
RBA
Integrated back draught damper
•
•
•
•
•
•
• Cowl
•
• ATEX
Horizontaö
RGA
Simple and reliable fan selection
Simple and reliable selection
proSELECTA II is a technical selection program that allows you to
configure your own individually designed fan. It provides you with
the opportunity to choose from the entire range of fan types and
their associated options.
The result from proSELECTA II is the provision of all the technical
data for your fan, including sound level data, dimension
specifications and accessories. Apart from that, as a registered
user, your purchase prices are provided. Additionally fully
dimensioned drawings in dxf format are available, which can be
downloaded and transferred straight into your CAD system.
So that you can be sure. Models and options that are technically
not permissible, are automatically excluded in proSELECTA II. So
there is no chance that you will configure a “wrong” device option.
During the fan selection process, you can choose any of the
standardised ATEX options.
Free registration and many advantages
You can register as a proSELECTA II user with us, which enables us
to offer you faster order processing. What this means for you is:
• The complete configuration of your fan with its associated system
accessories and belt drive layout.
• The possibility to produce fans that operate via a frequency
inverter.
• The option of saving your own fan configuration on our server.
• The opportunity to modify your saved configuration, even over the
phone to your Nicotra Gebhardt representative.
• Specification
• Relative sound power data
• Terminal cowl
RGA
Centrifugal roof extract fan RGA
with external rotor motor
horizontal discharge
cowl made of moulded plastic
• Specification
• Relative sound power data
• Terminal cowl
Centrifugal roof extract fan RDM genovent®
with IEC standard motor placed out of airstream
vertical discharge
integrated back draught dampers
with silencer lining – RDM 32
• Specification
• Relative sound power data
• Frequency inverter opperation
Centrifugal roof extract fan FDA
with external rotor motor
vertical discharge
low noise execution
• Specification
• Relative sound power data
FDA
RDM
RDA
Centrifugal roof extract fan RDA genovent®
with external rotor motor
vertical discharge
integrated back draught dampers – RDA 31/32
with silencer lining – RDA 32
horizontal discharge – RDA 21
• Specification
• Relative sound power data
RBA
Centrifugal ventilation fanbox RBA
with external rotor motor
vertical discharge
BelAir
Ventilation Systems BelAir
for living areas on request!
• Mechanical accessories
• Switches and controllers
Accessories
Accessories
Samples
Description
Descriptions
Specifications
Service
The silent unit
There are cases where a fan has to be silent first. It is
for cases like this that the FDA 31 has been designed.
A casing equipped with highly efficient lining reduces
the discharge sound level.
The cubic design of the steel casing in addition integrates the unit into any roof surrounding. This is the
reason that thousands of these units are doing their
job without drawing attention. Perhaps on one of your
roofs soon too …
FDA
Roof fan line FDA 31
Nicotra Gebhardt external rotor motor
Flow rate up to 33,000 m³/h
Incredibly silent –
incredibly performing
The FDA 31 is equipped with a Nicotra Gebhardt external rotor motor. The flow rate is up to 33,000 m³/h.
This makes the FDA 31 silent and performing – another master piece coming from Nicotra Gebhardt.
104
Many reasons for choosing
the silent unit
Using an intelligent concept for the FDA 31 a high level of expectations concerning
performance, quality, design and noise comfort is met.
Jc
ubic design with integrated silencer made of galvanised steel sheet.
J the high performance backward curved impeller assures a smooth operation at
high efficiency level.
Ja
wide programme of external rotor motors mainly made by Nicotra Gebhardt.
Executions: single speed, 2-speed, voltage controlled by transformer or phase
cutting.
J s imple installation and inspection.
FDA
J full range of accessories.
105
Roof Extract Fans / FDA / Technical Data
FDA 31-2528
Technical Data in Class 2 acc. to DIN 24166
Curves PolesVoltage/
Fre- Speed
Connection quency
max. power Nominal
consumption current
FDA 31-
kW 2528-MD•
2528-6D•
2528-GD
2528-4E•
2528-6E•
V
Hz 1/min Starting/Full qVmaxLWA8 Capa- Protection/WeightMedia
load current
at qVmax citor
Temp. class
temp.
A m³/h
[A1|A2] 4/4 400, 3~ /Y
501420/1260
0.13/0.09
0.40/0.16
2.8
[A3] 6 400, 3~ Y 50
950
0.08
0.28
1.6
[A4|A5] 4/8 400, 3~ YY/Y 50
1430/ 720 0.16/0.05 0.37/0.15 3.0
[A6]
4
230, 1~501380 0.16 0.76 1.7
[A7] 6 230, 1~
50
910
0.08
0.34
1.7
dB AT
mF
1730/1570
60/57
-
1160
49
-
1740/ 880 60/42 -
1690
59 3
1120
48
2
kg °C
IP44/F68-20...+60
IP44/F
67
-20...+60
IP44/F
68
-20...+60
IP44/F67-20...+55
IP44/F
67
-20...+60
• (also) stepless speed controllable by tension variation
AT All indicated sound values are sound power levels. For more calculations when determining the
A-sound pressure level at any distances read the statements on part „Sounds“ in chapter „Description“.
Curves in Class 2 acc. to DIN 24166
Pa
FDA 31-2528-MD
LWA =
8 58
dB
200
54
56
51
150
r1=1.15 kg/m³
Pa
[A1]
200
dB
0
Pa
200
0
0
qV
400
0.1
[A6]
100
40
0
0
0
qV
400
0.1
800
0.2
1200
0.3
0.4
42
[A7]
45
60
56
150
1000 m³/h
m³/s
800
0.2
36 [A5]
FDA 31-2528-6E
LWA =
8 46
dB
80
53
600
psF
psF
m³/h
m³/s
40
60
= 57
57
A8
[A4]
42
1200
0.3
0.4
50
49
LW
54
46
800
0.2
60
57
400
0.1
LWA =
8 58
dB
100
54
0
0
qV
FDA 31-2528-GD
150
50
FDA 31-2528-4E
20
400
0.1
800
0.2
1200
0.3
0.4
m³/h
m³/s
48
59
0
0
qV
psF
50
psF
43
25
Pa
0
Pa
[A3]
50
psF
8 dB
57
100
200
FDA 31-2528-6D
75
[A2]
0
LWA8 = 4
0
200
0
0
qV
400
0.1
600
800
0.2
1000 m³/h
m³/s
Accessories
Isolator
Motor protection unit
Transformer
7 taps
Transformer
5-steps
Speed regulator Speed regulator Speed regulator Speed controller
electronic
electronic
micro processor electronic
FDA 31-
ESM ETO
ETH
EPH
ESH EPA
2528-MD•
21-0030-6504-0040-8D10-0010-8D35-0010-8D–
83-0050-8D
2528-6D•
21-0030-3501-0040-8D10-0010-8D35-0010-8D–
–
2528-GD21-0030-65 03-0040-8D6
––––
2528-4E•
21-0030-22–
10-0018-5E31-0020-5E03-0010-5E83-0060-5E
2528-6E•
21-0030-22–
10-0018-5E31-0020-5E03-0010-5E–
106
m³/h
m³/s
Roof Extract Fans / FDA / Technical Data
FDA 31-2528
410
704
Dimensions in mm, Subject to change.
FDA 31-2528-..
M6
Flat roof
upstand
Upstand
silencer
ZBU 01-0040-25 [St] 4 kg
ø256
Connection
plate
378
330
270
6×M6
ø286
115
650
283
1 When using back draught
damper ZLK in connection
with silencer upstand ZDS a
spacer ZKK is required
□400
□710
618
ZKE 11-0250 1.4 kg
130
535

150
ZKF 11-0250 0.7 kg
Mating flange
6×ø7
ø256
ø286
ø306
150
340
618
M
M
10
10
ZBS 09-0040-2 [Al] 5 kg
ø12
ø256
ø286
ø306
330
618
M
750
10
Inlet
silencer
ø256
ø286
ø345
ZLK 21-0250 9 kg 1
Motor drive
shutter
ø7
6×M6
ø256
ø286
ø306
ZBS 11-0040 [GFK] 11 kg
200
Flanged
inlet cone
ø286
ZSG 04-0250 0.4 kg
Mesh inlet guard
3× ø7
ø256
ø286
ø306
ø422
ZKK 20-0040 [St] 11 kg 1
Spacer
M10
ø11.5
275
10
□319
ø7
70
ZKD 01-0250 2 kg
□330
M
Soaker
sheet WDS
207
ø88
ZDR 30-0250 12 kg
150
6×ø7
180
Automatic
shutter
175
150
ZLK 01-0250 6 kg 1
240
□378
□330
25
10
6×ø7
ø256
ø286
ø306
□618
Inclined roof
upstand
Inlet connection
(flexible)
270
650
6 A protection for high speed
is only active if Dahlander
bridge is on place
378
330
Inclined roof
upstand
silencer
115
□378
□330
340
ZDS 09-0040-2 [Al] 13 kg 1
M
Flat roof
upstand tall
M
ZBS 23-0040 [St] 10 kg
10
618
250
 Pressure loss at back draught damper
138
ZDS 01-0040 [Al] 13 kg
ZDS 20-0040 [St] 18 kg 1
Accessories / Index
2 inclination in 5° steps up to
45° possible
6
ZBS 01-0040 [Al] 4 kg
ZBS 20-0040 [St] 8 kg
□395
□330
Mains lead
138
a-
Nicotra Gebhardt external
rotor motor with impeller fitted
directly. Casing equipped with
sound absorbing lining.
1600
Accessories
FDA 31-
ø12
115
M6
440
626
28
32
330
6×
330
386
920
107
Roof Extract Fans / FDA / Technical Data
FDA 31-2531
Technical Data in Class 2 acc. to DIN 24166
Curves PolesVoltage/
Fre- Speed
Connection quency
max. power Nominal
consumption current
FDA 31-
kW 2531-MD•
2531-6D•
2531-GD
2531-4E•
2531-6E•
V
Hz 1/min Starting/Full qVmaxLWA8 Capa- Protection/WeightMedia
load current
at qVmax citor
Temp. class
temp.
A m³/h
[B1|B2] 4/4 400, 3~ /Y
501340/1070
0.19/0.13
0.43/0.22
2.6
[B3] 6 400, 3~ Y 50
940
0.13
0.41
1.8
[B4|B5] 4/8 400, 3~ YY/Y 50
1400/ 710 0.23/0.06 0.50/0.18 3.2
[B6]
4
230, 1~501420 0.23 1.2 2.3
[B7] 6 230, 1~
50
920
0.12
0.54
1.5
dB AT
mF
2440/2010
60/55
-
1690
51
-
2530/1270 61/43 -
2550
61 6
1670
50
3
kg °C
IP44/F69-20...+60
IP44/F
69
-20...+60
IP44/F
70
-20...+60
IP44/F69-20...+60
IP44/F
69
-20...+60
• (also) stepless speed controllable by tension variation
AT All indicated sound values are sound power levels. For more calculations when determining the
A-sound pressure level at any distances read the statements on part „Sounds“ in chapter „Description“.
120 LWA8 = 5
0 dB
50
58
[B6]
1500
0.4
m³/h
m³/s
0
[B5]
FDA 31-2531-6E
46
[B7]
80
48
59
60
40
50
20
0
500 1000 1500 2000 2500 m³/h
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 m³/s
qV
0
50
61
psF
0
0
qV
500
1000
0.1
0.3
0.2
1500
0.4
m³/h
m³/s
Accessories
Isolator
Motor protection unit
Transformer
7 taps
Transformer
5-steps
Speed regulator Speed regulator Speed regulator Speed controller
electronic
electronic
micro processor electronic
FDA 31-
ESM ETO
ETH
EPH
ESH EPA
2531-MD•
21-0030-6504-0040-8D10-0010-8D35-0010-8D–
83-0050-8D
2531-6D•
21-0030-3501-0040-8D10-0010-8D35-0010-8D–
83-0050-8D
2531-GD21-0030-65 03-0040-8D6
––––
2531-4E•
21-0030-22–
10-0018-5E31-0020-5E03-0020-5E83-0060-5E
2531-6E•
21-0030-22–
10-0018-5E31-0020-5E03-0010-5E83-0060-5E
108
0
500 1000 1500 2000 2500 m³/h
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 m³/s
qV
LWA =
8 50 dB
100
100
psF
psF
120
57
150
0
500
1000
0.1
0.2
0.3
Pa
140
dB
200
0
0
qV
39
61
250
FDA 31-2531-4E
= 61
43
50
43
A8
[B4]
100
51
psF
60
55
LW
0
57
150
20
1500 2000 m³/h
0.4 0.5 0.6 m³/s
LWA =
8 61
dB
59
52
0
500
1000
0 0.1 0.2 0.3
qV
[B3]
40
FDA 31-2531-GD
200
60
50
Pa
46
48
[B2]
Pa
250
80
100
0
FDA 31-2531-6D
100
[B1]
150
r1=1.15 kg/m³
Pa
140
psF
Curves in Class 2 acc. to DIN 24166
LWA =
FDA 31-2531-MD
8 60
dB
56
200
55
Pa
Roof Extract Fans / FDA / Technical Data
FDA 31-2531
410
725
Dimensions in mm, Subject to change.
FDA 31-2531-..
M6
Flat roof
upstand
Upstand
silencer
ZBU 01-0040-25 [St] 4 kg
ø256
Connection
plate
378
330
270
6×M6
ø286
115
650
283
1 When using back draught
damper ZLK in connection
with silencer upstand ZDS a
spacer ZKK is required
□400
□710
618
ZKE 11-0250 1.4 kg
130
535

150
ZKF 11-0250 0.7 kg
Mating flange
6×ø7
ø256
ø286
ø306
150
340
618
M
M
10
10
ZBS 09-0040-2 [Al] 5 kg
ø12
ø256
ø286
ø306
330
618
M
750
10
Inlet
silencer
ø256
ø286
ø345
ZLK 21-0250 9 kg 1
Motor drive
shutter
ø7
6×M6
ø256
ø286
ø306
ZBS 11-0040 [GFK] 11 kg
200
Flanged
inlet cone
ø286
ZSG 04-0250 0.4 kg
Mesh inlet guard
3× ø7
ø256
ø286
ø306
ø422
ZKK 20-0040 [St] 11 kg 1
Spacer
M10
ø11.5
275
10
□319
ø7
70
ZKD 01-0250 2 kg
□330
M
Soaker
sheet WDS
207
ø88
ZDR 30-0250 12 kg
150
6×ø7
180
Automatic
shutter
175
150
ZLK 01-0250 6 kg 1
240
□378
□330
25
10
6×ø7
ø256
ø286
ø306
□618
Inclined roof
upstand
Inlet connection
(flexible)
270
650
6 A protection for high speed
is only active if Dahlander
bridge is on place
378
330
Inclined roof
upstand
silencer
115
□378
□330
340
ZDS 09-0040-2 [Al] 13 kg 1
M
Flat roof
upstand tall
M
ZBS 23-0040 [St] 10 kg
10
618
250
 Pressure loss at back draught damper
138
ZDS 01-0040 [Al] 13 kg
ZDS 20-0040 [St] 18 kg 1
Accessories / Index
2 inclination in 5° steps up to
45° possible
6
ZBS 01-0040 [Al] 4 kg
ZBS 20-0040 [St] 8 kg
□395
□330
Mains lead
138
a-
Nicotra Gebhardt external
rotor motor with impeller fitted
directly. Casing equipped with
sound absorbing lining.
1600
Accessories
FDA 31-
ø12
115
M6
440
626
28
32
330
6×
330
386
920
109
Roof Extract Fans / FDA / Technical Data
FDA 31-3535
Technical Data in Class 2 acc. to DIN 24166
Curves PolesVoltage/
Fre- Speed
Connection quency
max. power Nominal
consumption current
FDA 31-
V
1/min kW A m³/h
dB AT
mF
kg °C
3535-MD•
3535-ND•
3535-GD
3535-4E•
3535-6E•
400, 3~ /Y50
400, 3~ /Y 50
400, 3~ YY/Y 50
230, 1~
50
230, 1~
50
1340/1080
940/ 820
1280/ 670
1340
930
0.35/0.22
0.17/0.09
0.33/0.06
0.40
0.15
0.75/0.39 2.7
0.50/0.18 2.2
0.56/0.15 2.3
1.9
1.8
0.72
1.7
3470/2910
2400/2160
3340/1730
3470
2380
66/61
56/53
65/48
66
56
-
-
-
8
4
110
110
111
110
110
-20...+60
-20...+60
-20...+60
-20...+60
-20...+60
[C1|C2] 4/4
[C3|C4] 6/6
[C5|C6] 4/8
[C7] 4
[C8] 6
Hz Starting/Full qVmaxLWA8 Capa- Protection/WeightMedia
load current
at qVmax citor
Temp. class
temp.
