sensore rilevatore perdite gas refrigerante / refrigerant gas
Transcript
sensore rilevatore perdite gas refrigerante / refrigerant gas
Cod. +050003515 - rel. 1.4 - 29.09.2015 DPWL*: sensore rilevatore perdite gas refrigerante / refrigerant gas leak sensor The purpose of this guide is to describe the minimum operations required for quick configuration and setup of the DPWL refrigerant gas sensor supplied with 24 Vac transformer. Perform the configuration operations shown in the list marked (those marked – should be skipped) under the “Type of configuration required” column, depending on the controller used or type of connection. For further information see instruction sheet +050003510 or technical manual +0300035EN. La presente guida ha lo scopo di fornire le operazioni minime da eseguire per una veloce configurazione e messa in funzione del sensore rivelatore di gas refrigerante DPWL alimentato con trasformatore 24Vac. Eseguire la configurazione delle operazioni riportate nell’elenco contraddistinte dal segno (quelle evidenziate con il segno – non sono da fare) seguendo la colonna del “tipo di configurazione da eseguire” in accordo al controllo o tipo di collegamento. Per maggiori informazioni consultare il foglio istruzioni +050003510 o manuale tecnico +0300035EN. Tipo di configurazione da eseguire pCO5/PVPRO/ IR33 Univ. pRACK /pCO3 (collegamento PWPRO (collega(collegamento Funz. ingresso analogico mento seriale ingresso analogico) autonomo 4…20mA) RS485 Modbus) Vedi nota 1 Conf. Elenco delle azioni da fare J1-J2 Semiconductor sensor R22-R134a-R404a-R407aR407c-R407f-R410a-R507a-R290-CO2 version J3 Infrared sensor CO2 version P1 TP (Alarm) Audible Alarm and Relay Set Point Voltage Test Point 12 ABCD ABCD SW1 SW2 Addressing 3 SW1 SW2 P3 5 10 5 10 Volts CN3 AC Select G + – J1 CN1 Modbus CN2 J3 J2 N/C I Output Signal N/O DC Select 0 0 1 2 5 10 5 10 CN4 0V V+ 12-24 Vdc GNX V IB AR M TP3 (0V) LE A L LE A L J7 J8 J9 J10 J3 CN3 I Output Signal N/C 2 N/O 1 COM 0 COM 0V V+ 12-24 Vdc GNX V 0 AR TP3 (0V) AC Select G + – J1 CN1 Modbus CN2 SPAN AU D AU D IB M Volts J7 J8 J9 J10 J2 12 4-20mA CN4 SPAN DC Select P4 RED LED TP2 (Vs) P3 Board Ground Plane Test Point 3 B 0 GREEN LED 4-20mA ADJ V Reset Addressing 6 45 7 EF 01 TP1(Alarm) Zero RX 2345 J4 Alarm 6 45 7 EF 01 P2 –V 6789 P2 TP2 (Vs) Sensor Voltage Test Point 2345 RED LED P4 6789 GREEN LED P1 Delay SIGNAL 89A Semiconductor (SC) Sensor PC board J5 J6 TX +V B 0 Infrared (IR-RS) Sensor PC board J4 Delay Alarm Reset 89A J5 J6 Fig. 1 Fig. 2 Legenda: SW1 and SW2 Modbus Addressing J4 Reset Jumper CN3 Relay Connector J3 Audible Alarm Jumper ADDR SW1 SW2 (DEC) (LSB) (MSB) ON (Then OFF) OFF D00 0 0 D01 D02 : D17 : 247 1 0 : 1 : 7 0 1 : 1 : 7 Valid Addresses 248 : 255 8 : F F : F Reserved Addresses Normally Open N/O J4 Normal Operation Delay jumper Sounder and Relay Delay J5-J6 J5 J6 OFF OFF 0 (no delay) ON OFF 1 minute OFF ON 5 minutes ON ON 10 minutes Legenda: On=Presente Off=Non Presente Configura indirizzo seriale: SW1 seleziona gli indirizzi da 1 a 15. SW2 moltiplica il valore impostato su SW1SW1 per un valore 16. Vedi tabella 2 SW2 Formula: ID = SW1+(SW2 x 16) Esempio: ID = 17 SW1=1; SW2=1 Collegare il cavo seriale RS485 prestando attenzioCN4 ne ai collegamenti Defaul Baud rate 9600. Verificare che il software preveda la gestione del sensore. Collegamenti uscita digitale N/O – COM CN3 (max 1A/24V) CN2 Collegare uscita corrente tra 0V e I (vedi Nota 3) Alimentare il sensore con trasformatore esterno 12…24 Vac 3 VA (Se si alimenta solo sensore si possono usare i seguenti trasformatori: