Data sheet for SINAMICS G120C
Transcript
Data sheet for SINAMICS G120C
Data sheet for SINAMICS G120C Ordering data 6SL3210-1KE15-8AB1 Client order no. : Item no. : Order no. : Consignment no. : Offer no. : Project : Remarks : Rated data General tech. specifications Input Power factor λ 0,70 ... 0,85 Number of phases 3 AC Offset factor cos φ 0,95 Line voltage 380 ... 480 V +10 % -20 % Efficiency η 0,97 Line frequency 47 ... 63 Hz Sound pressure level (1m) 52 dB Rated current (LO) 7,40 A Power loss 0,09 kW Rated current (HO) 6,00 A Ambient conditions Output Cooling Raffreddamento ad aria mediante ventilatore integrato 400 V Cooling air requirement 0,005 m³/s Rated power (LO) 2,20 kW Installation altitude 1000 m Rated power (HO) 1,50 kW Ambient temperature Rated current (IN) 6,00 A Operation -10 ... 40 °C (14 ... 104 °F) Rated current (LO) 5,60 A Transport -40 ... 70 °C (-40 ... 158 °F) Rated current (HO) 4,10 A Storage -40 ... 70 °C (-40 ... 158 °F) Max. output current 8,20 A Pulse frequency 4 kHz Output frequency for vector control 0 ... 240 Hz Output frequency for V/f control 0 ... 650 Hz Number of phases 3 AC Rated voltage Relative humidity Max. operation 95 % a 40 °C (104 °F), condensa e formazione di ghiaccio non ammesse A causa delle disposizioni di legge, a partire dal firmware V4.7 la frequenza max. di uscita è limitata a 550 Hz. Overload capability Low Overload (LO) 150 % corrente di carico base IL per 3 s, successivamente 110 % corrente di carico base IL per 57 s in un tempo di ciclo di 300 s High Overload (HO) 200 % corrente di carico base IH per 3 s, successivamente 150 % corrente di carico base IH per 57 s in un tempo di ciclo di 300 s Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Page 1 of 2 generiert / generated Thu Mar 26 16:24:47 CET 2015 Data sheet for SINAMICS G120C Ordering data 6SL3210-1KE15-8AB1 Mechanical data Connections Signal cable Degree of protection IP20 / UL open type Size FSA Net weight 1,70 kg Width 73,0 mm Version Morsetti a vite innestabili Height 196,0 mm Conductor cross-section 1,00 ... 2,50 mm² (16 ... 14 AWG) Depth 203,0 mm Inputs/ outputs Standard digital inputs Conductor cross-section 0,15 ... 1,50 mm² (28 ... 16 AWG) Line side Motor end Version Morsetti a vite innestabili Conductor cross-section 1,00 ... 2,50 mm² (16 ... 14 AWG) DC link (for braking resistor) Number 6 Switching level: 0→1 11 V Version Morsetti a vite innestabili Switching level: 1→0 5V Conductor cross-section 1,00 ... 2,50 mm² (16 ... 14 AWG) Max. inrush current 15 mA PE connection Sulla custodia con vite M4 Fail-safe digital inputs Number Max. motor cable length 1 Digital outputs Number as relay changeover contact 1 Output (resistive load) DC 30 V, 1 A Number as transistor 1 Output (resistive load) DC 30 V, 1 A Analog/ digital inputs Number 1 (Ingresso differenziale) Analog outputs Number 1 (Uscita non isolata) PTC/ KTY interface 1 ingresso per sensore di temperatura, sensori collegabili PTC, KTY e Thermo-Click, con precisione ±5 °C Shielded 50 m Unshielded 100 m Communication Communication RS485 Closed-loop control techniques V/f linear / square-law / parameterizable Sì V/f with flux current control (FCC) Sì V/f ECO linear / square-law Sì Sensorless vector control Sì Vector control, with sensor No Encoderless torque control No Torque control, with encoder No Standards Compliance with standards CE, cULus, c-tick CE marking Direttiva EMC 2004/108/CE, Direttiva sulla bassa tensione 2006/95/CE Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Page 2 of 2 generiert / generated Thu Mar 26 16:24:47 CET 2015