IP44/F
IP44/F
IP54/F
IP44/F
IP44/F
• (also) stepless speed controllable by tension variation
AT All indicated sound values are sound power levels. For more calculations when determining the
A-sound pressure level at any distances read the statements on part „Sounds“ in chapter „Description“.
r1=1.15 kg/m³
Pa
150
125
psF
psF
psF
100 45
41 [C6]
0
0
0
qV
1000
2000
0.4
0.6
0.2
4 dB
50
[C8]
53
50
1000
2000
0.4
0.6
0.2
3000
0.8
25
m³/h
m³/s
0
56
66
0
0
qV
psF
50
psF
150
=5
75
100
[C5]
0
500 1000 1500 2000 2500 m³/h
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 m³/s
qV
Accessories
Isolator
Motor protection unit
Transformer
7 taps
Transformer
5-steps
Speed regulator Speed regulator Speed regulator Speed controller
electronic
electronic
micro processor electronic
FDA 31-
ESM ETO
ETH
EPH
ESH EPA
3535-MD•
21-0030-6504-0040-8D10-0010-8D35-0010-8D–
83-0050-8D
3535-ND•
21-0030-6504-0040-8D10-0010-8D35-0010-8D–
83-0050-8D
3535-GD21-0030-65 03-0040-8D6
––––
3535-4E•
21-0030-22–
10-0040-5E31-0020-5E03-0020-5E83-0060-5E
3535-6E•
21-0030-22–
10-0018-5E31-0020-5E03-0010-5E83-0060-5E
110
65
A8
100
63
150
58
200
0
500 1000 1500 2000 2500 m³/h
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 m³/s
qV
125
[C7]
B
FDA 31-3535-6E
150
59
2d
62
3 dB
=6
50
175 L
W
200
0
[C4]
Pa
=6
250
0
A8
48
300
[C3]
56
53
A8
47
LW
250
25
m³/h
m³/s
FDA 31-3535-4E
350 LW
50
50
FDA 31-3535-GD
300
53
Pa
3000
0.8
66
61
1000
2000
0.4
0.6
0.2
51
Pa
350
dB
75
63
0
0
qV
= 54
A8
50
50
0
LW
100
58
100
FDA 31-3535-ND
175
59
Curves in Class 2 acc. to DIN 24166
Pa
FDA 31-3535-MD
350 LWA
8 =6
3 dB
300
59
250
[C1]
200
54
150
[C2]
3000
0.8
m³/h
m³/s
Roof Extract Fans / FDA / Technical Data
FDA 31-3535
600
786
M8
216
ZDS 01-0056 [Al] 29 kg
ZDS 20-0056 [St] 40 kg 1
Flat roof
upstand
Upstand
silencer
□555
□450
Mains lead
ZBU 01-0056-35 [St] 6 kg
538
450
ø361
Connection
plate
430
□560
□870
8×M8
ø395
115
800
283
1 When using back draught
damper ZLK in connection
with silencer upstand ZDS a
spacer ZKK is required
778
ZKE 11-0355 2.1 kg
130
685

150
ZKF 11-0355 0.9 kg
Mating flange
8×ø9.5
ø361
ø395
ø421
150
500
778
M
M
10
10
ZBS 09-0056-2 [Al] 6 kg
250
ø361
ø395
ø421
450
ø12
778
M
750
10
Inlet
silencer
ø361
ø395
ø500
ZLK 21-0355 11 kg 1
Motor drive
shutter
8×M8
ø361
ø395
ø421
ZBS 11-0056 [GFK] 12 kg
200
Flanged
inlet cone
ø395
ZSG 04-0355 0.6 kg
Mesh inlet guard
4× ø9.5
ø361
ø395
ø421
ø515
ZKK 20-0056 [St] 14 kg 1
Spacer
M10
ø11.5
275
10
□420
ø9.5
63
ZKD 01-0355 3.5 kg
□450
M
Soaker
sheet WDS
258
ø9.5
ø88
ZDR 30-0355 17 kg
150
8×ø9.5
236
Automatic
shutter
205
150
ZLK 01-0355 7 kg 1
240
□538
□450
30
10
8×ø9.5
ø361
ø395
ø421
□778
Inclined roof
upstand
Inlet connection
(flexible)
430
800
6 A protection for high speed
is only active if Dahlander
bridge is on place
538
450
Inclined roof
upstand
silencer
115
□538
□450
500
ZDS 09-0056-2 [Al] 29 kg 1
M
Flat roof
upstand tall
M
ZBS 23-0056 [St] 14 kg
10
778
a-
 Pressure loss at back draught damper
192
ZBS 01-0056 [Al] 5 kg
ZBS 20-0056 [St] 10 kg
Accessories / Index
2 inclination in 5° steps up to
45° possible
39
ø12
1600
Nicotra Gebhardt external
rotor motor with impeller fitted
directly. Casing equipped with
sound absorbing lining.
5
450
32
M8
600
836
Accessories
FDA 31-
8×
115
Dimensions in mm, Subject to change.
FDA 31-3535-..
450
546
920
111
Roof Extract Fans / FDA / Technical Data
FDA 31-3540
Technical Data in Class 2 acc. to DIN 24166
Curves PolesVoltage/
Fre- Speed
Connection quency
max. power Nominal
consumption current
FDA 31-
kW A m³/h
dB AT
0.58/0.44
0.22/0.13
0.62/0.12
0.52
0.20
1.35/0.74 3.4
0.55/0.23 2.0
1.20/0.38 3.7
2.3 1.8
0.91
1.7
4830/4250
3100/2520
4780/2520
4340
3100
69/66 -
IP44/F
115 -20...+60
58/52 -
IP44/F
112 -20...+60
69/52 -
IP54/F
117 -20...+60
6612IP44/F115
-20...+55
58
5
IP44/F
112 -20...+60
3540-MD•
3540-ND•
3540-GD
3540-4E•
3540-6E•
V
Hz 1/min [D1|D2]4/4 400, 3~ /Y50
1400/1190
[D3|D4]6/6 400, 3~ /Y 50
890/ 690
[D5|D6]4/8 400, 3~ YY/Y 50
1380/ 700
[D7]
4
230, 1~501220
[D8] 6 230, 1~
50
890
Starting/Full qVmaxLWA8 Capa- Protection/WeightMedia
load current
at qVmax citor
Temp. class
temp.
mF
kg °C
• (also) stepless speed controllable by tension variation
AT All indicated sound values are sound power levels. For more calculations when determining the
A-sound pressure level at any distances read the statements on part „Sounds“ in chapter „Description“.
150
[D1]
59
=5
6 dB
A8
54
[D4]
100
1000
2000
0.2
0.4
0.6
LW
psF
psF
Pa
A8
B
0
52
0
1000 2000
0.2 0.4 0.6
0
qV
3000 4000 m³/h
0.8 1.0 1.2 m³/s
FDA 31-3540-6E
=5
6 dB
150
59
m³/h
m³/s
[D6]
51
300
3000
0.8
45
69
5d
0
0
qV
58
FDA 31-3540-4E
52
350
=6
[D5]
50
48
A8
0
62
65
45
66
LW
Pa
3000 4000 m³/h
0.8 1.0 1.2 m³/s
dB
200
69
0
1000 2000
0.2 0.4 0.6
0
qV
= 67
[D3]
63
0
LW
FDA 31-3540-GD
300
50
100
Pa
400
50
100
66
[D2]
200
A8
FDA 31-3540-ND
51
300
r1=1.15 kg/m³
LW
Pa
psF
Curves in Class 2 acc. to DIN 24166
Pa
FDA 31-3540-MD
LW
A8 = 6
8 dB
400 6
63
4
250
[D7]
200
64
54
150
50
0
1000 2000
0.2 0.4 0.6
0
qV
3000 4000 m³/h
0.8 1.0 1.2 m³/s
0
58
66
psF
50
psF
100
0
[D8]
100
0
0
qV
1000
2000
0.4
0.6
0.2
3000
0.8
m³/h
m³/s
Accessories
Isolator
Motor protection unit
Transformer
7 taps
Transformer
5-steps
Speed regulator Speed regulator Speed regulator Speed controller
electronic
electronic
micro processor electronic
FDA 31-
ESM ETO
ETH
EPH
ESH EPA
3540-MD•
21-0030-6504-0040-8D10-0020-8D35-0020-8D–
83-0050-8D
3540-ND•
21-0030-6504-0040-8D10-0010-8D35-0010-8D–
83-0050-8D
3540-GD21-0030-65 03-0040-8D6
––––
3540-4E•
21-0030-2501-0020-5E10-0040-5E35-0040-5E03-0040-5E83-0060-5E
3540-6E•
21-0030-22–
10-0018-5E31-0020-5E03-0010-5E83-0060-5E
112
Roof Extract Fans / FDA / Technical Data
FDA 31-3540
600
810
M8
216
ZDS 01-0056 [Al] 29 kg
ZDS 20-0056 [St] 40 kg 1
Flat roof
upstand
Upstand
silencer
□555
□450
Mains lead
ZBU 01-0056-35 [St] 6 kg
538
450
ø361
Connection
plate
430
□560
□870
8×M8
ø395
115
800
283
1 When using back draught
damper ZLK in connection
with silencer upstand ZDS a
spacer ZKK is required
778
ZKE 11-0355 2.1 kg
130
685

150
ZKF 11-0355 0.9 kg
Mating flange
8×ø9.5
ø361
ø395
ø421
150
500
778
M
M
10
10
ZBS 09-0056-2 [Al] 6 kg
250
ø361
ø395
ø421
450
ø12
778
M
750
10
Inlet
silencer
ø361
ø395
ø500
ZLK 21-0355 11 kg 1
Motor drive
shutter
8×M8
ø361
ø395
ø421
ZBS 11-0056 [GFK] 12 kg
200
Flanged
inlet cone
ø395
ZSG 04-0355 0.6 kg
Mesh inlet guard
4× ø9.5
ø361
ø395
ø421
ø515
ZKK 20-0056 [St] 14 kg 1
Spacer
M10
ø11.5
275
10
□420
ø9.5
63
ZKD 01-0355 3.5 kg
□450
M
Soaker
sheet WDS
258
ø9.5
ø88
ZDR 30-0355 17 kg
150
8×ø9.5
236
Automatic
shutter
205
150
ZLK 01-0355 7 kg 1
240
□538
□450
30
10
8×ø9.5
ø361
ø395
ø421
□778
Inclined roof
upstand
Inlet connection
(flexible)
430
800
6 A protection for high speed
is only active if Dahlander
bridge is on place
538
450
Inclined roof
upstand
silencer
115
□538
□450
500
ZDS 09-0056-2 [Al] 29 kg 1
M
Flat roof
upstand tall
M
ZBS 23-0056 [St] 14 kg
10
778
a-
 Pressure loss at back draught damper
192
ZBS 01-0056 [Al] 5 kg
ZBS 20-0056 [St] 10 kg
Accessories / Index
2 inclination in 5° steps up to
45° possible
39
ø12
1600
Nicotra Gebhardt external
rotor motor with impeller fitted
directly. Casing equipped with
sound absorbing lining.
5
450
32
M8
600
836
Accessories
FDA 31-
8×
115
Dimensions in mm, Subject to change.
FDA 31-3540-..
450
546
920
113
Roof Extract Fans / FDA / Technical Data
FDA 31-3545
Technical Data in Class 2 acc. to DIN 24166
Curves PolesVoltage/
Fre- Speed
Connection quency
max. power Nominal
consumption current
FDA 31-
kW A m³/h
dB AT
0.95/0.76
0.30/0.17
1.00/0.15
0.95
0.31
2.30/1.30 4.1
0.67/0.32 2.2
2.00/0.54 3.9
4.4 2.1
1.4
1.4
6800/6130
4190/3060
6650/3320
6450
4150
72/69 -
IP44/F
119 -20...+60
59/51 -
IP44/F
119 -20...+60
72/54 -
IP54/F
124 -20...+60
7120IP44/F119
-20...+55
59
8
IP44/F
119 -20...+60
3545-MD•
3545-ND•
3545-GD
3545-4E•
3545-6E•
V
Hz 1/min [E1|E2] 4/4 400, 3~ /Y50
1420/1250
[E3|E4] 6/6 400, 3~ /Y 50
860/ 600
[E5|E6] 4/8 400, 3~ YY/Y 50
1380/ 690
[E7]
4
230, 1~501330
[E8] 6 230, 1~
50
850
Starting/Full qVmaxLWA8 Capa- Protection/WeightMedia
load current
at qVmax citor
Temp. class
temp.
mF
kg °C
• (also) stepless speed controllable by tension variation
AT All indicated sound values are sound power levels. For more calculations when determining the
A-sound pressure level at any distances read the statements on part „Sounds“ in chapter „Description“.
r1=1.15 kg/m³
Pa
A8
63
300
[E1]
B
54
50
=7
psF
Pa
B
LW
A8
65
3000
4000 m³/h
1.0
m³/s
100
0
53
48
[E6]
54
0 1000 2000 3000 4000 5000
0.5
0
1.0
1.5
qV
FDA 31-3545-6E
250
0d
400
2000
0.5
[E5]
200
=5
9d
B
54
[E7]
300
150
[E8]
68
200
0 1000 2000 3000 4000 5000
0.5
0
1.0
1.5
qV
psF
m³/h
m³/s
0
59
0
50
71
psF
100
56
100
0
0
qV
1000
2000
0.5
3000
4000 m³/h
1.0
m³/s
Accessories
Isolator
Motor protection unit
Transformer
7 taps
Transformer
5-steps
Speed regulator Speed regulator Speed regulator Speed controller
electronic
electronic
micro processor electronic
FDA 31-
ESM ETO
ETH
EPH
ESH EPA
3545-MD•
21-0030-6504-0040-8D10-0040-8D36-0040-8D–
83-0050-8D
3545-ND•
21-0030-6504-0040-8D10-0010-8D35-0010-8D–
83-0050-8D
3545-GD21-0030-65 03-0040-8D6
––––
3545-4E•
21-0030-2501-0020-5E10-0070-5E35-0070-5E–
83-0060-5E
3545-6E•
21-0030-22–
10-0018-5E31-0020-5E03-0020-5E83-0060-5E
114
72
500
FDA 31-3545-4E
1000
59
A8
200
[E4]
48
0
0
qV
66
69
45
51
LW
0
1 dB
300
[E3]
40
m³/h
m³/s
=7
400
56
72
69
0 1000 2000 3000 4000 5000
0.5
0
1.0
1.5
qV
A8
FDA 31-3545-GD
9d
66
psF
=5
120
LW
500
80
100
Pa
160
69
[E2]
200
0
200
Pa
psF
400
FDA 31-3545-ND
240 LW
69
Curves in Class 2 acc. to DIN 24166
Pa
LW
FDA 31-3545-MD
A8 =
71 d
B
500
67
m³/h
m³/s
Roof Extract Fans / FDA / Technical Data
FDA 31-3545
600
853
M8
216
ZDS 01-0056 [Al] 29 kg
ZDS 20-0056 [St] 40 kg 1
Flat roof
upstand
Upstand
silencer
□555
□450
Mains lead
ZBU 01-0056-35 [St] 6 kg
538
450
ø361
Connection
plate
430
□560
□870
8×M8
ø395
115
800
283
1 When using back draught
damper ZLK in connection
with silencer upstand ZDS a
spacer ZKK is required
778
ZKE 11-0355 2.1 kg
130
685

150
ZKF 11-0355 0.9 kg
Mating flange
8×ø9.5
ø361
ø395
ø421
150
500
778
M
M
10
10
ZBS 09-0056-2 [Al] 6 kg
250
ø361
ø395
ø421
450
ø12
778
M
750
10
Inlet
silencer
ø361
ø395
ø500
ZLK 21-0355 11 kg 1
Motor drive
shutter
8×M8
ø361
ø395
ø421
ZBS 11-0056 [GFK] 12 kg
200
Flanged
inlet cone
ø395
ZSG 04-0355 0.6 kg
Mesh inlet guard
4× ø9.5
ø361
ø395
ø421
ø515
ZKK 20-0056 [St] 14 kg 1
Spacer
M10
ø11.5
275
10
□420
ø9.5
63
ZKD 01-0355 3.5 kg
□450
M
Soaker
sheet WDS
258
ø9.5
ø88
ZDR 30-0355 17 kg
150
8×ø9.5
236
Automatic
shutter
205
150
ZLK 01-0355 7 kg 1
240
□538
□450
30
10
8×ø9.5
ø361
ø395
ø421
□778
Inclined roof
upstand
Inlet connection
(flexible)
430
800
6 A protection for high speed
is only active if Dahlander
bridge is on place
538
450
Inclined roof
upstand
silencer
115
□538
□450
500
ZDS 09-0056-2 [Al] 29 kg 1
M
Flat roof
upstand tall
M
ZBS 23-0056 [St] 14 kg
10
778
a-
 Pressure loss at back draught damper
192
ZBS 01-0056 [Al] 5 kg
ZBS 20-0056 [St] 10 kg
Accessories / Index
2 inclination in 5° steps up to
45° possible
39
ø12
1600
Nicotra Gebhardt external
rotor motor with impeller fitted
directly. Casing equipped with
sound absorbing lining.
5
450
32
M8
600
836
Accessories
FDA 31-
8×
115
Dimensions in mm, Subject to change.
FDA 31-3545-..
450
546
920
115
Roof Extract Fans / FDA / Technical Data
FDA 31-4550
Technical Data in Class 2 acc. to DIN 24166
Curves PolesVoltage/
Fre- Speed
Connection quency
max. power Nominal
consumption current
FDA 31-
kW A m³/h
dB AT
1.60/1.05
0.52/0.38
0.28
1.62/0.25
1.45
0.54
3.20/1.80 3.8
1.30/0.69 3.3
0.69
2.3
2.90/0.77 3.3
6.3 2.0
2.6
1.8
9150/7740
6250/5430
4500
8960/4530
8660
6100
74/69 -
IP44/F
193 -20...+60
64/60 -
IP44/F
184 -20...+60
56
-
IP54/F
183 -20...+55
74/56 -
IP54/F
199 -20...+50
7330IP44/F192
-20...+60
64
12
IP44/F
184 -20...+45
4550-MD•
4550-ND•
4550-8D•
4550-GD
4550-4E•
4550-6E•
V
Hz 1/min [F1|F2] 4/4 400, 3~ /Y50
1350/1100
[F3|F4] 6/6 400, 3~ /Y 50
930/ 780
[F5] 8 400, 3~  50
660
[F6|F7] 4/8 400, 3~ YY/Y 50
1320/ 670
[F8]
4
230, 1~501260
[F9] 6 230, 1~
50
900
Starting/Full qVmaxLWA8 Capa- Protection/WeightMedia
load current
at qVmax citor
Temp. class
temp.
mF
kg °C
• (also) stepless speed controllable by tension variation
AT All indicated sound values are sound power levels. For more calculations when determining the
A-sound pressure level at any distances read the statements on part „Sounds“ in chapter „Description“.