CN1 TRA12VDE00 – pannello, TRADR4W012 – guida omega, TRASP3E120 – a spina); J1-J2 J3 - J5-J6 - - - - - - - - - - - Vedi nota 2 Tab. 1 CN3 COM Common N/C Normally Closed da fare Legenda Note: Conf. List of operations Reset N/O COM N/C Reserved Address Configura il tipo di alimentazione Vac J1=PRESENTE - J2=NON PRESENTE Configura il tipo di alimentazione Vdc J1= NON PRESENTE - J2= PRESENTE Configura il segnalatore acustico J3= PRESENTE = attivo J3= NON PRESENTE = disattivo Impostazione del ritardo allarme selezionando il jumper seguendo la tabella sotto riportata. Se si ha un collegamento seriale RS485 selezionare J5=Off e J6=Off, impostando il ritardo da parametro via seriale. - non fare Set the type of power supply Vac J1=PRESENT - J2=NOT PRESENT Set the type of power supply Vdc J1= PRESENT - J2= NOT PRESENT Enable audible signal J3= PRESENT = enabled J3= NOT PRESENT = disabled Set the alarm delay by setting the jumpers shown in the table below. If an RS485 serial connection is used, select J5=Off and J6=Off, setting the delay by parameter via the serial connection. Delay jumper J5 J6 OFF OFF ON OFF OFF ON ON ON Key: On=Present Type of configuration required pCO5/PVPRO / IR33 Univ. (analogue PWPRO (RS485 Stand-alone input connection) Modbus serial operation See note 1 connection) - - - - - - - - - - - - See note 2 Sounder and Relay Delay 0 (no delay) 1 minute 5 minutes 10 minutes Off=Not present Set serial address: SW1 selects addresses from 1 to 15. SW2 multiplies the value set on SW1 by value SW116. See table 2 SW2 Formula: ID = SW1+(SW2 x 16) Example: ID = 17 SW1=1; SW2=1 Carefully connect the RS485 serial cable. Default CN4 baud rate 9600. Make sure the software allows management of the sensor. N/O – COM digital output connections CN3 (max 1A/24V) Connect current output between CN2 0V and I (see Note 3) Power up the sensor with 12-24 Vac 3 VA external transformer (if only powering the sensor the following transformers can be used: CN1 TRA12VDE00 – panel, TRADR4W012 – DIN rail, TRASP3E120 – plug-in); Tab. 1 to do Key Usato con controllo IR33 Universale il valore espresso a display in ppm per la versione semiconduttore è x 10, per la versione infrared x100; È possibile alimentare in DC anche prelevando l’alimentazione da pRACK dai terminali +VTerm e GND (J24) In questo caso DPWL - J1 non presente, J2 presente; J7 – J8 – J9 – J10 si configurano solo se si desidera l’uscita in tensione (vedi manuale tecnico). pRack /pCO3 (4 to 20 mA analogue input connection) Note: - not to do When used with the IR33 Universal controller the value on the display in ppm for the semiconductor version is x 10, for the infrared version is x100; DC power is also available from the pRack via the +VTerm and GND (J24) terminals. In this case, DPWL - J1 is not present, J2 is present; J7 – J8 – J9 – J10 are only configured for voltage output (see the technical manual). Changing the baud rate from 9600 (default) to 19200 Cambio del baud rate da 9600 (default) a 19.200 J1 and J2 Power Supply P1-P4 Adjustment Pots Selection Jumper AC Power Selected DC Power Selected J5 and J6 Delay Jumper for Audible Alarm and Relay J5 P1 Adjusts Alarm Setpoint for Audible Alarm and Relay P2 Adjusts Zero Level Voltage for Output Signal J6 0 0 Minutes (No Delay) 1. 2. 3. 4. Posizionare i commutatori rotativi SW1=F e SW2=F; Cortocircuitare per un breve attimo il jumper J4; Rimpostare l’indirizzo desiderato di SW1 e SW2; Per verificare se è stato cambiato, togliere l’alimentazione e verificare se alla riaccensione il led rosso esegue un lampeggio (conferma dell’avvenuto cambiamento del parametro); 1. 