1d
B
200
69
psF
LW
A8
=6
2 dB
57
[F9]
0
0
qV
2000
0.5
4000 6000
8000 m³/h
1.0
1.5
m³/s
2.0
50
0
0 1000 2000 3000 4000 5000 6000
0.5
0
1.0
1.5
qV
psF
Accessories
Isolator
Motor protection unit
Transformer
7 taps
Transformer
5-steps
Speed regulator Speed regulator Speed regulator Speed controller
electronic
electronic
micro processor electronic
FDA 31-
ESM ETO
ETH
EPH
ESH EPA
4550-MD•
21-0030-6504-0040-8D10-0040-8D36-0040-8D–
83-0050-8D
4550-ND•
21-0030-6504-0040-8D10-0020-8D35-0020-8D–
83-0050-8D
4550-8D21-0030-3501-0040-8D10-0010-8D35-0010-8D–
83-0050-8D
4550-GD21-0030-65 03-0040-8D6
––––
4550-4E•
21-0030-2501-0020-5E10-0070-5E35-0070-5E–
83-0100-5E
4550-6E•
21-0030-2501-0020-5E10-0040-5E31-0040-5E03-0040-5E83-0060-5E
116
4000 m³/h
1.0
m³/s
64
73
4000 6000
8000 m³/h
1.0
1.5
m³/s
2.0
0
3000
100
100
74
2000
0.5
[F7]
56
2000
0.5
60
100
0
0
qV
150
200
49
1000
FDA 31-4550-6E
250
[F8]
70
200 54
0
0
qV
Pa
300
66
300
300
psF
m³/h
m³/s
0
350
400
[F6]
6000
1.5
FDA 31-4550-4E
=7
500
67
4000
1.0
psF
B
400
psF
psF
2d
2000
0.5
56
600
500
0
0
0
qV
[F5]
50
50
A8
B
100
[F3]
[F4]
LW
4d
49
54
Pa
=5
58
200
0
FDA 31-4550-8D
49
=7
150
64
A
A8
3 dB
60
FDA 31-4550-GD
600
250
4000 6000
8000 m³/h
1.0
1.5
m³/s
2.0
Pa
700 LW
300
LW
=6
57
2000
0.5
74
69
0
0
qV
A8
100
100
0
350 L
W
Pa
61
68
200
FDA 31-4550-ND
150
71
[F2]
300
r1=1.15 kg/m³
Pa
59
68
Curves in Class 2 acc. to DIN 24166
Pa
FDA 31-4550-MD
700 LWA8 =
73
dB
600
68
500
[F1]
400
63
m³/h
m³/s
Roof Extract Fans / FDA / Technical Data
FDA 31-4550
740
1053
M8
M8
750
1016
Flat roof
upstand
Upstand
silencer
ZBU 01-0071-45 [St] 10 kg
ø453
Connection
plate
688
590
580
6×M8
ø487
115
900
283
1 When using back draught
damper ZLK in connection
with silencer upstand ZDS a
spacer ZKK is required
□710
□1020
988
ZKE 11-0450 2.7 kg
130
6×ø9.5
ZKF 11-0450 1.2 kg
Mating flange
6×ø9.5
ø453
ø487
ø513
150
650
988
M
M
12
12
ZBS 09-0071-2 [Al] 9 kg
ø14
ø453
ø487
ø513
590
988
M
12
1000
Inlet
silencer
ø453
ø487
ø650
ZLK 21-0450 14 kg 1
Motor drive
shutter
6×M8
ø453
ø487
ø513
ZBS 11-0071 [GFK] 29 kg
200
Flanged
inlet cone
ø487
ZSG 04-0450 0.7 kg
Mesh inlet guard
3× ø9.5
ø453
ø487
ø513
ø640
ZKK 20-0071 [St] 16 kg 1
Spacer
M12
ø14
275
12
□560
ø9.5
120
ZKD 01-0450 5 kg
□590
M
Soaker
sheet WDS
300
ø9.5
ø88
282
ZDR 30-0450 22 kg
150
6×ø9.5
278
Automatic
shutter
175
150
ZLK 01-0450 10 kg 1
240
□688
□590
30
150

785
ø453
ø487
ø513
□988
Inclined roof
upstand
Inlet connection
(flexible)
580
900
6 A protection for high speed
is only active if Dahlander
bridge is on place
650
688
590
Inclined roof
upstand
silencer
115
□688
□590
12
ZDS 09-0071-2 [Al] 57 kg 1
M
Flat roof
upstand tall
M
ZBS 23-0071 [St] 20 kg
12
988
250
 Pressure loss at back draught damper
282
ZDS 01-0071 [Al] 57 kg
ZDS 20-0071 [St] 79 kg 1
Accessories / Index
2 inclination in 5° steps up to
45° possible
7
ZBS 01-0071 [Al] 8 kg
ZBS 20-0071 [St] 16 kg
□705
□590
Mains lead
222
a-
Nicotra Gebhardt external
rotor motor with impeller fitted
directly. Casing equipped with
sound absorbing lining.
ø14
2000
Accessories
FDA 31-
48
32
590
6×
115
Dimensions in mm, Subject to change.
FDA 31-4550-..
590
700
1400
117
Roof Extract Fans / FDA / Technical Data
FDA 31-4556
Technical Data in Class 2 acc. to DIN 24166
Curves PolesVoltage/
Fre- Speed
Connection quency
max. power Nominal
consumption current
FDA 31-
V
kW 4556-MD•
4556-ND•
4556-8D•
4556-GD
400, 3~ /Y 50
400, 3~ /Y 50
400, 3~  50
400, 3~ YY/Y 50
[G1|G2] 4/4
[G3|G4] 6/6
[G5] 8
[G6|G7] 4/8
Hz 1/min 1270/ 960 2.40/1.46
920/ 770 0.90/0.59
610
0.38
1400/ 710 3.00/0.41
Starting/Full qVmaxLWA8 Capa- Protection/WeightMedia
load current
at qVmax citor
Temp. class
temp.
A m³/h
dB AT
mF
kg °C
4.30/2.4
2.10/1.1
0.93
5.20/1.2
12580/9950
8990/7790
6130
13620/6860
75/69
67/63
56
78/60
-
-
-
-
202
191
202
211
-20...+45
-20...+60
-20...+60
-20...+45
3.4
3.5
1.9
5.0
IP54/F
IP44/F
IP54/F
IP54/F
• (also) stepless speed controllable by tension variation
AT All indicated sound values are sound power levels. For more calculations when determining the
A-sound pressure level at any distances read the statements on part „Sounds“ in chapter „Description“.
Curves in Class 2 acc. to DIN 24166
LW
Pa
FDA 31-4556-MD
A8 =
75
700
dB
69
600
LW
Pa
A8
350
300
= 67
FDA 31-4556-ND
LW
Pa
A8
dB
61
62
150
r1=1.15 kg/m³
=
FDA 31-4556-8D
56
dB
68
62
0
0
0
qV
2000
0.5
4000 6000 8000 m³/h
2.0
1.0
m³/s
1.5
0
56
m³/h
m³/s
67
psF
50
63
psF
50
0
0
qV
2000
0.5
4000
1.0
FDA 31-4556-GD
72
700
75
69
0 2000 4000 6000 8000 10000
2.0
0
1.0
3.0
qV
[G5]
53
LW
Pa
A8 = 7
7 dB
800
59
66
100
100
0
100
[G4]
150
[G2]
200
[G3]
64
72
300
56
200
psF
400
[G1]
50
250
500
600
[G6]
500
75
400
300
60
54
100
0
[G7]
60
78
psF
200
0 2000 4000 6000 8000 10000
2.0
0q
3.0
V
m³/h
m³/s
Accessories
Isolator
Motor protection unit
Transformer
7 taps
Transformer
5-steps
Speed regulator Speed regulator Speed regulator Speed controller
electronic
electronic
micro processor electronic
FDA 31-
ESM ETO
ETH
EPH
ESH EPA
4556-MD•
21-0030-6504-0040-8D10-0065-8D36-0070-8D–
83-0050-8D
4556-ND•
21-0030-6504-0040-8D10-0040-8D36-0040-8D–
83-0050-8D
4556-8D21-0030-3501-0040-8D10-0010-8D35-0010-8D–
83-0050-8D
4556-GD21-0030-65 03-0040-8D6
––––
118
6000
1.5
m³/h
m³/s
Roof Extract Fans / FDA / Technical Data
FDA 31-4556
740
1096
M8
M8
750
1016
Flat roof
upstand
Upstand
silencer
ZBU 01-0071-45 [St] 10 kg
ø453
Connection
plate
688
590
580
6×M8
ø487
115
900
283
1 When using back draught
damper ZLK in connection
with silencer upstand ZDS a
spacer ZKK is required
□710
□1020
988
ZKE 11-0450 2.7 kg
130
6×ø9.5
ZKF 11-0450 1.2 kg
Mating flange
6×ø9.5
ø453
ø487
ø513
150
650
988
M
M
12
12
ZBS 09-0071-2 [Al] 9 kg
ø14
ø453
ø487
ø513
590
988
M
12
1000
Inlet
silencer
ø453
ø487
ø650
ZLK 21-0450 14 kg 1
Motor drive
shutter
6×M8
ø453
ø487
ø513
ZBS 11-0071 [GFK] 29 kg
200
Flanged
inlet cone
ø487
ZSG 04-0450 0.7 kg
Mesh inlet guard
3× ø9.5
ø453
ø487
ø513
ø640
ZKK 20-0071 [St] 16 kg 1
Spacer
M12
ø14
275
12
□560
ø9.5
120
ZKD 01-0450 5 kg
□590
M
Soaker
sheet WDS
300
ø9.5
ø88
282
ZDR 30-0450 22 kg
150
6×ø9.5
278
Automatic
shutter
175
150
ZLK 01-0450 10 kg 1
240
□688
□590
30
150

785
ø453
ø487
ø513
□988
Inclined roof
upstand
Inlet connection
(flexible)
580
900
6 A protection for high speed
is only active if Dahlander
bridge is on place
650
688
590
Inclined roof
upstand
silencer
115
□688
□590
12
ZDS 09-0071-2 [Al] 57 kg 1
M
Flat roof
upstand tall
M
ZBS 23-0071 [St] 20 kg
12
988
250
 Pressure loss at back draught damper
282
ZDS 01-0071 [Al] 57 kg
ZDS 20-0071 [St] 79 kg 1
Accessories / Index
2 inclination in 5° steps up to
45° possible
7
ZBS 01-0071 [Al] 8 kg
ZBS 20-0071 [St] 16 kg
□705
□590
Mains lead
222
a-
Nicotra Gebhardt external
rotor motor with impeller fitted
directly. Casing equipped with
sound absorbing lining.
ø14
2000
Accessories
FDA 31-
48
32
590
6×
115
Dimensions in mm, Subject to change.
FDA 31-4556-..
590
700
1400
119
Roof Extract Fans / FDA / Technical Data
FDA 31-5663
Technical Data in Class 2 acc. to DIN 24166
Curves PolesVoltage/
Fre- Speed
Connection quency
max. power Nominal
consumption current
FDA 31-
1/min kW 900/700
700
920/470
1.30/0.88 2.9/1.7 2.6
0.76
1.8
2.8
1.73/0.29 3.1/0.93 3.9
V
Hz 5663-ND• [H1|H2]6/6 400, 3~ /Y50
5663-8D• [H3] 8 400, 3~  50
5663-HD [H4|H5]6/12 400, 3~ YY/Y 50
Starting/Full qVmaxLWA8 Capa- Protection/WeightMedia
load current
at qVmax citor
Temp. class
temp.
A m³/h
mF
dB AT
12500/1030070/65 -
9630
64
-
12750/ 6450 71/53 -
IP44/F
IP54/F
IP54/F
kg °C
277
279
294
-20...+60
-20...+55
-20...+55
• (also) stepless speed controllable by tension variation
AT All indicated sound values are sound power levels. For more calculations when determining the
A-sound pressure level at any distances read the statements on part „Sounds“ in chapter „Description“.
Curves in Class 2 acc. to DIN 24166
Pa
FDA 31-5663-ND
LW
A8 = 7
0 dB
400
dB
= 70
dB
300
[H4]
100
[H5]
0
0
qV
2000
0.5
4000 6000 8000 m³/h
2.0
1.0
m³/s
1.5
psF
0
0 2000 4000 6000 8000 10000
2.0
0
1.0
3.0
qV
Accessories
Isolator
Motor protection unit
Transformer
7 taps
Transformer
5-steps
Speed regulator Speed regulator Speed regulator Speed controller
electronic
electronic
micro processor electronic
FDA 31-
ESM ETO
ETH
EPH
ESH EPA
5663-ND•
21-0030-6504-0040-8D10-0040-8D36-0040-8D–
83-0050-8D
5663-8D•
21-0030-3501-0040-8D10-0020-8D35-0020-8D–
83-0050-8D
5663-HD21-0030-65 03-0040-8D6
––––
120
71
psF
48
53
70
65
m³/h
m³/s
0
53
64
50
68
200
100
0 2000 4000 6000 8000 10000
2.0
0
1.0
3.0
qV
A8
FDA 31-5663-HD
65
58
61
[H2]
LW
150
67
59
Pa
400
61
psF
= 63
[H3]
[H1]
100
0
A8
FDA 31-5663-8D
200
300
200
LW
250
65
63
r1=1.15 kg/m³
Pa
m³/h
m³/s
Roof Extract Fans / FDA / Technical Data
FDA 31-5663
990
1109
ZDS 01-0090 [Al] 76 kg
ZDS 20-0090 [St] 105 kg 1
Flat roof
upstand
Upstand
silencer
□895
□750
335
ZBU 01-0090-56 [St] 17 kg
ø569
Connection
plate
878
750
770
8×M10
ø605
115
900
283
1 When using back draught
damper ZLK in connection
with silencer upstand ZDS a
spacer ZKK is required
□900
□1210
1178
ZKE 11-0560 3.6 kg
130
785

150
ZKF 11-0560 1.5 kg
Mating flange
8×ø11.5
ø569
ø605
ø639
150
840
1178
M
M
12
12
ZBS 09-0090-2 [Al] 13 kg
250
ø569
ø605
ø639
750
ø14
1178
M
12
1000
Inlet
silencer
ø569
ø605
ø770
ZLK 21-0560 16 kg 1
Motor drive
shutter
8×M10
ø569
ø605
ø639
ZBS 11-0090 [GFK] 36 kg
200
Flanged
inlet cone
□720
ZSG 04-0560 0.8 kg
Mesh inlet guard
4× ø11.5
ø569
ø605
ø639
ø785
ZKK 20-0090 [St] 19 kg 1
M12
ø14
275
Spacer
12
ø11.5 ø605
78
ZKD 01-0560 7.5 kg
□750
M
Soaker
sheet WDS
360
ø11.5
ø88
343
ZDR 30-0560 50 kg
150
8×ø11.5
343
Automatic
shutter
240
150
ZLK 01-0560 13 kg 1
240
□878
□750
35
12
8×ø11.5
ø569
ø605
ø639
□1178
Inclined roof
upstand
Inlet connection
(flexible)
770
900
6 A protection for high speed
is only active if Dahlander
bridge is on place
878
750
Inclined roof
upstand
silencer
115
□878
□750
840
ZDS 09-0090-2 [Al] 76 kg 1
M
Flat roof
upstand tall
M
ZBS 23-0090 [St] 32 kg
12
1178
a-
 Pressure loss at back draught damper
Mains lead
317
ZBS 01-0090 [Al] 13 kg
ZBS 20-0090 [St] 25 kg
Accessories / Index
2 inclination in 5° steps up to
45° possible
60
ø14
2000
Nicotra Gebhardt external
rotor motor with impeller fitted
directly. Casing equipped with
sound absorbing lining.
5
750
40
M10
940
1256
Accessories
FDA 31-
0
M1
8×
115
Dimensions in mm, Subject to change.
FDA 31-5663-..
750
886
1400
121
Roof Extract Fans / FDA / Technical Data
FDA 31-5671
Technical Data in Class 2 acc. to DIN 24166
Curves PolesVoltage/
Fre- Speed
Connection quency
max. power Nominal
consumption current
FDA 31-
kW V
Hz 1/min Starting/Full qVmaxLWA8 Capa- Protection/WeightMedia
load current
at qVmax citor
Temp. class
temp.
A m³/h
mF
dB AT
kg °C
5671-ND• [J1|J2] 6/6 400, 3~ /Y50
880/680 2.5/1.5
5.0/2.8 3.6
16850/1364074/68 -
IP54/F
297 -20...+45
5671-8D• [J3] 8 400, 3~ 
50
6501.22.7
2.61255066
-
IP54/F
291
-20...+55
5671-HD [J4|J5] 6/12 400, 3~ YY/Y 50
880/440
2.6/0.39
4.9/1.5 3.4
16850/ 8430 74/56 -
IP54/F
302 -20...+50
• (also) stepless speed controllable by tension variation
AT All indicated sound values are sound power levels. For more calculations when determining the
A-sound pressure level at any distances read the statements on part „Sounds“ in chapter „Description“.
Curves in Class 2 acc. to DIN 24166
LW
Pa
FDA 31-5671-ND
A8 =
73 d
B
500
300
69
[J4]
300
200
0 2000 4000 6000 8000 10000
2.0
0
1.0
3.0
qV
m³/h
m³/s
55
100
psF
psF
0
3 dB
0
50 [J5]
56
0
0
qV
4000
1.0
8000
2.0
74
psF
[J3]
50
m³/h
m³/s
=7
71
12000
3.0
4.0
FDA 31-5671-HD
400
62
66
8000
2.0
74
68
4000
1.0
A8
B
63
0
0
qV
LW
100
65
0
6d
150
71
[J2]
100
=6
Pa
500
200
63
200
A8
250
[J1]
300
FDA 31-5671-8D
350 L
W
69
67
400
r1=1.15 kg/m³
Pa
12000
3.0
4.0
Accessories
Isolator
Motor protection unit
Transformer
7 taps
Transformer
5-steps
Speed regulator Speed regulator Speed regulator Speed controller
electronic
electronic
micro processor electronic
FDA 31-
ESM ETO
ETH
EPH
ESH EPA
5671-ND•
21-0030-6504-0040-8D10-0065-8D36-0070-8D–
83-0050-8D
5671-8D•
21-0030-3501-0040-8D10-0040-8D36-0040-8D–
83-0050-8D
5671-HD21-0030-65 03-0040-8D6
––––
122
m³/h
m³/s
Roof Extract Fans / FDA / Technical Data
FDA 31-5671
990
1158
ZDS 01-0090 [Al] 76 kg
ZDS 20-0090 [St] 105 kg 1
Flat roof
upstand
Upstand
silencer
□895
□750
335
ZBU 01-0090-56 [St] 17 kg
ø569
Connection
plate
878
750
770
8×M10
ø605
115
900
283
1 When using back draught
damper ZLK in connection
with silencer upstand ZDS a
spacer ZKK is required
□900
□1210
1178
ZKE 11-0560 3.6 kg
130
785

150
ZKF 11-0560 1.5 kg
Mating flange
8×ø11.5
ø569
ø605
ø639
150
840
1178
M
M
12
12
ZBS 09-0090-2 [Al] 13 kg
250
ø569
ø605
ø639
750
ø14
1178
M
12
1000
Inlet
silencer
ø569
ø605
ø770
ZLK 21-0560 16 kg 1
Motor drive
shutter
8×M10
ø569
ø605
ø639
ZBS 11-0090 [GFK] 36 kg
200
Flanged
inlet cone
□720
ZSG 04-0560 0.8 kg
Mesh inlet guard
4× ø11.5
ø569
ø605
ø639
ø785
ZKK 20-0090 [St] 19 kg 1
M12
ø14
275
Spacer
12
ø11.5 ø605
78
ZKD 01-0560 7.5 kg
□750
M
Soaker
sheet WDS
360
ø11.5
ø88
343
ZDR 30-0560 50 kg
150
8×ø11.5
343
Automatic
shutter
240
150
ZLK 01-0560 13 kg 1
240
□878
□750
35
12
8×ø11.5
ø569
ø605
ø639
□1178
Inclined roof
upstand
Inlet connection
(flexible)
770
900
6 A protection for high speed
is only active if Dahlander
bridge is on place
878
750
Inclined roof
upstand
silencer
115
□878
□750
840
ZDS 09-0090-2 [Al] 76 kg 1
M
Flat roof
upstand tall
M
ZBS 23-0090 [St] 32 kg
12
1178
a-
 Pressure loss at back draught damper
Mains lead
317
ZBS 01-0090 [Al] 13 kg
ZBS 20-0090 [St] 25 kg
Accessories / Index
2 inclination in 5° steps up to
45° possible
60
ø14
2000
Nicotra Gebhardt external
rotor motor with impeller fitted
directly. Casing equipped with
sound absorbing lining.
5
750
40
M10
940
1256
Accessories
FDA 31-
0
M1
8×
115
Dimensions in mm, Subject to change.
FDA 31-5671-..
750
886
1400
123
Roof Extract Fans / FDA / Technical Data
FDA 31-7180
Technical Data in Class 2 acc. to DIN 24166
Curves PolesVoltage/
Fre- Speed
Connection quency
max. power Nominal
consumption current
FDA 31-
kW V
Hz 1/min Starting/Full qVmaxLWA8 Capa- Protection/WeightMedia
load current
at qVmax citor
Temp. class
temp.
A m³/h
dB AT
mF
kg °C
7180-6D* [L1] 6 400, 3~ 
50
9455.210.2
6.22480079
-
IP54/F
477
-20...+55
7180-8D• [L2] 8 400, 3~  50
660
2.0
4.4
3.1
17600
70
-
IP54/F
468 -20...+40
7180-HD [L4|L5]
6/12
400, 3~ YY/Y
50 960/4805.5/0.8511.0/3.3
4.5
24800/12470
79/61- IP54/F 477-20...+55
• (also) stepless speed controllable by tension variation
* these types do not have variable speed control by tension variation
AT All indicated sound values are sound power levels. For more calculations when determining the
A-sound pressure level at any distances read the statements on part „Sounds“ in chapter „Description“.
Pa
A8
= 71
FDA 31-7180-8D
dB
[L2]
67
0
0
0
qV
5000
10000
2.0
1.0
3.0
15000
4.0
m³/h
m³/s
psF
psF
psF
20000 m³/h
5.0 6.0 m³/s
57 [L5]
100
0
79
4.0
[L4]
200 62
70
10000
3.0
75
300
100
79
2.0
0 dB
700
400
0
0
1.0
qV
FDA 31-7180-HD
76
200
200
0
LWA8 = 8
500
300
100
Pa
600
300
76
400
r1=1.15 kg/m³
LW
66
Curves in Class 2 acc. to DIN 24166
LWA8 = 8
Pa
FDA 31-7180-6D
0 dB
700
75
600
[L1]
500
61
0
0
1.0
qV
2.0
10000
3.0
4.0
Accessories
Isolator
Motor protection unit
Transformer
7 taps
Transformer
5-steps
Speed regulator Speed regulator Speed regulator Speed controller
electronic
electronic
micro processor electronic
FDA 31-
ESM ETO
ETH
EPH
ESH EPA
7180-6D*
21-0075-35
–––––
7180-8D•
21-0030-3501-0040-8D10-0065-8D36-0070-8D–
83-0050-8D
7180-HD
21-0075-65
–––––
124
20000 m³/h
5.0 6.0 m³/s
Roof Extract Fans / FDA / Technical Data
FDA 31-7180
1183
1616
ZDS 01-0125 [Al] 130 kg
ZDS 20-0125 [St] 180 kg 1
Flat roof
upstand
Upstand
silencer
□1205
□1050
445
ZBU 01-0125-71 [St] 36 kg
ø715
Connection
plate
1226
1050
1117
8×M10
ø751
115
900
283
1 When using back draught
damper ZLK in connection
with silencer upstand ZDS a
spacer ZKK is required
□1210
□1520
1500
1190
785

150
ZKF 11-0710 2.5 kg
Mating flange
8×ø11.5
ø715
ø751
ø785
150
Automatic
shutter
ø715
ø751
ø785
1050
1000
M
ø715
ø751
ø915
ZLK 21-0710 20 kg 1
Motor drive
shutter
437
ø11.5
8×M10
ø715
ø751
ø785
ø88
415
ø14
12
Inlet
silencer
300
ZDR 30-0710 75 kg
ZKD 01-0710 10 kg
Flanged
inlet cone
ø11.5 ø751
175
150
8×ø11.5
ZSG 04-0710 1.1 kg
Mesh inlet guard
4× ø11.5
ø715
ø751
ø785
ø905
ZKK 20-0125 [St] 32 kg 1
Spacer
M12
ø14
275
150
ZLK 01-0710 19 kg 1
415
250
□1226
□1050
300
1190
1526
M
M
12
12
ZBS 09-0125-2 [Al] 18 kg
35
12
8×ø11.5
ø715
ø751
ø785
□1526
Inclined roof
upstand
Inlet connection
(flexible)
1117
900
6 A protection for high speed
is only active if Dahlander
bridge is on place
1226
1050
Inclined roof
upstand
silencer
115
□1226
□1050
130
ZKE 11-0710 5 kg
ZDS 09-0125-2 [Al] 130 kg 1
M
Flat roof
upstand tall
M
ZBS 23-0125 [St] 40 kg
12
1526
1526
 Pressure loss at back draught damper
Mains lead
445
ZBS 01-0125 [Al] 17 kg
ZBS 20-0125 [St] 34 kg
Accessories / Index
2 inclination in 5° steps up to
45° possible
75
ø14
a-
Nicotra Gebhardt external
rotor motor with impeller fitted
directly. Casing equipped with
sound absorbing lining.
1
1050
65
M10
1270
1556
Accessories
FDA 31-
0
M1
8×
115
Dimensions in mm, Subject to change.
FDA 31-7180-..
1050
1235
125
Roof Extract Fans / FDA / Technical Data
FDA 31-7190
Technical Data in Class 2 acc. to DIN 24166
Curves PolesVoltage/
Fre- Speed
Connection quency
max. power Nominal
consumption current
FDA 31-
V
kW 7190-6D* [M1]
400, 3~ 
50
9408.816.4
6.13455083
-
IP54/F
500
-20...+40
6
Hz 1/min Starting/Full qVmaxLWA8 Capa- Protection/WeightMedia
load current
at qVmax citor
Temp. class
temp.
A m³/h
dB AT
mF
kg °C
• (also) stepless speed controllable by tension variation
* these types do not have variable speed control by tension variation
AT All indicated sound values are sound power levels. For more calculations when determining the
A-sound pressure level at any distances read the statements on part „Sounds“ in chapter „Description“.
r1=1.15 kg/m³
Curves in Class 2 acc. to DIN 24166
Pa
LWA8 = 8
FDA 31-7190-6D
3 dB
900
78
800
[M1]
700
600
79
500
400
300
psF
83
200
100
0
10000
0
20000
30000 m³/h
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 m³/s
qV
Accessories
Isolator
Motor protection unit
Transformer
7 taps
Transformer
5-steps
Speed regulator Speed regulator Speed regulator Speed controller
electronic
electronic
micro processor electronic
FDA 31-
ESM ETO
ETH
EPH
ESH EPA
7190-6D*
21-0075-35
–––––
126
Roof Extract Fans / FDA / Technical Data
FDA 31-7190
1183
1668
ZDS 01-0125 [Al] 130 kg
ZDS 20-0125 [St] 180 kg 1
Flat roof
upstand
Upstand
silencer
□1205
□1050
445
ZBU 01-0125-71 [St] 36 kg
ø715
Connection
plate
1226
1050
1117
8×M10
ø751
115
900
283
1 When using back draught
damper ZLK in connection
with silencer upstand ZDS a
spacer ZKK is required
□1210
□1520
1500
1190
785

150
ZKF 11-0710 2.5 kg
Mating flange
8×ø11.5
ø715
ø751
ø785
150
Automatic
shutter
ø715
ø751
ø785
1050
1000
M
ø715
ø751
ø915
ZLK 21-0710 20 kg 1
Motor drive
shutter
437
ø11.5
8×M10
ø715
ø751
ø785
ø88
415
ø14
12
Inlet
silencer
300
ZDR 30-0710 75 kg
ZKD 01-0710 10 kg
Flanged
inlet cone
ø11.5 ø751
175
150
8×ø11.5
ZSG 04-0710 1.1 kg
Mesh inlet guard
4× ø11.5
ø715
ø751
ø785
ø905
ZKK 20-0125 [St] 32 kg 1
Spacer
M12
ø14
275
150
ZLK 01-0710 19 kg 1
415
250
□1226
□1050
300
1190
1526
M
M
12
12
ZBS 09-0125-2 [Al] 18 kg
35
12
8×ø11.5
ø715
ø751
ø785
□1526
Inclined roof
upstand
Inlet connection
(flexible)
1117
900
6 A protection for high speed
is only active if Dahlander
bridge is on place
1226
1050
Inclined roof
upstand
silencer
115
□1226
□1050
130
ZKE 11-0710 5 kg
ZDS 09-0125-2 [Al] 130 kg 1
M
Flat roof
upstand tall
M
ZBS 23-0125 [St] 40 kg
12
1526
1526
 Pressure loss at back draught damper
Mains lead
445
ZBS 01-0125 [Al] 17 kg
ZBS 20-0125 [St] 34 kg
Accessories / Index
2 inclination in 5° steps up to
45° possible
75
ø14
a-
Nicotra Gebhardt external
rotor motor with impeller fitted
directly. Casing equipped with
sound absorbing lining.
1
1050
65
M10
1270
1556
Accessories
FDA 31-
0
M1
8×
115
Dimensions in mm, Subject to change.
FDA 31-7190-..
1050
1235
127
Roof Extract Fans / FDA / Specification
FDA 31-2528/-7190
Specifications
Nicotra Gebhardt Radial-Roof-Fan
Designed for flow medium temperatures ranging from -20 °C up to approx. +40 °C.
Cubic casing made of galvanised sheet steel with noise attenuated lining.
Base frame of galvanised sheet steel for pedestal mounting, with a broad upstand for
pedestal insulation. On the inlet side with connection option for flange in accordance
with DIN 24 155-2.
Inlet guard on the discharge cross-section.
High performance centrifugal impeller with backward-curved blades, mounted on the
rotor of an integrated motor.
Totally maintenance-free motor with anti-vibration mounting, thermal contacts for
complete protection.
Fan ready for connection with terminal box attached.
Data in Class 2 according to DIN 24 166.
Options (at choice)
l Standard, casing with noise attenuated lining
l single speed (1~ or 3~)
l double speed (3~)
l speed controllable by tension variation (1~ or 3~)
Fan type
FDA 31-
VolumeqV = . . . . . . . . . . . . . . . .m3/h
Pressure increase
psF = . . . . . . . . . . . . . . . .
Media temperature t = . . . . . . . . . . . . . . . .°C
Speed N = . . . . . . . . . . . . . . . .1/min
max. power consumption Pe = . . . . . . . . . . . . . . . .kW
Nominal current I = . . . . . . . . . . . . . . . .A
Voltage/Frequency U/f = . . . . . . . . . . . . . . . .V/Hz
Sound power level
LWA8 = . . . . . . . . . . . . . . . .dB
Weight m = . . . . . . . . . . . . . . . .kg
Special fittings (at extra cost)
Isolator mounted (ESH 21)
Corrosion protection (Powder-Coating RAL 7039)
Accessories (at extra cost)
Flat roof upstand – Aluminium (ZBS 01) | galvanised sheet steel (ZBS 20)
Flat roof upstand tall – galvanised sheet steel (ZBS 23)
Inclined roof upstand – Aluminium (ZBS 09)
Soaker sheet WDS – GFK (ZBS 11) up to size 5671
Upstand silencer – Aluminium (ZDS 01) | galvanised sheet steel (ZDS 20)
Inclined roof upstand silencer – Aluminium (ZDS 09)
Inlet silencer (ZDR 30)
Flanged inlet cone (ZKD 01)
Connection plate (ZBU 01)
Inlet connection - flexible (ZKE 11)
Mating flange (ZKF 11)
Automatic shutter (ZLK 01)
Motor drive shutter (ZLK 21)
Mesh inlet guard (ZSG 04)
Spacer – galvanised sheet steel (ZKK 20)
Switches / Regulators / Controllers
Assignment see technical data
Specification see Accessories
Wiring diagrams see online at www.nicotra-gebhardt.com
128
Roof Extract Fans / FDA / Description
FDA 31-2528/-7190
Determination of the Octave level
For more exact calculations when determining the required attenuation, the sound
power level in the octave bands is important.
LWfc 3 = LWA + LWrel 3
LWfc 8 = LWA + LWrel 8
The relative sound power levels for inlet and discharge sides, at various duty points,
can be read from the corresponding tables.
LWA3 = LWA8 + 11 dB
Inlet side
Relative sound power level for inlet side LWrel3 at octave centre frequencies fm [LWrel3 = LWfc3 - LWA3]
FDA 31-
Opperation
Point
63
125
250
500
1000
2000
4000
8000
Hz
0.3 qVmax
12 13 -1 -6 -11-12-17-31
dB
2528/-2531 0.6 qVmax
9
12
-2
-5
-9
-10
-16
-29
dB
qVmax
3
12
-2
-5
-8
-10
-17
-29
dB
0.3 qVmax
13 12 0 -4 -10-15-19-28
dB
3535/-3545 0.6 qVmax
9
12
0
-4
-10
-12
-16
-25
dB
qVmax
5
11
1
-3
-10
-12
-19
-22
dB
0.3 qVmax
4550/-4556 0.6 qVmax
qVmax
14
9
5
9
8
7
3
3
2
-3
-3
-3
-9
-8
-8
-14
-12
-12
-15
-13
-13
-21
-17
-14
dB
dB
dB
0.3 qVmax
5663/-5671 0.6 qVmax
qVmax
16
14
12
7
7
7
3
3
4
-4
-4
-4
-7
-8
-8
-12
-11
-12
-14
-13
-13
-21
-20
-21
dB
dB
dB
0.3 qVmax
7180/-7190 0.6 qVmax
qVmax
15
13
10
7
7
7
3
3
4
-4
-4
-4
-7
-7
-8
-11
-11
-11
-13
-12
-12
-20
-19
-19
dB
dB
dB
Discharge side
Relative sound power level for discharge side LWrel8 at octave centre frequencies fm [LWrel8 = LWfc8 LWA8]
FDA 31-
Opperation
Point 63
125
250
500
1000
2000
4000
8000
Hz
0.3 qVmax
14 10 6 -9 -16-18-19-22
dB
2528/-2531 0.6 qVmax
14 11 5 -9 -14-16-17-20
dB
qVmax
9
9
6
-7
-14
-16
-17
-20
dB
0.3 qVmax
14 10 6 -9 -16-18-19-22
dB
3535/-3545 0.6 qVmax
14 11 5 -9 -14-16-17-20
dB
qVmax
9
9
6
-7
-14
-16
-17
-20
dB
0.3 qVmax
16 12 5 -9 -17-19-20-23
dB
4550/-4556 0.6 qVmax
12 12 5 -8 -16-18-19-21
dB
qVmax 9 11 4 -5 -12-14-15-16
dB
0.3 qVmax
16 13 4 -7 -19-23-27-29
dB
5663/-5671 0.6 qVmax
16 13 4 -7 -14-17-22-27
dB
qVmax
13
11
4
-5
-9
-12
-17
-22
dB
0.3 qVmax
16 13 4 -7 -19-23-27-29
dB
7180/-7190 0.6 qVmax
16 13 4 -7 -14-17-22-27
dB
qVmax
13
11
4
-5
-9
-12
-17
-22
dB
The sound power levels in the octave bands can – in the case of being situated at
blade frequency – reach higher values as indicated in the table.
129
Roof Extract Fans / FDA / Description
FDA 31-2528/-7190
Flow rate in the case of low voltage
Speed controllable fans
100
%
Threephase-AC
80
60
Singlephase-AC
40
qV/qVN
20
0
70
80
Singlephase-AC
120
160
Threephase-AC
100
120
200
U
140
U
240
160
280
180
320
200
230 V
360
400 V
This diagramme is made for determining the flow rate in the case of low voltage.
The flow rate ratio is shown in function of the voltage at the tappings.
Example for evaluation of the flow rate at low voltage:
Fan
Speed transformer, 5-step
Secundary voltage
FDA 31-4550-4E
ETH 35-0070-5E
130 Volt
In the grey area for a fan with single phase motor the result for the flow rate is 60 % of
the rated value.