2. 3. 4. Switch rotary selectors SW1=F and SW2=F; Jumper terminal J4 for a brief moment; Reset the desired address on SW1 and SW2; To make sure that the setting has been changed, power down and when restarting check that the red LED flashes (confirming the parameter has been changed); Changing the alarm threshold in ppm ON J1 OFF J1 OFF J2 CN1 12-24 Vac P3 CN1 0V V+ 12-24 Vdc G Modbus J6 1 1 Minutes Delay Per cambiare il livello di soglia allarme ppm 1. Collegare il multimetro in volts DC tra TP3 (0V–GND) e TP1 (alarm). 2. Ruotare il trimmer P1 nella scala da 0 a 5Vdc selezionando il valore ( scala lineare). Per il calcolo applicare la seguente formula: ON J2 P4 CN4 Modbus Connector G + – J5 J5 Adjusts Output Signal Span Non-inverting Modbus Signal TxD+/RxD+ – Non-inverting Modbus Signal TxD–/RxD– J5 Adjusts 4-20 mA Current Output J6 5 Minutes Delay V(TP1-TP3) = 10 Minutes Delay 10 GNX 0 Volt, Ground J7 0-5 V Output GNX V I Output Signal V 0-10 V Output 1-5 V Output 2-10 V Output I ppm (set point desiderato) x 5V max valore fondo scala ppm Es. sensore ver. semiconduttore con set point a 500 ppm V(TP1-TP3) = 500 x 5 max valore fondo scala ppm: Semiconduttore = 1000; Infrared = 10000. Se possibile, cambiare la soglia allarme da supervisore o parametri modbus. Current Output, 4-20 mA J8 J9 J10 Address SW1 SW2 Selection 0 0 0 Reserve 1 1 0 Address 1 2 2 0 Address 2 3 3 0 Address 3 4 4 0 Address 4 5 5 0 Address 5 6 6 0 Address 6 7 7 0 Address 7 8 8 0 Address 8 9 9 0 Address 9 10 A 0 Address 10 Address SW1 SW2 Selection 11 B 0 Address 11 12 C 0 Address 12 13 D 0 Address 13 14 E 0 Address 14 15 F 0 Address 15 16 0 1 Address 16 17 1 1 Address 17 18 2 1 Address 18 19 3 1 Address 19 20 4 1 Address 20 21 5 1 Address 21 V(TP1-TP3) = ppm (set point desiderato) x 5V max valore fondo scala ppm E.g. semiconductor ver. sensor with set point 500 ppm V(TP1-TP3) = 500 x 5 = 2,5 V 1000 = 2,5 V 1000 max. full scale ppm value: Semiconduttore = 1000; Infrared = 10000. It is possible change the threshold alarm by supervisor or modbus parameter. Esempio selezione indirizzo ID (SW1-SW2) J7-J10 Output Jumper for CN2 Output Signal Connector Ground (Isolated from 0V) + J6 5 1. Connect the multimeter with DC voltage setting between TP3 (0V–GND) and TP1 (alarm). 2. Turn trimmer P1 on the scale from 0 to 5 Vdc to select the value (linear scale). For the calculation apply the following formula: Example address ID settings (SW1-SW2) Address SW1 SW2 Selection ……… …. …… …………. 246 6 F Address 246 247 7 F Address 247 248 8 F Reserve 249 9 F Reserve 250 A F Reserve 251 B F Reserve 252 C F Reserve 253 D F Reserve 254 E F 9600 Baud rate 255 F F 19200 Baud rate Tab. 2 Address SW1 SW2 Selection 0 0 0 Reserve 1 1 0 Address 1 2 2 0 Address 2 3 3 0 Address 3 4 4 0 Address 4 5 5 0 Address 5 6 6 0 Address 6 7 7 0 Address 7 8 8 0 Address 8 9 9 0 Address 9 10 A 0 Address 10 Address SW1 SW2 Selection 11 B 0 Address 11 12 C 0 Address 12 13 D 0 Address 13 14 E 0 Address 14 15 F 0 Address 15 16 0 1 Address 16 17 1 1 Address 17 18 2 1 Address 18 19 3 1 Address 19 20 4 1 Address 20 21 5 1 Address 21 Address SW1 SW2 Selection ……… …. …… …………. 