130
Roof Extract Fans / FDA / Description
Notes
131
The Accessories
As important as the fan itself
The roof fan becomes a system if the accessories are added.
They are avayable as standard components
and can be supplied with the fan.
ZBS 01-0031/-0125 [Al]
ZBS 20-0031/-0125 [St]
ZDS 01-0028/-0125 [Al]
ZDS 20-0028/-0125 [St]
Flat roof upstand
Upstand silencer
ZBU 01-0028/-0125-.. [St]
Connection plate
ZKE 11-0180/-0900
ZKE 13-0225
ZBS 23-0031/-0125 [St]
Flat roof upstand tall
Inlet connection (flexible)
ZDS 09-0028/-0125-.. [Al]
Inclined roof
upstand silencer
ZKF 11-0180/-0900
ZKF 13-0225
Mating flange
ZBS 09-0031/-0125-.. [Al]
Inclined roof upstand
ZDR 30-0250/-0710
Inlet silencer
ZLK 01-0180/-0710
ZLK 03-0225
Automatic shutter
ZLK 21-0250/-0710
Motor drive shutter
ZBS 11-0040/-0090 [GFK]
Soaker sheet WDS
ZKD 01-0250/-0710
ZSG 04-0180/-0900
Flanged inlet cone
Mesh inlet guard
Spacer
152
Accessories
ZKK 20-0040/-0125 [St]
Roof Extract Fans / Samples
Samples
Samples
RKA 31
RGA
ZDS
ZBS
ZKE
ZLK
ZKF
Samples
RDM
ZBS
ZKE
ZKF
153
Roof Extract Fans / Samples
Samples
Samples
RKM 31
RDA
ZBS
ZDR
ZBS 09
ZKD
Samples
RDM 31/32
TBA / RBA
ZKE
ZBS
ZKE
ZKF
154
ZKF
Roof Extract Fans / Accessories
Accessories
Flat roof upstand
ZBS 01-0031/-0125 [Al]
ZBS 20-0031/-0125 [St]
Flat roof upstand tall
ZBS 23-0031/-0125 [St]
Inclined roof upstand
ZBS 09-0031/-0125-** [Al]
Ready-to-fit Flat roof upstand made of aluminium (ZBS 01) or galvanised sheet steel
(ZBS 20), with sound absorbing and thermal lining.
Flat roof upstand made of galvanised sheet steel (ZBS 23), with sound absorbing and
thermal lining.
Upstand for inclined roof made of aluminium sheet, provided with sound and thermal
insulation, available in steps of 5 degrees from 5 to 45 degrees roof inclination.
Order code (example): ZBS 09-0040-30 Upstand for inclined roof for RDA 31-25284E, roof inclination 30°.
Soaker sheet WDS
ZBS 11-0040/-0090 [GFK]
Spacer
ZKK 20-0040/-0125
Soaker sheets WDS, in glass fibre reinforced polyester, solve the problem of fitting a
roof unit to a corrugated roof (“Pitch length” of corrugation 177 mm) with up to 25°
pitch.
An intermediate piece made of galvanised sheet steel (ZKK 20) has to be provided if a
back draught damper is fitted together with a silencer upstand.
Fitted to the upstand itprovides the necessary distance between silencer and roof fan.
This garantees an even air flow without creating extra pressure losses.
Connection plate
ZBU 01-0028/-0125-.. [St]
Connection plate made of galvanised steel sheet with threaded bolts for fixing a flanged duct.
The connection plate has to be integrated into the roof with upstand silencer ZDS 01,
ZDS 20 or upstand
ZBS 01, ZBS 20, ZBS 13, ZBS 23 in order enable an easy connection of ductwork.
ZBR 01-0031/-0056-BA
155
Roof Extract Fans / Accessories
Accessories
Overhead silencer
ZDH 20-0250/-0710 [St]
Upstand silencer
ZDS 01-0028/-0125 [Al]
ZDS 20-0028/-0125 [St]
Inclined roof upstand silencer
ZDS 09-0028/-0125-** [Al]
Overhead silencer for sound reduction on discharge, houses the fan and can be easily positioned, in place of the cowl. The silencer is made from galvanised steel sheet.
The overhead silencer is designed to fit to the RGA range. It is supplied with
the fan as a kit to be assembled on site after installation of the fan base with
motorimpeller.
The Overhead Silencer ZDH is not available for ATEX fans (Type RGA 31-....-.X3G)!
Noise reduction values
average
noise reduction
ZDH 20dB
Noise reduction in dB at centre frequencies in Hz
63 125 250 500 1000200040008000
0250/-0355
0450/-0500
0560/-0710
0 -3 -5 -15-22-20-13-14
0 -5 -7 -15-21-20-16-17
-4 -8 -5 -13-17-18-18-17
11
11
11
Upstand silencer for the inlet side. The exterior skin is made of aluminium (ZDS 01) or
galvanised sheet steel (ZDS 20).
ZDS..–0040 and ZDS ..–0056 with removable absorber lining.
Inclined roof upstand silencer for the inlet side. The exterior skin is made of aluminium
(ZDS 09), available in steps of 5 degrees from 5 to 45 degrees roof inclination.
Pressure drop
Pa
25
90
..-00
..-01
ZDS
71
ZDS
..-00
..-00
ZDS
..-00
28
50
ZDS
ZDS
..-00
40
100
56
150
ZDS
pA
30
20
500
qV
1000
0.1
5000 10000 m³/h 40000
0.5
1.0
m³/s
5.0
10
Noise reduction values
average
noise reduction Noise reduction in dB at centre frequencies in Hz
ZDS ..dB
63 125 250 500 1000200040008000
0028
0040
0056
0071
0090
0125
156
16
16
16
17
15
16
2
3
3
3
2
3
5
5
5
5
5
6
8
8
8
9
8
8
1218222015
1319232115
1218212015
1320252217
1117211913
1420252311
Roof Extract Fans / Accessories
Accessories
Inlet silencer
ZDR 30-0250/-0710
The tubular inlet silencer has a square flange on the side nearest to the roof unit, for
bolting to the respective flat roof upstand. It slides inside the upstand, while the opposite end can take either additional ducting or an inlet cone.
The exterior skin is made of galvanised sheet steel, and the interior of galvanised perforated plate, the cavity between them is filled with non-flammable acoustic material.
There is no central core of material, so that any pressure loss will be insignificant.
Noise reduction values
average
noise reduction Noise reduction in dB at centre frequencies in Hz
ZDR 30dB
63 125 250 500 1000200040008000
0250
0355
0450
0560
0710
Flanged inlet cone
ZKD 01-0250/-0710
7
8
12
13
13
0
2
2
3
3
3
4
4
5
5
5
10
14
13
8
7
6
12
16
14
10
8
8.5
1720151210
91721151210
101822161210
The flanged inlet cone is for mounting under the inlet silencer, farthest from the unit, if
no additional ducting is planned.
This improves the intake flow environment and reduces losses.
Inlet connection (flexible)
ZKE 11-0180/-0900
ZKE 13-0225
Inlet connection (flexible) prevents the transmission of vibration to other parts of the
installation. Flange dimensions are in accordance with DIN 24155-2.
Mating flange
ZKF 11-0180/-0900
ZKF 13-0225
Mating flange, for joining an internal duct to the roof unit base.
Flange dimensions are in accordance with DIN 24155-2.
Mesh inlet guard
ZSG 04-0180/-0900
Mesh inlet guard, in accordance with EN ISO 13857.
157
Roof Extract Fans / Accessories
Accessories
Automatic shutter
ZLK 01-0180/-0710
ZLK 03-0225
Automatic shutters ZLK 01 are working as back draught dampers at stand still of the
roof fan thus avoiding uncontrolled intake of cold air.
Due to turbulences generated by the back draught damper ZLK the sound data for
intake and discharge may increase of app. 3 dB at discharge when a damper is fitted.
Motor drive shutter
ZLK 21-0250/-0710
Motor actuated shutters ZLK 21 control the exhaust air stream (mechanically or
naturally generated) also if the fan is not in operation. This is true also for ventilation
hoods. The shutter opens when the fan is switched on and closes at stop of the latter.
When working in parallel with the fan the shutter is working like a non motorised one.
Technical Data
Nominal
voltage
ZLK 21
V
230
Nominal
frequency
Hz
Shortcut
current
A
Power
consumption
W
Protection
class
IP
50
0.08
85
43
It is recommended to provide an intermediate duct piece between fan and shutter.
For this case the indicated pressure drops are applicable. If the shutter is directly fitted after the roof fan, higher pressure drops have to be expected.
The Motor drive shutter ZLK 21 is not available for ATEX fans (Type RGA 31-.....X-3G)!
A short circuit proof, single phase, actuator draws the shutter flaps by highly resistant
nylon ropes to open position and stays switched on during the whole opening phase.
The system is not equipped with end switches which could get dirty and ineffective
during live time.
After being switched off a push back spring closes the shutter.
The actuator has to be electrically connected to the main fan relay enabling the shutter to be opened at every time when the fan is put into operation. An auxiliary contact
for closing is not necessary.
When providing an motorised shutter it is recommended to fit an intermediate duct
piece between fan and shutter in order to facilitate access to the shutter actuator.
Connection diagram
Pressure drop
Pa
.-0 0
56
0
K.
.-0
71
0
5
45
35
ZL
K.
.-0
K.
ZL
ZL
ZL
10
K.
K.
.-0
.-0
25
20
ZL
L1
L2
L3
N
0
50
5
M
1~
2
pA
M
3~
1
200 500
qV
158
0.1
1000 2000
0.5
5000 10000
1.0
m³/h
5.0 m³/s
Roof Extract Fans / Accessories
Accessories
Increased corrosion protection / Powder Coating
For the operation under standard climatic conditions and for ventilation units without
remarkable corrosion load the standard paint execution without particular corrosion
protection will be sufficient.
For increased corrosion loads the corrosion protection options class “S40” or “K90”
can be selected.
Corrosion protection - Class S40
Degreasing, ironphosphating
• Powder coating - Layer thickness ≥40 μm, Colour RAL 7039
• Wet lacquering - Layer thickness ≥40 μm (primer + lacquer finish), Colour
RAL 7039
Corrosion protection - Class K90
Degreasing, ironphosphating
• Powder coating - Layer thickness ≥90 μm, Colour RAL 7039
• Wet lacquering - Layer thickness ≥90 μm (primer + lacquer finish), Colour
RAL 7039
Special colours (of the RAL range) on request.
The plastic cowl of the roof fan line RGA cannot be painted.
Roof fans in ATEX-execution cannot be supplied with a coating.
159
Roof Extract Fans / Accessories
Accessories
Isolator
ESH 21
Execution
Stylish, shockproof plastic casing, protection class IP 44/65, markings 0 and I.
The isolator switch is equipped with easy-connect tapings and wiring diagram.
The switch ESH 21 up to 3 kW protection class IP 44 and equipped with an integrated lock.
The switch ESH 21 from 5.5 kW protection class IP 65. It is equipped with a cover
coupling and an integrated lock. The turning switch can be key locked in position
“On” and “Off”.
Function
The isolator switch is provided for isolating the fan safely from the mains during any
cleaning, inspection or maintenance work, thus avoiding uncontrolled hazards by
thirds who could switch the fan on. This switch is not to be considered as a main or
an emergency switch.
The article can vary from the
figure.
Attention!
Combination with inverter!
Special radio noise suppression measures could be necessary; never keep the switch
under current, arising current peaks harm the switch and the windings.
All dedicated isolator switches are equipped with auxiliary contacts (1 open and
1 close).
The isolator switches for motors with inbuilt PTC thermistor are equipped with 3 auxiliary contacts in order to not trouble the preceding trigger unit by a appearing motor
fault.
Technical Data / Dimensions
ESH 21-
d
b
ESH 21 m 3 kW
a
c
b
ESH 21 L 3 kW
a
d
c
max. motor power
kW
Dimensions in mm, Subject to change
a
b
c
3.0
73
108
45
143
0030-32
0055-32
0075-32
0110-32
0150-32
0220-32
0300-32
0370-32
0450-32
0550-32
0900-32
3.0
5.5
7.5
11.0
15.0
22.0
30.0
370
45.0
55.0
90.0
73
85
85
85
100
100
145
145
200
200
280
108
120
120
160
190
190
250
250
300
300
400
45
80
80
78
91
91
107
107
172
172
180
143
58
58
58
58
58
58
58
73
73
73
0030-62
0055-62
0075-62
0110-62
0150-62
0220-62
0300-62
0370-62
0450-62
0750-62
3.0
5.5
7.5
11.0
15.0
22.0
30.0
37.0
45.0
75.0
73
85
100
100
145
145
200
200
300
280
108
120
190
190
250
250
300
300
300
280
45
90
91
91
100
107
172
172
172
230
143
58
58
58
58
58
73
73
73
73
0030-25
3.0
73
108
45
143
0030-35
0075-35
3.0
7.5
73
85
108
120
45
106
143
58
0030-65
0075-65
3.0
7.5
73
110
108
66
45
110
143
51
0075-95
7.5
110
66
110
51
The isolator switches are classified following to the motor rating. The type designation
indicates the main data.
Example: ESH 21-0030-65 =3 kW-switch
6 main contacts
5 auxiliary contacts
160
d
0030-22
Roof Extract Fans / Accessories
Accessories
for three-phase current motors (standard motors)
without thermal contacts
Design
Plastic casing in protection class IP 55, permissible ambient temperature +40 °C,
40 Hz – 60 Hz, frontal operation, for wall mounting. Motor protection unit for singlespeed, non- variable speed three-phase current motors without thermal contacts.
Function
The motor protection units must be adjusted on site to the trigger current.
If the preset trigger current is exceeded, the device disconnects the motor from the
mains supply via a thermal overload release. Pressing the “on key” causes the unit to
turn on again.
All motor protection units EUM 33 are also suitable for the protection of EExe-motors
(PTB-Prüfung Gesch-Nr. 3.35/386.3060). They must however be mounted outside of
explosion endangered areas, since they are not themselves designed with explosion
protection.
Technical Data
EUM
Continuous
flow
A
Setting
range
A
max. rated
power AC-3
kW
33-0004-8D
33-0006-8D
33-0010-8D
33-0016-8D
33-0024-8D
33-0040-8D
33-0060-8D
33-0100-8D
33-0160-8D
33-0200-8D
33-0250-8D
33-0500-8D
33-0580-8D
0.4
0.6
1.0
1.6
2.4
4.0
6.0
10.0
16.0
20.0
25.0
50.0
58.0
0.24/-0.4
0.09
0.4/- 0.6
0.12
0.6/- 1.0
0.25
1.0/- 1.6
0.55
1.6/- 2.4
0.80
2.4/- 4.0
1.50
4.0/- 6.0
2.50
6.0/-10.0
4.00
10.0/-16.0
7.50
16.0/-20.0
9.00
20.0/-25.0 12.50
40.0/-50.0 25.00
50.0/-58.0 30.00
Dimensions in mm, Subject to change
160
181
Motor protection unit
EUM 33
97
47.5
114
130
Connection diagram
L1
L2
L3
PE
EUM33
1
3
5
2
4
6
U1
V1
W1
161
Roof Extract Fans / Accessories
Accessories
Motor protection unit
ESM 01-/11-/12-/13-
for motors with fitted thermal control sensors
(thermal contacts, PTC)
Design
Beautifully shaped plastic casing made of shock resistant polystyrol, protection class
IP 54.
All units are suitable for wall mounting and include: hand switches for frontal operation, operational signal lamp and control safety accessible from outside.
Permissible ambient temperature: +40 °C.
Function
Should the motor winding temperature rise excessively, the imbedded motor winding
thermal contact or PTC will open the control circuit, causing the mains relay to drop
out and thus disconnect the motor from the mains supply.
The motor will also be turned off in the case of a mains-side dropout of the control
phase, as well as if the contacts fail or if the mains supply is interrupted.
The motor protection units are not equipped with an automatic re-poweron after a
mains voltage failure and are thus fail-safe.
After the motor windings have cooled down, a lock-out device in the relay circuit prevents the motor from switching itself on. The hand switch must first be momentarily
turned to the 0-position and then back to the ‘on’ position.
The operational signal lamp indicates the operation of the motor. It goes out in the
case of a malfunction.
The motor protection units are suitable for group switching, i. e. several motors with
the same switching can be connectedto a common switchingdevice.
The sum of the motors’ rated power may not exceed the maximal device rated power. The thermal contacts of all motors are to be switched in series. The PTCs switched in series may not exceed the sum of 6.
Technical Data
for motors with thermal contacts
ESM max. permitted rated
motor power
kW Nominal
voltage
V
Weight
01-0020-5E2.0
01-0040-8D4.0
02-0040-8D4.0
03-0040-8D4.0
04-0040-8D4.0
230
400
400
400
400
0.9
0.9
0.9
0.9
0.9
for motors with PTC
ESM Nominal
voltage
V
Weight
4000
400
400
0.9
0.9
0.9
max. permitted rated
motor power
kW 11-0040-8D4.0
12-0040-8D4.0
13-0040-8D4.0
For connection type see diagrams
140
30
Dimensions in mm, Subject to change
190
Please use the enclosed wiring diagrams in the control boxes always!
162
150
kg
kg
Roof Extract Fans / Accessories
Accessories
Motor protection unit
Connection diagram
ESM 01-0020-5E
Alternating current model, single speed
ATTENTION: for thermo contacts (TK) use always series connection!
N L1
TK TK TK TK
U1 U1 U1 U2 U2 U2
TK U1 Z2
TK Z1 U2
Anti-clockwise
rotation
TK TK TK TK
TK TK
TK TK
Connection with 2 motors
TK U1 Z2
TK Z1 U2
TK TK TK TK
TK TK
TK TK
PE N L1
Mains
Clockwise rotation
TK TK
Connection with 3 motors
Motor 1-phase
Connection diagram
ESM 01-0040-8D
Three-phase current model, single speed
ESM 02-0040-8D
Three-phase current model, 2 speed with two separate windings
ATTENTION: for thermo contacts (TK) use always series connection!
N L1 L2 L3
TK TK TK TK
U1 U1 U1 V1 V1 V1 W1 W1 W1
ATTENTION: for thermo contacts (TK) use always series connection!
N L1 L2 L3
TK TK TK TK
TK TK TK TK
TK TK TK TK
TK TK
Connection with 2 motors
PE N L1 L2 L3
Mains
TK U1 V1 W1
TK TK TK TK
TK U1 V1 W1
TK TK TK TK
TK W2 U2 V2
TK TK
TK W2 U2 V2
TK TK
PE N L1 L2 L3
Connection with 3 motors
Motor 3-phase
TK TK TK TK
1U 1V 1W 2U 2V 2W
Mains
TK
TK TK
TK
Connection with 3 motors
Motor 3-phase
ESM 04-0040-8D
Three-phase current model, 2 speed with Y/g-connection
ATTENTION: for thermo contacts (TK) use always series connection!
N L1 L2 L3
TK TK TK TK
TK TK TK TK
TK TK TK TK
TK TK
TK TK
TK TK
U1 V1 W1 U2 V2 W2
TK TK
Connection with 2
motors
Connection with 2 motors
Mains
TK TK
TK TK TK TK
ATTENTION: for thermo contacts (TK) use always series connection!
PE N L1 L2 L3
1U 1V 1W 2U 2V 2W
Connection with 2 motors
Connection diagram
ESM 03-0040-8D
Three-phase current model, 2 speed with Dahlander winding
N L1 L2 L3
TK TK TK TK
TK TK TK TK
TK 1U 1V 1W
TK TK TK TK
TK U1 V1 W1
TK TK
TK 2W 2U 2V
TK TK
TK W2 U2 V2
TK
TK TK
TK
Connection with 3 motors
PE N L1 L2 L3
Motor 3-phase
Mains
TK
TK TK
TK
Connection with 3 motors
Motor 3-phase
163
Roof Extract Fans / Accessories
Accessories
Motor protection unit
Connection diagram
ESM 11-0040-8D
Three-phase current model, single speed
ESM 12-0040-8D
Three-phase current model, 2 speed with two separate windings
ATTENTION: for PTC (KL) use always series connection!
N L1 L2 L3
KL KL KL KL
U1 U1 U1 V1 V1 V1 W1 W1 W1
ATTENTION: for PTC (KL) use always series connection!
N L1 L2 L3
KL KL KL KL
KL KL KL KL
KL KL KL KL
KL KL
KL U1 V1 W1
KL KL KL KL
KL U1 V1 W1
KL KL KL KL
KL W2 U2 V2
KL KL
KL W2 U2 V2
KL KL
PE N L1 L2 L3
Motor 3-phase
Connection diagram
ESM 13-0040-8D
Three-phase current model, 2 speed with Dahlander winding
ATTENTION: for PTC (KL) use always series connection!
N L1 L2 L3
KL KL KL KL
1U 1V 1W 2U 2V 2W
KL KL KL KL
KL KL
KL KL
Connection with 2 motors
PE N L1 L2 L3
Mains
164
KL KL
KL KL KL KL
Connection with 3 motors
Mains
1U 1V 1W 2U 2V 2W
Connection with 2 motors
Connection with 2 motors
PE N L1 L2 L3
KL KL KL KL
KL KL KL KL
KL 1U 1V 1W
KL KL
KL 2W 2U 2V
KL
KL KL
KL
Connection with 3 motors
Motor 3-phase
Mains
KL
KL KL
KL
Connection with 3 motors
Motor 3-phase
Roof Extract Fans / Accessories
Accessories
Transformer
ETO 10
with 7 secondary taps
Design
Transformer according to DIN VDE 0550-1 with built-on terminal strip for 7 taps, without casing, suitable for control cabinet installation.
Two transformers are necessary for three-phase current, which are to beconnected in
a V-switching configuration (see Wiring diagram). Permissible ambient temperature at
nominal current loading max. +35 °C.
ETO 10-....-5E
Primary voltage: 230 V / 50-60 Hz
Secondary voltage: 230/180/160/140/120/100/80 V
ETO 10-....-8D
Primary voltage: 400 V / 50-60 Hz
Secondary voltage: 400/310/270/235/200/170/140 V
Technical Data | Dimensions
Alternating current model
Nominal
Dimensions in mm,
current
Subject to change
ETO
A
abceøfhkg
c
Measurement diagram
øf
h
b
1.8
4.0
7.0
13.0
22.0
78
60
92
56
4.8
44
1.5
96
80
107
84
5.8
61
2.5
120
95
126
90
5.8
73
4.5
1351101351045.8 86 7.0
1351501351045.8 12612.5
Connection diagram
80 V
120 V
140 V
160 V
U2
1.0
2.0
4.0
6.5
15.0
78
60
92
56
4.8
44
1.5
96
80
107
84
5.8
61
2.5
120
95
126
90
5.8
73
4.5
135
110
135
104
5.8
86
7.0
1351501351045.8 12612.5
Connection diagram
Mains
L1
Motor
L2 L3
U1
V1 W1
0V
140 V
170 V
200 V
235 V
270 V
310 V
400 V
h
b
10-0010-8D
10-0020-8D
10-0040-8D
10-0065-8D
10-0150-8D
400 V
310 V
270 V
235 V
200 V
170 V
140 V
0V
øf
e
a
U1
Technical Data | Dimensions
Three-phase current model
Nominal
Dimensions in mm,
current
Subject to change
ETO
A
abceøfhkg
c
Measurement diagram
N
180 V
230 V
L
Motor
0V
Mains
100 V
e
a
10-0018-5E
10-0040-5E
10-0070-5E
10-0130-5E
10-0220-5E
165
Roof Extract Fans / Accessories
Accessories
Speed setting
ETH 31-/35-/36-/37-
transformatic, 5-step, with casing
Design
Completely plastic casing in protection class IP 54, Type:
ETH 31, 35 and ETH 37-0010/-0020-8D.
Painted metal casing in protection class IP 23, Type:
ETH 36 and ETH 37-0040/-0070-8D.
All units are suitable for wall mounting and include: speed control via hand switch
with 0-position and 5 switching steps, operating signal lamp, 230 V output for e. g. a
solenoid valve.
Permissible ambient temperature: -25 °C up to +40 °C.
ETH 31
These units include no motor protection unit. Protection switches for thermal contact
connections are to be laid in the conductor between the control device and the motor.
In Nicotra Gebhardt externallymounted rotor motors, the thermal contacts are already
bound into the motor winding.
ETH 35, ETH 36, ETH 37
These units possess a motor protection installation for thermal contact or PTC connection with a supplementary warning signal lamp, a potential-free exchanger and a
potential-afflicted (230 V) room thermostat connection (remote on – off).
Function
For motors with built-in thermal contacts, these open the control current circuit when
the permissible winding temperature is exceeded (ETH 31, 35, 36). Motors equipped
with PTC thermistor give an electrical signal to the trigger unit (ETH 37) when the temperature exceeds the default value. The trigger controls the main relay thus cutting
the motor feed. This causes the main fuse to fall out and disconnect the motor from
the mains.
After the motor winding has cooled down (ca. 2 Min.) or after remedying the cause of
the malfunction, respectively, turn the main switch temporarily to the 0-position and
then back to the operational position.
Dimensions in mm, Subject to change
1
2 3 4
f
5
b
d
0
a
166
c
g
e
ETH
abcdef gkg
31-0020-5E
31-0040-5E
35-0040-5E
35-0070-5E
36-0200-5E
35-0010-8D
35-0020-8D
36-0040-8D
36-0070-8D
36-0140-8D
37-0010-8D
37-0020-8D
37-0040-8D
37-0070-8D
155200150144 986.2 30
155200150144 986.2 30
155200150144 986.2 30
2002541701941406.2 30
2253051652651886.2 30
155200150144 986.2 30
2002541701941406.2 30
2253051652651886.2 30
2253051652651886.2 30
3023852233502656.2 30
2002541701941406.2 30
2002541701941406.2 30
2253051652651886.2 30
2253051652651886.2 30
4.0
4.0
4.0
8.0
17.0
6.0
8.0
14.0
20.0
35.0
5.5
8.0
14.0
20.0
Roof Extract Fans / Accessories
Accessories
Speed setting
ETH 31-/35-/36-/37-
transformatic, 5-step, with casing
Technical Data
Alternating current model
without motor protection installation
Nominal current
A
Mains safety
ETH
31-0020-5E
31-0040-5E
2.0
4.0
2 AT
6 AT
Primary voltage: 230 V; 50-60 Hz
Secondary voltage: 60/105/130/160/230 V
Technical Data
Alternating current model
with motor protection installation
ETH
Nominal current
Mains safety
A
35-0040-5E
35-0070-5E
36-0200-5E
4.0
7.0
20.0
6 AT
8 AT
20 AT
Primary voltage: 230 V; 50-60 Hz
Secondary voltage: 60/105/130/160/230 V
Technical Data
Three-phase current model
with motor protection installation
ETH
Nominal current
Mains safety
A
35-0010-8D
35-0020-8D
36-0040-8D
36-0070-8D
36-0140-8D
1.0
2.0
4.0
7.0
14.0
1 AT
2 AT
4 AT
8 AT
16 AT
Primary voltage: 400 V; 50-60 Hz
Secondary voltage: 140/180/230/280/400 V
Technical Data
Three-phase current model
with motor protection installation for motors with PTC
ETH
37-0010-8D
37-0020-8D
37-0040-8D
37-0070-8D
Nominal current
Mains safety
A
1.0
2.0
4.0
7.0
1 AT
2 AT
4 AT
8 AT
Primary voltage: 400 V; 50-60 Hz
Secondary voltage: 140/180/230/280/400 V
167
Accessories
Speed setting
ETH 31-/35-/36-/37-
transformatic, 5-step, with casing
Connection diagram
ETH 31
N L1
PE U1 U2 PE L1 N
PE N L1
PE U1 U2 PE L1 N
Motor
Mains
Connection diagram
ETH 35-/36-....-5E
N L1
PE U1 U2 TK TK RT RT PE L1 N 11 12 14
PE N L1
PE U1 U2
Mains
Motor
PE L1 N 11 12 14
Connection diagram
ETH 35-/36-....-8D
N L1 L2 L3
PE N L1 L2 L3
Mains
PE U1 V1 W1 TK TK RT RT PE L1 N 11 12 14
PE U1 V1 W1
Motor
PE L1 N 11 12 14
Connection diagram
ETH 37-....-8D
N L1 L2 L3
PE N L1 L2 L3
Mains
PE U1 V1 W1PTC PTC RT RT PE L1 N 11 12 14
PE U1 V1 W1
Motor
PE L1 N 11 12 14
TK = Thermal contact of the motor
PTC= P ositive Temperature Coefficient (PTC-Thermistor) of the motor
RT = Room thermostat or external switch
1 = additional outlet e. g. for solenoid valve, lamp, etc.
2 = free contacts for the status signal “Operating/Malfunction”
168
Roof Extract Fans / Accessories
Accessories
electronic, stepless
Design
Shock-resistant plastic casing (creamwhite) in protection class IP 44, with turn knob
on the front side.
Clearly arranged terminal strip for mains and motor connection.
For use as an integral version in a standard switch box, the speedregulator with its
front plate is simply removed from the casing underside.
Function
The transformer contains a turn knob for the variation of the nominal value by means
of phase-angle control, semiconductor fuse and a response output.
The transformer EPH is not equipped with any motor protection installation!
If thermo contacts are in use it is recommended to assure the electrical safety by
installing motor protection units EUM 11-0100-5E (IP 54) or EUM 21-0100-5E (IP 00,
for integration in a panel).
Technical Data
EPH
NominalNominalFrequency
Fuse
currentvoltage
A
V
Hz
03-0010-5E
03-0020-5E
03-0040-5E
1.0
2.0
4.0
230/240
230/240
230/240
50/60
50/60
50/60
Dimensions in mm, Subject to change
EPH 03-0010/-0040-5E
Surface mounting version
F 1.0 A
F 2.0 A
F 4.0 A
EPH 03-0010/-0020-5E
flush mounting version
Sealing
ø4
64
Transformer
EPH 03
82
~65
24
32
Connection diagram
N N
Re
L
M
N
169
Roof Extract Fans / Accessories
Accessories
Transformer
EPA 83
electronic, stepless, digital
Electronic controller for pressure, airspeed, temperature, with stepless adjustable output voltage for fans with controllable alternating current or threephase current motors
respectively.
Design
EPA 83 Surface mounting version
Plastic casing with die-cast aluminium base-plate in protection class IP 54.
Function
The pressure controller EPA 83 is equipped with a main switch, a motor protection
by thermal contact or PTC thermistors, nominal value input, main switch/automatic
with bypass-function, actual value input for sensors with 0...10 V signal (Temperature
sensor EIT, Differential pressure sensor EIP and Air velocity sensor EIL), for sensors
with 4...20 mA signal; semiconductor fuses and adjustment options for minimal and
maximal speed, menu-directed set-up via three function keys, output (0...10 V), potential-free operation signal contact, external nominal value preset via potentiometer,
integrated semiconductor fuses, phase monitoring, controller block, reset pushbutton
connection.
170
Technical Data
Alternating current design
Protection
class
EPA
IP
max. current
Nominal
Frequency
consumptionvoltage
A
V
Hz
app.
Weight
kg
83-0060-5E
83-0100-5E
0.2/- 6.0
230
0.2/-10.0 230
1.6
2.6
54
54
50/60
50/60
Technical Data
Three-phase current design
Protection
class
EPA
IP
max. current
Nominal
Frequency
consumptionvoltage
A
V
Hz
app.
Weight
kg
83-0050-8D
83-0100-8D
83-0150-8D
83-0250-8D
0.2/- 5.0
0.5/-10.0
0.5/-15.0
0.5/-25.0
2.7
3.1
5.2
13.6
54
54
54
54
400
400
400
400
50/60
50/60
50/60
50/60
Roof Extract Fans / Accessories
Accessories
Transformer
EPA 83
electronic, stepless, digital
Dimensions in mm, Subject to change
EPA 83-0060-5E
Surface mounting version
EPA 83-0100-5E
Surface mounting version
128
102
140.5
115
240
ø5.5
60
10
264
225
137
185
30
213
198
5
186
Dimensions in mm, Subject to change
EPA 83-0050-8D
Surface mounting version
13
EPA 83-0100-8D
Surface mounting version
131
115
131
115
13
186
Dimensions in mm, Subject to change
EPA 83-0150-8D
Surface mounting version
13
EPA 83-0250-8D
Surface mounting version
131
115
304
282
267
261
244
ø5.5
435
394
320
264
225
12
240
17
37
186
ø5.5
264
225
240
ø5.5
264
225
240
186
13
ø9
171
Roof Extract Fans / Accessories
Accessories
Transformer
EPA 83
electronic, stepless, digital
Connection diagram
EPA 83-....-5E
Auto
0
100%
V
+
PE
N L1
Analog IN 1
TK
TK
1*
Analog IN 2
24V
Digital IN 2
21 22 24
K2
Analog OUT 1
PE PE N N L1 L1 U1 U1 U2 U2 11 12 14
K1
D1
D1
A1
GND
D2
D2
E2
GND
E1
GND
DATA
- GND
RS485
E2.1 E2.2
GND
1
U1 U2 PE TK TK
1* If function is not needed,
M
terminals must be bridged
1~
Mains
1~ 230 V 50/60 Hz
mA
E1.1 E1.2
Digital IN 1
DD+
Max. contact capacity 5 A / 250 V AC
°C
Input
0...10 V (Ri >100 k)
0...20 mA
4...20 mA
KTY10-6
(-8...+43 °C)
2
Output
0...10 V (Imax=10 mA)
1-phase motor
with integrated thermo
contacts
Input
0...10 V (Ri >100 k)
0...20 mA
4...20 mA
KTY10-6
(-24...+80 °C)
Analog IN 2
Digital IN 2
TK
TK
Analog IN 1
11 14 12 21 24 22
K2
K1
24 V DC OUT 1
GND
N L1 L2 L3 U V W
Analog OUT 1
Max. contact capacity 5 A / 250 V AC
Digital IN 1
Connection diagram
EPA 83-....-8D
D1
D1
A
GND
24V
24V
E1
GND
E2
GND
D2
D2 E1.1 E1.2
1
PE N L1 L2 L3
Mains
1~ 230 V 50/60 Hz
U V W PE
M
3~
TK
TK
3-phase motor
with integrated thermo
contacts
172
Output
Input
0...10 V
0...10 V
(Imax=10 mA) (Ri >100 k)
0...20 mA
4...20 mA
KTY10-6
(-24...+80 °C)
2
Input
0...10 V (Ri >100 k)
0...20 mA
4...20 mA
KTY10-6
(-8...+43 °C)
°C
E2.1 E2.2
V
mA
DD+
GND
24V
Roof Extract Fans / Accessories
Standard component of
brushless DC fans
Elektronical Commutation Unit
EKE 05
for Nicotra Gebhardt brushless DC motors
Execution
Electronical commuter unit with single phase input and and variable output voltage
and frequency, specially designed for matching to the operation of roof fans with
brushless DC motors. By using most modern power semi conductors a high
efficiency at any speed is guaranteed. The output voltage is generated at high pulse
frequencies (15 kHz).
Specification
- suitable for operating Nicotra Gebhardt brushless DC motors exclusively
- for single phase feed line 208-277 V / 47-63 Hz
- max. motor rating of 380 W
- internal power limitation
- max. ambient temperature at operation
-10 °C to +40 °C
- setting of max. and min. rpm possible (possibility of setting reduced speed at night)
- analogue interface 0...5 V / 0...10 V
- Monitoring of operation (potential-free error reading)
- no error contact closed
- error (e.g. no current) contact closed
- Reset and programming button
- easy and simple maximum speed programming
Standards and guide lines
Radio frequency suppression to EMV basic standard EN 50081-1 (residential and
business areas) and EN 61000-3-2 is met by using integrated filters and power factor
controller (PFC).