246 6 F Address 246 247 7 F Address 247 248 8 F Reserve 249 9 F Reserve 250 A F Reserve 251 B F Reserve 252 C F Reserve 253 D F Reserve 254 E F 9600 Baud rate 255 F F 19200 Baud rate Tab. 2 Esempio schemi di collegamento / Example connection diagrams pCO5 / PVPRO / PWPRO (collegamento RS485 Modbus) / pCO5 / PVPRO / PWPRO (RS485 Modbus connection) Controllo / Controller Sensore / Sensor J5 J6 Alarm TP1 Alarm TP1 BC5 B5 BC4 B4 +VDC VOLTS GND G0 Nota: non collegare il trasformatore a terra / Not connec the transformer to ground – + G0 G Controllo / Controller J5 J6 SENSOR LD 2 LD 2 RED TP2 TP3 0V CN4 AC J1 DC CN1 GND + – MODBUS TX/TR CN2 J2 0V V+ GNX LD 2 LD 2 GREEN RED SW1 SW2 ZERO P2 P4 4-20mA TP3 0V J7 J8 J9 J10 CN4 AC 5 10 5 10 J1 GND + – CN1 MODBUS TX/TR CN2 DC 0 0 1 2 VOLTS CN3 SPAN P3 TP2 Vs J7 J8 J9 J10 5 10 5 10 0 0 1 2 VOLTS CN3 J3 Carico massimo 1A/24V / Max. load 1A/24V NO6 NO5 C4 NO4 Y4 ID1 • Per la configurazione dei controlli seguire le istruzioni riportate nei relativi manuali; • è possibile collegare il sensore contemporaneamente l’uscita analogica di un controllo, l’uscita digitale per gestire un allarme locale e un collegamento seriale RS485 Modbus con il supervisore. J3 J2 0V V+ 0V V I N/O COM N/C RELAY 31 32 33 34 35 36 25 26 27 28 29 30 V I N/O COM N/C GND +B1 RELAY • For configuration of the controllers follow the instructions shown in the corresponding manual; • the sensor can be connected at the same time with the analogue output to a controller, the digital output to manage a local alarm and RS485 Modbus serial connection to the supervisor. B1 GND Trasformatore 24Vac / 24Vac transformer 24Vac transformer lineline Linea 230Vac /230Vac 230Vac C1 J4 Alarm TP1 P4 4-20mA SPAN P3 Vs Linea 230Vac / 230Vac line P1 Alarm P1 Alarm SW1 SW2 ZERO P2 Trasformatore 24Vac / 24Vac transformer J4 Alarm TP1 GREEN G0 NB: collegare un solo dispositivo Master alla rete dei sensori / NB: connect just one Master device to sensor network Fig. 4 Funzionamento autonomo / Stand-alone operation Sensore / Sensor Sensore / Sensor Sensor G Trasformatore 24Vac / 24Vac transformer Linea 230Vac / 230Vac line Fig. 3 ir33 universale (collegamento Ing. Analogico 4...20 mA) / ir33 universal (4 to 20 mA analogue input connection) SENSOR J4 J3 seriale RS485 (Modbus®) G0 Nota: non collegare il trasformatore a terra / Not connec the transformer to ground Trasformatore 24Vac / 24Vac transformer Linea 230Vac / 230Vac line J5 J6 J2 GND G Trasformatore 24Vac / 24Vac transformer Linea 230Vac / 230Vac line J24 J2 0V V+ 0V V I N/O COM N/C RELAY fino a 247 dispositivi/ up to 247 devices B1 G J1 J3 Y3 CN3 Y2 GND + – CN1 MODBUS TX/TR CN2 Y1 DC J3 GND B3 B2 J2 B1 J24 GND G0 J2 0V V+ 0V V I N/O COM N/C RELAY +Vterm J1 +5 VREF J3 B MS c ard BC5 J1 VOLTS CN3 B5 GND + – CN1 MODBUS TX/TR CN2 DC Fie l dB u s c ard 0 0 1 2 BC4 0 0 1 2 input: 24 V 50...60 Hz / 28...36 V max. power: 45 VA/20 W 5 10 5 10 B4 AC J7 J8 J9 J10 +VDC fi e l d c a rd CN4 GND TP3 0V B3 input: 24 V / ; 50 to 60 Hz max. power: 40 VA/15W 5 10 5 10 AC SPAN P3 B2 CN4 J1 TP2 G TP3 0V P4 4-20mA Vs J7 J8 J9 J10 J13 J10 B1 SPAN P3 Vs J9 J12 J25 BMS2 J26 FBus2 Supervisore / Supervisor SW1 SW2 ZERO P2 P4 4-20mA TP2 RED +5 VREF SW1 SW2 ZERO P2 GREEN GND Controllo / Controller Controllo +Vterm RED J11 pLAN G0 LD 2 LD 2 G LD 2 GREEN LD 2 NO3 SENSOR C1 SENSOR J4 P1 Alarm NO2 J4 P1 Alarm VG0 J5 J6 VG Sensore / Sensor NO1 pRack / pCO3 (collegamento Ing. Analogico 4...20 mA) / pRack / pCO3 (4 to 20 mA analogue input connection) G G0 G G0 Trasformatore 24Vac / 24Vac transformer 24Vac transformer Trasformatore 12/24 Vac / 12/24 Vac transformer 230Vac line Linea 230Vac / 230Vac line CAREL Industries HQs Via dell’Industria, 11 - 35020 Brugine - Padova (Italy) Tel. (+39) 0499716611 – Fax (+39) 0499716600 – www.carel.com – e-mail: [email protected] Fig. 5 Linea 230Vac / 230Vac line CAREL reserves the right to modify the features of its products without prior notice. Fig. 6 Cod. +050003515 - rel. 1.4 - 29.09.2015