Technical Data
Input
Output
Nominal Nominal Power Voltage / Voltage
power output
factor
Frequency
current
EKE V / Hz (1~)Vpic-pic (=)W
A (3~)
cos phi
05-0018-5E-IA
208...277 / 47...63 420
1.74
0.99
400
Protection
class
IP20
Connection diagram
1 mains
2 analog input
Nmin
Nmax
3 error contact opener
4 reset / programming
1
5 programming LED
4 A B
6 error LED
1
2
3
1
8
1
8
7 operating LED
Links
Nmin
1 2 3 4
A
B
Nmax
1
2
3
4
A
B
Nmin
Nmax
= +5 V
= 0...10 V
= 0... 5 V
= ground
= error contact
= error contact
= minimal speed setting
= maximal speed setting
173
Roof Extract Fans / Accessories
Accessories
Speed Regulator Module
EGH 01
for Roof Fans with brushless DC motor or frequency inverter
Design
- rotary knob to switch and stepless speed variation
- Impact-resistant plastic casing (cream-coloured) in protection class IP44
- also for integration in a normal switching box
- clearly visible and identifiable terminal strip for connections
Function
The module has a rotary knob for on/off and stepless speed variation through the
analogue input of the inverter (BLDC driver, frequency inverter).
Technical Data
protection class
Weight
Type
kW
switching contact
IP
kg
EGH 01
10
44
0.145
10 A / 12 V DC
Dimensions in mm, Subject to change
Surface mounting version
flush mounting version
Sealing
64
ø4
~65
82
24
Connection diagram
174
T
max. 4A / 250V AC +10V 0...10V
10A / 12V DC
(+5V) (0...5V)
32
Roof Extract Fans / Accessories
Accessories
Frequency inverter
G110
MM420
Design
Frequency inverter with variable output voltage and frequency, specially designed for
the operation of centrifugal fans with induption motors.
Due to the use of modern power semiconductors it is possible to achieve a speed of
revolution with high efficiency.
Switching frequencies up to 16kHz can be set with all types. If the high­est switching
frequencies are required (for example for reasons of noise reduction), the maximum
out­put current is decreased, in which case the performance category should be specially checked.
The overall package includes the fre­quency inverter, filter for class B (for residential and commercial uses) as well as a control unit.
General Performance characteristics
Motor protection feature for motors with thermistor temperature sensors, adjustable
accelaration and deaccelaration ramps, minimum and maximum rotation speeds,
fixed rotation speeds, trapping switch during operation, programmable inputs and
PI-controller (MM420 and MM430 only), RS 485 serial interface as well as a detailed
operating instructions.
Caution about combination with isolators (ESH)!
Special EMC-action can be necessary, furthermore do not switch during operation,
overvoltages can destroy the switch and the motor-winding.
Performance range G110 1AC 230V
(for single-phase AC supply)
0.25 to 2.2 kW rated motor power, 200 to 240V ±10% single-phase AC, 47 to 63Hz,
three-phase current output 3 × 230V AC, protection class IP 20.
Permitted ambient temperature during operation:
-10 °C to +40 °C.
Performance range MM420 3AC 400V
(for three-phase AC supply)
0.55 to 11kW rated motor power, 380 to 480V ±10% three-phase AC, 47 to 63Hz,
three-phase current output 3 × 400V AC, protection class IP 20. Permitted ambient
temperature during operation: -10 °C to +50 °C. The interference suppression filter
required to comply with the EMC basic interference suppression standard EN 500811 (residential and commercial uses) is integrated into the package as substructure
option. Power choke to comply with EN 61000-3-2 as additional component.
Observe performance reduction when using high clock frequencies!
Performance range MM430 3AC 400V
(for three-phase AC supply)
15 to 250kW rated motor power, 380 to 480V ±10% three-phase AC, 47 to 63Hz,
three-phase current output 3 x 400V AC, protection class IP 20.
Permitted ambient temperature during operation: -10 C to +50 °C. The interference
suppression filter required to comply with the EMC basic interference suppression
standard EN 50081-1 (industrial applications) is partially integrated. In order to attain
EMC requirements Class B a frequency inverter without filter should be selected. The
appropriate EMC-B filter is then required as an additional component.
Observe performance reduction when using high clock frequencies!
175
Roof Extract Fans / Accessories
Accessories
Frequency inverter
G110
MM420
The indicated ratings of the units are made for a quick selection. The exact dedication of an inverter in this catalogue is made by taking into account of the max. admitted current at a pulse frequency of 4kHz. It is important to know that at higher pulse
frequencies the supplied current of the inverter will be decreasing, with the possible
consequences of having to select a larger inverter unit. Also longer feed lines or additional radio frequency filters may lead to the choice of a larger inverter size.
Technical Data
for three-phase AC motors on the single-phase supply(1~ power) SINAMICS** G110
Parts of the unit Accessories
Unit
NominalNominalFrequency
Filter Control Line
current
power
inverter
class B
panel
choke
G110 1AC 230V
A (4kHz/+40 °C) kW
6SL3211-6SE6400-6SL3255-6SE64000.25KW EMV B
0.37KW EMV B
0.55KW EMV B
0.75KW EMV B
1.10KW EMV B
1.50KW EMV B
2.20KW EMV B
1.70
2.30
3.20
3.90
6.00
7.80
11.00
0.250AB12-5BA0integriert
0.370AB13-7BA0integriert
0.550AB15-5BA0integriert
0.750AB17-5BA0integriert
1.100AB21-1AA0integriert
1.500AB21-5AA0integriert
2.200AB22-2AA0integriert
0AA00-4BA0 3CC00-4AB3
0AA00-4BA0 3CC01-0AB3
0AA00-4BA0 3CC01-0AB3
0AA00-4BA0 3CC01-0AB3
0AA00-4BA0 3CC02-6BB3
0AA00-4BA0 3CC02-6BB3
0AA00-4BA0 3CC02-6BB3
Technical Data
for three-phase AC motors on the three-phase supply (3~ power) MICROMASTER** 420
Parts of the unit Accessories
Unit
NominalNominalFrequency
Filter Control Line
current
power
inverter
class B
panel
choke
MM420 3AC 400V
A (4kHz) kW
6SE6420-6SE6400-6SE6400-6SE64000.55KW EMV B
0.75KW EMV B
1.10KW EMV B
1.50KW EMV B
2.20KW EMV B
3.00KW EMV B
4.00KW EMV B
5.50KW EMV B
7.50KW EMV B
11.0KW EMV B
1.60
2.10
3.00
4.00
5.90
7.70
10.20
13.20
18.40
26.00
G110
MM420
0.552UD15-5AA12FB00-6AD0 0BP00-0AA0 3CC00-2AD3
0.752UD17-5AA12FB00-6AD0 0BP00-0AA0 3CC00-4AD3
1.102UD21-1AA12FB00-6AD0 0BP00-0AA0 3CC00-4AD3
1.502UD21-5AA12FB00-6AD0 0BP00-0AA0 3CC00-6AD3
2.202AD22-2BA12FS01-6BD0 0BP00-0AA0 3CC01-0BD3
3.002AD23-0BA12FS01-6BD0 0BP00-0AA0 3CC01-0BD3
4.002AD24-0BA12FS01-6BD0 0BP00-0AA0 3CC01-4BD3
5.502AD25-5CA12FS03-8CD0 0BP00-0AA0 3CC02-2CD3
7.502AD27-5CA12FS03-8CD0 0BP00-0AA0 3CC02-2CD3
11.002AD31-1CA02FS03-8CD0 0BP00-0AA0 3CC03-5CD3
Technical Data
MM430
for three-phase AC motors on the three-phase supply (3~ power) MICROMASTER** 430
Accessories
Unit
NominalNominalFrequency
Filter Control Filter Line
current
power
inverter
class A
panel
class B
choke
6SE6400-*
MM430 3AC 400V
A (4kHz) kW
6SE6430-6SE6400-6SE6400-6SE6400-6SL3000-°
32.00
15.02AD31-5CA0integriert
0BE00-0AA0 2FS03-8CD0 *3CC03-5CD3
38.00
18.52AD31-8DA0integriert
0BE00-0AA0 ***
*3CC04-4DD0
45.00
22.02AD32-2DA0integriert
0BE00-0AA0 ***
*3CC04-4DD0
62.00
30.02AD33-0DA0integriert
0BE00-0AA0 ***
*3CC05-2DD0
75.00
37.02AD33-7EA0integriert
0BE00-0AA0 ***
*3CC08-3ED0
90.00
45.02AD34-5EA0integriert
0BE00-0AA0 ***
*3CC08-3ED0
110.00
55.02AD35-5FA0integriert
0BE00-0AA0***
*3CC11-2FD0
145.00
75.02AD37-5FA0integriert
0BE00-0AA0***
*3CC11-2FD0
178.00
90.02AD38-8FA0integriert
0BE00-0AA0***
*3CC11-7FD0
180.40110.02UD41-1FA00BE32-5AA00BE00-0AA0–
°0CE32-3AA0
220.00132.02UD41-3FA00BE34-4AA00BE00-0AA0–
°0CE32-8AA0
265.80160.02UD41-6GA00BE34-4AA00BE00-0AA0–
°0CE33-3AA0
325.60200.02UD42-0GA00BE34-4AA00BE00-0AA0–
°0CE35-1AA0
419.80250.02UD42-5GA00BE36-0AA00BE00-0AA0–
°0CE35-1AA0
176
Roof Extract Fans / Accessories
Accessories
Frequency inverter
G110
** SINAMICS and MICROMASTER are registered trademarks of SIEMENS AG
*** In order to comply with EMC requirements class B, a frequency inverter without filter should be
chosen. The appropriate EMC-B filter is then additionally required.
MM420
a
Dimensions in mm, Subject to change
for three-phase AC motors on the single-phase supply (1~ power) SINAMICS** G110
b
c
G110
Unit
G110 1AC 230V
Frequency inverter
6SL3211-
Nominal power
kW a
b
0.25KW EMV B
0.37KW EMV B
0.55KW EMV B
0.75KW EMV B
1.10KW EMV B
1.50KW EMV B
2.20KW EMV B
0AB12-5BA0
0AB13-7BA0
0AB15-5BA0
0AB17-5BA0
0AB21-1AA0
0AB21-5AA0
0AB22-2AA0
0.25
0.37
0.55
0.75
1.10
1.50
2.20
c
150
90
116
150
90
116
150
90
131
150
90
131
160140142
160140142
181184152
a
Dimensions in mm, Subject to change
for three-phase AC motors on the three-phase supply (3~ power) MICROMASTER** 420
b
c
a
c
0.8
0.8
0.9
0.9
1.5
1.5
2.1
MM420
Unit
MM420 3AC 400V
Frequency inverter
6SE6420-
Nominal power
kW a
b
0.55KW EMV B
0.75KW EMV B
1.10KW EMV B
1.50KW EMV B
2.20KW EMV B
3.00KW EMV B
4.00KW EMV B
5.50KW EMV B
7.50KW EMV B
11.0KW EMV B
2UD15-5AA1
2UD17-5AA1
2UD21-1AA1
2UD21-5AA1
2AD22-2BA1
2AD23-0BA1
2AD24-0BA1
2AD25-5CA1
2AD27-5CA1
2AD31-1CA0
0.55
0.75
1.10
1.50
2.20
3.00
4.00
5.50
7.50
11.00
c
173
73
149
173
73
149
173
73
149
173
73
149
202
149
172
202
149
172
202
149
172
245
185
195
245
185
195
245185195
Dimensions in mm, Subject to change
for three-phase AC motors on the three-phase supply (3~ power) MICROMASTER** 430
b
Weight
kg
Weight
kg
1.0
1.0
1.0
1.0
3.3
3.3
3.3
5.0
5.0
5.0
MM430
Unit
Frequency inverter
Nominal power
MM430 3AC 400V
6SE6430-
kW a
–
–
–
–
–
–
–
–
–
–
–
–
–
–
2AD31-5CA0
2AD31-8DA0
2AD32-2DA0
2AD33-0DA0
2AD33-7EA0
2AD34-5EA0
2AD35-5FA0
2AD37-5FA0
2AD38-8FA0
2UD41-1FA0
2UD41-3FA0
2UD41-6GA0
2UD42-0GA0
2UD42-5GA0
15.0
18.5
22.0
30.0
37.0
45.0
55.0
75.0
90.0
110.0
132.0
160.0
200.0
250.0
245 185
520 275
520 275
520 275
650 275
650 275
1150 350
1150 350
1150 350
1450326
1450326
1533326
1533326
1533326
b
Weight
c
kg
195
245
245
245
245
245
320
320
320
356
356
545
545
545
5.7
17
17
17
22
22
75
75
75
116
116
176
176
176
177
Roof Extract Fans / Accessories
Accessories
Differential pressure sensor
EIP 01
Sensor with membrane for measuring the pressure, negative pressure or differential
pressure of nonaggressive gases.
Type
The differential pressure to be measured acts transformed into an output signal of
0...10 V by electronics (in SMD technology).
Application ranges
Volume flow regulators in centrifugal fans (with volume flow measuring device IMV)
in connection with a frequency inverter type G110, MM420, MM430, or a universal
regulator appliance type ERA 02-4000-5E in connection with a frequency regulator
Electrical connection and installation
The differential pressure sensor delivers a starting signal (0-10 V) by pressure increase
at the ”Plus” connection opposite pressure on the ”Minus” connection. Voltage
supply:
15-30 V DC or 24 V AC, ±15 %.
Pressure connections must point downward, tube connection ø5 mm.
Measuring accuracy
Null drift: ±0.75 %
Sum of linearity and hysteresis: ±1 %
Temperature drift zero point: ±0.3 % / 10 K
Temperature drift length of measurement: ±0.2 % / 10 K
Technical Data
Measuring Protection max. current
range
type
consumption
EIP
Pa
ca. mA
Overload Output signal
protectionprop.
Pa
V DC
Operating
temperature
°C
01-0200-12
01-0500-12
01-1000-12
01-2000-12
01-4000-12
20000
20000
20000
20000
20000
0 ... +50
0 ... +50
0 ... +50
0 ... +50
0 ... +50
0 - 200
0 - 500
0 - 1000
0 - 2000
0 - 4000
IP65
IP65
IP65
IP65
IP65
12
12
12
12
12
0-10
0-10
0-10
0-10
0-10
Dimensions in mm, Subject to change
50
ca. 500
4,5
70
Connection diagram
Pressure connections
Ø5 mm
ø5
8
16
Voltage supply
15...30 V DC
24 V AC ±10 %
brown
+~
+
p
yellow
Output
p
0 ... 10 V DC
white
=
^ ~
178
Roof Extract Fans / Accessories
Accessories
Universal control device
ERA 02
for installation in control cabinets
Digital control module for controlling pressure, air velocity or volume flow (PI
controller). For example, a transformer for fans is controlled via the 0-10 V output. The
device is designed for installation in control cabinets.
Type
Multi functional LC-display for actual and nominal values (m/s, hPa = mbar, 100 m³/h).
Menuassisted adjustment via three function keys.
Actual value input 0-10 V e.g. for:
- air speed sensors Type EIL in measuring ranges from 0-1 m/s and 0-10 m/s e.g. for:
Air velocity control in clean room technology
- Pressure sensors Type EIP... in measurement ranges 50-4000 Pa e. g. for:
Pressure control in canal systems of air conditioning systems (VVS),
Flow control in centrifugal fans with pressure tappings in the inlet cone.The control
module calculates the required flow (m³/h) from the differential measured pressure
between the surrounding level and inlet cone.
Max. volume flow 65000 m³/h
- Output 0-10 V e. g. for controlling a transformer.
- Failure message is output via display (internal/external) and relay programmable.
- External set value specification via potentiometer or 0-10 V signal.
- Specification of two set values (day/night), can be switched over externally or via
keyboard.
- Protection against unauthorised setting by keyboard code.
Application area
-P
ressure regulation for centralised ventilation systems and variable volume flow
systems for building air conditioning (VVS) e.g. in combination with a frequency
inverter or a commutation unit or a transformer and a pressure sensor.
-V
olume flow regulation for centrifugal fans (with measuring stub in the inlet cone)
e.g. in combination with a frequency inverter or a commutation unit or a transformer
or a mini-interface inverter and a pressure sensor and the volume flow volumeter.
-A
ir speed regulation for clean room systems, e.g. in combination with a transformer
and an air speed sensor.
Electrical connection and installation
Connection to 230 V, 50/60 Hz. The control module can be installed in a control
cabinet door. Admissible relative humidity: 85 %, noncondensing. Power supply for
the sensors included: +24 V, ±20 %, Imax = 70 mA.
_
_
qV = K p = K10 r2 p
Setting options
– Set values in the measurement range of the sensor (m/s, hPa = mbar), or in the
volume flow range of the fan (x 100 m³/h)
– Switch over of set value (day/night)
– Min./max. setting range
– Translation of performance curve (P component)
– Constant of integration can be selected (I component)
– Reversal of the effect of the control behaviour
– Rotation of the performance curve
– Switchover or programming of internal/external set value
– Sensor selection via keypad
– Programming for ”Filter fault”
– Keypad code
– K factor entry
(The K10-factor can be found in the current lists of our fan line)
Technical Data
Input
Out
ProtectionOperating Operating
max.
class
consumption
temperature
ERA
V
mA
VA
°C
02-4000-5E
0...10
10
IP 20
< 10
0 ... +55
179
Roof Extract Fans / Accessories
Accessories
Universal control device
ERA 02
for installation in control cabinets
99
106
Dimensions in mm, Subject to change
166.5
44
max. 105
10.5
159
Instrument panel window
Connection diagram
°C
V
mA
1
2
3
E2
4
(+) (–)
D+
24V
24V
D2
A1
GND
E1
L1 N PE
D–
GND
D1
D3
A2
GND
E2
5
°C
V
mA
E1
11 14 12 21 24 22
K1
Line
+
A
1 Out, 24 V DC
2 Input, Digital 1/2/3
3 Out, Analog 1/2
4 Input, Analog 0-10 V 1/2
5 Contact rating max. 5 A / 250  V AC
180
DATA
B GND
RS485
A2
2
(Imax=10mA)
+
A1
1
(Imax=10mA)
E2
4
+
E1
3
1 Out 0-10 V
2 Out 0-10 V
3 Input 0-10 V
4 Input 0-10 V
+
K2
Roof Extract Fans / Accessories
Accessories
Time control module
ETG 01
The time control module ETG is for the implementation of time-controlled discharged
air systems.
With the time switch module ETG all fans with integrated single phase AC motors (1~;
230 V; 50 Hz, 0...7 A) can be controlled.
Allocation is via the motor nominal current.
The operating intervals can be freely programmed, and if required, the second pre-set
speed stage can be changed. Programming the selected weekly cycle is possible by
using up to 42 programmable switching points.
The system is equipped with automatic changeover between summer and winter
times, as well as integrated motor protection for motors with thermal contacts.
Technical Data
Time switch module ETG for fans with single-phasen-AC motors 230 V; 50 Hz
Controlling
Nominal current
ETG A
01-0018-5Etime
01-0040-5Etime
01-0070-5Etime
1.8
4.0
7.0
300
Dimensions in mm, Subject to change
300
170
ETG 02
181
Roof Extract Fans / Description
Description
Example of type code
168
Description
The type code of every fan is composed as follows. Example:
RDM 31-3540-4D-10-..
Special:
- 25= Material code (KDM: PPs and PP-GF)
- 3G= Fan category “3“ Medium “G“
Index for motor size
Motor:
- D = 3-phase current
- A = 3-phase current (voltage adjustable)
- E = single phase current
- EC= Brushless-DC-motor with Commutation unit
- X = ATEX version
N° of poles:
- 2 = 2-poles
- 4 = 4-poles
- 6 = 6-poles
- 8 = 8-poles
- M = 4/4-poles
- N = 6/6-poles
- I = 4/6-poles
- G = 4/8-poles
- K = 6/8-poles
- H = 6/12-poles
Impeller diameter
(nominal 400mm)
Connecting diameter
(nominal 355mm)
Specification
- 1 = Standard
- 2 = Noise attenuated
Impeller geometry
- 2 = Type 20
- 3 = Type 30
Drive type
- A = External rotor motor
- M = IEC standard motor
Roof Extract Fans / Description
Description
Symbol / Unit / Description
f
Hz
Frequency
fc
Hz
Octave band frequency
IA/IN-
Startin current / Full load current
INA
Nominal motor current
LpAdB
A-weighted sound pressure level
LWAdB
A-weighted sound power level
LWA2dB
A-weighted casing sound power level
LWA3dB
A-weighted inlet sound power level
LWA8dB
A-weighted casing and free discharge sound power level (Outlet side)
LWfcdB
Sound power level at the octave bands
LWfc2dB
Casing sound power level at the octave bands
LWfc3dB
Inlet and duct sound power level at the octave bands (Inlet side)
LWfc8dB
Casing and free discharge sound power level at the octave bands (Outlet side)
LWreldB
Relative sound power level
LWrel2dB
Relative casing sound power level
LWrel3dB
Relative inlet sound power level (Inlet side)
LWrel8dB
Relative casing and free discharge sound power level (Outlet side)
mkg
Weight
N1/min
Fan speed
PekW
Power consumption
PNkW
Nominal motor power
t°C
Temperature of gas medium
um/s
Impeller tip speed
UV
Voltage
qVm³/h
Volume flow
qVNm³/h
Nominal volume flow
qVmaxm³/h
Maximal volume flow
qVoptm³/h
Volume flow at optimum efficiency
gpPa
Differential pressure
psFPa
Effective pressure free discharge (static pressure)
r1kg/m³
Density of gas medium at inlet
169
Roof Extract Fans / Description
Description
Gas media
The roof extract units are suitable for the transport of dust-free air and other nonaggressive gases and vapours.
The possible min. and max. temperatures of the conveying medium for each fan are
given with the specification sheet.
Plastic roof fans KDM are corrosion resistant and weather proof. They are designed
for extraction of aggressive gases or vapours (e.g. laboratories, suction hoods, galvanic processing etc.).
For an order or inquiry it is advisable to state the proposed usage and / or media to
be conveyed, so that it can be checked that the materials employed are suitable.
Protection
The roof fans are equipped with a guard at discharge. The intake side is not equipped
with a guard as a standard because usually there are installation parts connected.
The fans may only be put into operation if all necessary protection directives are met
and effective (Check with operation instructions).
The safety devices have to executed and installed according to DIN EN ISO 12100.
If the intake of the fan is freely accessible safety devices according to
DIN EN ISO 13857 have to be provided.
Safety instructions
Transport, fitting, electrical connection, start up, and maintenance are to be executed
following to the instructions given with the manual and by respecting the actual standards, directives, and safety rules.
Fitting instructions
verovent roof units are built for fitting to roof-mounted upstands. The fitting level
should be horizontal if at all possible. A slope angle of up to 20°, ATEX types up to 5°
would be admitted.
The roof fans of the lines RDA 31/32 and RDM 31/32 have to be installed in a way
that the 2 opposite discharge openings are parallel in line with the roof inclination.
Accessories
For the intake side, for the installation on roof top and for the extended function of the
motor a standardised scope of accessories is available.
Specification, technical data, and dimensions are available in the corresponding catalogues.
Electrical wiring
All roof extract unit are delivered ready for connection. Electrical connection takes
place in accordance with the enclosed operating instructions and observing the
relevant applicable local regulations and directives. Electrical power supply occurs
through the cable duct in the fan base frame to the terminal box. Every fan is accompanied by a connection circuit diagram.
You can also find the relevant circuit diagram online under:
www.nicotra-gebhardt.com.
Explosion-proofed Version (ATEX)
Roof fan in explosion proof specification correspond to the EU Directive 94/9/EG
(ATEX) category 3G. They are suitable for conveying explosive atmosphere of zone 2
and for installation in zone 2 or in an area which is not under explosion hazard. The
maximum conveying temperature is +40 °C.
The installation of roof fans on an inclined roof is allowed until an inclination of 5° to
vertical.
170
Roof Extract Fans / Description
Description
Drive types
Nicotra Gebhardt external-rotor motors
Integrated motors that have proved themselves in practice are used for the drive.
Deep groove ball bearings that have been checked to be quiet and maintenance free
ensure a long service life.
To protect against thermal overload, all motors are equipped with thermal contacts.
This thermal overload protection must be effective during operation in order for the
factory guarantee to apply in case of damage. Please be sure to study the associated
circuit diagram for the fan regarding the technical inclusion of thermal contacts, also
available online at www.nicotra-gebhardt.com.
IEC standard motors
The standard fan drive consists of flanged IEC motors, execution B5, protection class
IP 55, heat class F. There is single-speed, multi-speed, and speed controlled motors
available.
According to their execution the motors are equipped with either PTC thermistors
or with thermo contacts as a standard. Only roof fan series „KD“ and „HD“ are not
equipped with PTC thermistors or thermo contacts. In connection with a triggering
unit, a motor protection unit, or a speed control unit with integrated protection, each
fan drive will be protected against thermal overload.
This thermal overload protection has to be in place and to be effective during operation in order to make the warranty applying in case of damage.
Please respect the instructions of the wiring diagram supplied with every fan. If these
instructions are missing they can be down loaded from www.nicotra-gebhardt.com.
Brushless-DC-motors with commutation unit
Brushless-DC-motors are DC motors that make use of developments in semiconductor technology to attain optimum use of energy, even in partial load operation.
With that Brushless-DC-motors provide the drive with the greatest energy efficiency
for fans. As the motor is operated as a standard with performance electronics, it is
predestined from the start for speed regulation. No other fan drive provides a comparable efficiency in the partial load area.
The motors do not have any direct temperature monitoring by thermal contacts or
thermistors. Motor protection is via current monitoring contained in the electronic
commutation unit.
The single-phase supplied commutation unit with variable output voltage and frequency is optimal coordinated with the operation of the Nicotra Gebhardt BrushlessDC-motors.
Explosion-proofed Version (ATEX)
The use of electronic controllers and inverters for speed control of explosion
proofed emotors is non admissible!
explosion proofed external-rotor-motors
Only proven external rotor motors of protection class IP 44 and insulation class F are
used. The motors are equipped with maintenance free closed groove ball bearings
lubricated for lifetime. They comply to ignition type EEX e II T3 (increased safety „e“,
according to EN 60079-7, EC certification labelled II 2G EEx e II T3) and certified for
temperature class T1 to T3. The motors are suitable for operation in explosion hazard
areas of zone 2.
The fan speed can be reduced by voltage using a transformer for reduction. The feed
voltage may not be lower than 115 V. (admitted range 115 V to 400 V).
In order to protect the motors against overheating PTC thermistors are provided. The
PTC unit has to be connected to a ATEX certified PTC switch labelled Ex II (2)G.
explosion proofed IEC Standard motors
The drive is realised with flanged standard motors type B5, protection class IP 55 and
thermal class F (used to B). They comply to ignition type EEX e II T3 (increased safety
„e“, according to EN 60079-7, EC certification labelled II 2G EEx e II T3) and certified
for temperature class T1 to T3.
In order to maintain the explosion safety level in operation, suitable overcurrent protection has to be provided.
171
Roof Extract Fans / Description
Description
Performance data
The performance curves are obtained using an inlet side test chamber in accordance
with ISO 5801 “Industrial fans - Performance testing using standardized airways“. The
performance grids show the effective pressure increase psF (Pressure increase obtained from the fan in free-field conditions) as a function of the flow volume qV.
Reference media density: r1 = 1.15 kg/m³.
1 = Fan under test
2 = Chamber
3 = Grille
4 = Variable throttle
5 = Auxiliary fan
6 = Honeycomb straightener
7 = Standard intake nozzle
1
2
t1
3
4
5 6
psF
7
ta
pa
pa
qV = f(pa)
Roof units are built to tolerances of Class 2 of DIN 24166 “Fans, TechnicalSpecifications”.
Hence, the following deviations from the catalogue values are permitted:
Flow volume
qV
±5 %
Pressure increase
psF
±5 %
Absorbed power
Pe
+8 %
Sounds
Measurement and evaluation of noise levels are in accordance with DIN 45635-38
„Sound measurements on machines; fans“.
Duct method – inlet side
The duct measurement method is described in DIN EN ISO 5136.The sound power
emanating from the roof unit into the inlet-side duct is measured.
Envelope method – discharge side
The envelope method is described in DIN 45635-1 and -38 (BS 848 Part 2).
A cuboid envelope is assumed at a fixed distance surrounding the roof unit, with
measuring points lying on its planes.
1 = Soundabsorbing room
2 = Microphones for envelopemeasurement
3 = Fan under test
4 = Measuring duct
5 = Microphone with attachmentfor duct measurement
6 = Soundabsorbing end cover
7 = Variable throttle
1
2
3
5
4
Lp3/4
Lp7/8
pa
172
6
7
Roof Extract Fans / Description
Description
Sounds
At the fan curves the emission value of the A-weighted sound power level LWA is given
and are valid for both inlet (LWA3) and discharge (LWA8).
For the fans RDA/RDM, the sound values of the integrated dis­charge dampers are
considered.
For more exact calculations when determining the required attenuation, the sound
power level in the octave bands is important.
The relative sound power levels at intake and discharge, at various duty points, can
be read from the corresponding tables for each fan range.
LWfc = LWA + LWrel
The sound power level is the specific and objective noise parameter for every
machine. Only with these data sound comparisons between machines can be
made. For this reason only sound power level data are shown.
For fans classified to tolerance class 2 according to DIN 24166 a maximum deviation of the sound power level value of 4 dB is specified.
a
b
10
L
r
30
dB
20
r
1
5
m 10
Often the sound pressure value at a determined distance from a fan is required. In
fact this value depends from surrounding conditions (reflections, absorption, sound
propagation possibilities).
The sound pressure level at a distance of 4 meters can for instance be lower of 16 to
23 dB to the corresponding sound power level.
The A-weighted sound pressure value LpA to be expected at a certain distance from
the fan can be evaluated approximately with the adjacent diagram.
The diagram shows 2 curves covering the field where the relative sound power level
data at various distances usually is situated. For a sound propagation in a hemisphere
shape and without reflections the curve “a” can be used. For more uncertain conditions – usual in practice – the use of the curve “b” is recommended.
The determination of the sound pressure at fan intake can only be made if the local
acoustic properties are known. (see z.B. VDI-Richtlinie 2081).
173
Roof Extract Fans / Description
Description
Quality management system
DIN EN ISO 9001
Nicotra Gebhardt quality is the result of rigorously pursuing business policy goals,
which specify that Nicotra Gebhardt products must display properties and characteristics that are clearly above average when compared to similar products.
This maxim, which has applied since the company was founded, lead in April 1985 to
the auditing and certification of the existing quality assurance system. In subsequent
years, it was adjusted to comply with changed international and European standards.
Modern production procedures, monitored by our quality management system, ensure a high level of repeatability in manufacturing.
The tight tolerances allow high levels of data security for our products.
Information on machine safety
The fans contained in this catalogue are not machines in the spirit of EC Machinery
Directive and receive a Declaration of Incorporation . With reference to the building
product directive they are provided with a CE symbol and associated declaration of
conformity.
The assessment of danger arising from the fan and requisite safety measures occurred resulting from the VDMA (Association of German Mechanical Engineering Institutions) standard sheet 24167: Fans; safety requirements.
The Operating Instructions give which safety measures are still necessary on assembly to ensure that the fans comply with the EC Machinery Directive 2006/42/EG.
Notes on EMV Directive
Nicotra Gebhardt Roof Fans with EC Motors and the Electronic Commutation Unit
necessary for their operation comply in their construction with the EMV Directive
EMV 2004/108/EWG. The Operating Instructions give the appropriate measures to be
carried out for installation which are in keeping with the conditions of the EMV Directive. The observance of the EMV Directive can only be maintained for this product if
it is directly connected to the mains. If it is incorporated as part of another installation
with other components e.g. those subject to engineering regulations or operated in
a manner not in accordance with the Operating Instructions, it is the manufacturer or
operator of that installation who is responsible for the observance of the EMV Directive.
Notes on catalogue data
We reserve the right to change the dimensions and technical data contained in this
catalogue in the event that our product is further developed. All details correspond to
the version on the date of printing.
Service
Our mobile service
offer for intervention on the site in combination with our standby team at the workshop will assure an efficient support to all requirements you may have.
Make just a phone call and our service team will help you to solve your problem fast
and reliably.
Service Hotline
Phone
Fax
+49 (0)7942 / 101-384
+49 (0)7942 / 101-385
The part shop offered by Nicotra Gebhardt
The easy-to-handle online shop enables you to identify instantly every spare part. A
graphically supported list makes your selection easy. So an online service is available
which will help you to make your repair as simple as possible.
www.nicotra-gebhardt.com
174
Notes
175
nicotra-gebhardt.com
AUSTRALIA
65 Yale Drive,
Epping, VIC 3076
Phone +61 3 9017 5333
Fax
+61 3 8401 3969
E-mail [email protected]
BELGIUM
Haeghensgoed, 13 - 00/01
9270 Laarne
Phone +32 (0)9-336-00-01
Fax
+32 (0)9-336-00-05
E-mail [email protected]
CHINA
88 Tai‘An Road, XinQiao, ShiJi, Panyu
Guangzhou 511450
PR CHINA
Phone +86 (0)20-2293 5700
Fax
+86 (0)20-2293 5701
E-mail [email protected]
FRANCE
Leader's Park Bat A1
3 chemin des Cytises
69340 Francheville
Phone +33 (0)4 72 79 01 20
Fax
+33 (0)4 72 79 01 21
E-mail [email protected]
GERMANY
Gebhardtstraße 19-25
74638 Waldenburg
Phone +49 (0)7942 101 0
Fax
+49 (0)7942 101 170
E-mail [email protected]
GREAT BRITAIN
Unit D, Rail Mill Way
Parkgate Business Park
Rotherham
South Yorkshire
S62 6JQ
Phone +044 01709-780760
Fax
+044 01709-780762
E-mail [email protected]
INDIA
Plot no 28F & 29, Sector-31,Kasna,
Greater Noida-201 308 U.P (India)
Phone +91 120 4783400
Phone +91 22 65702056 (Mumbai)
Phone +91 80 25727830 (Bangalore)
E-mail [email protected]
ITALY
Via Modena, 18
24040 Zingonia (BG)
Phone +39 035 873 111
Fax
+39 035 884 319
E-mail [email protected]
MALAYSIA
Lot 1799, Jalan Balakong
Taman Perindustrian Bukit Belimbing
43300 Seri Kembangan
Selangor
Phone +603 8961-2588
Fax
+603 8961-8337
E-mail [email protected]
SPAIN
Ctra. Alcalá-Villar del Olmo, Km. 2,830
28810 Villalbilla-Madrid
Phone +34 918-846110
Fax
+34 918-859450
E-mail [email protected]
SINGAPORE
3, Science Park Drive, # 04-07, The Franklin
Singapore Science Park 1
Singapore 118223
Phone +65 6265 1522
Fax
+65 6265 2400
E-mail [email protected]
Nicotra Gebhardt Germany
Nicotra Gebhardt Italy
Nicotra Gebhardt GmbH
Gebhardtstraße 19-25
74638 Waldenburg
Germany
Phone +49 (0)7942 101 0
Fax +49 (0)7942 101 170
E-Mail [email protected]
Nicotra Gebhardt S.p.A
Via Modena, 18
24040 Zingonia (BG)
Italy
Phone +39 035 873 111
Fax +39 035 884 319
E-Mail [email protected]
SWEDEN
Kraketorpsgatan 30
43153 Mölndal
Phone 0046 101-302600
Fax
0046 31-878590
E-mail [email protected]
THAILAND
6/29 Soi Suksawadi 2, Moo 4, Suksawadi Road,
Kwang Jomthong, Khet Jomthong,
Bangkok 10150
Phone +662 476-1823-6
Fax
+662 476-1827
E-mail [email protected]
UNITED STATES
PO BOX 900921
Sandy, Utah 84090
Phone 001(801) 733-0248
Fax
001(801) 315-9400
Mobile 001(801) 682 0898
E-mail [email protected]
http://www.gebhardtfans.com/
EN-TD3-REF-5 – PDF2-January2014
Nicotra Gebhardt worldwide