Data sheet for SINAMICS G120C

Transcript

Data sheet for SINAMICS G120C
Data sheet for SINAMICS G120C
Ordering data
6SL3210-1KE15-8AB1
Client order no. :
Item no. :
Order no. :
Consignment no. :
Offer no. :
Project :
Remarks :
Rated data
General tech. specifications
Input
Power factor λ
0,70 ... 0,85
Number of phases
3 AC
Offset factor cos φ
0,95
Line voltage
380 ... 480 V +10 % -20 %
Efficiency η
0,97
Line frequency
47 ... 63 Hz
Sound pressure level (1m)
52 dB
Rated current (LO)
7,40 A
Power loss
0,09 kW
Rated current (HO)
6,00 A
Ambient conditions
Output
Cooling
Raffreddamento ad aria mediante
ventilatore integrato
400 V
Cooling air requirement
0,005 m³/s
Rated power (LO)
2,20 kW
Installation altitude
1000 m
Rated power (HO)
1,50 kW
Ambient temperature
Rated current (IN)
6,00 A
Operation
-10 ... 40 °C (14 ... 104 °F)
Rated current (LO)
5,60 A
Transport
-40 ... 70 °C (-40 ... 158 °F)
Rated current (HO)
4,10 A
Storage
-40 ... 70 °C (-40 ... 158 °F)
Max. output current
8,20 A
Pulse frequency
4 kHz
Output frequency for vector control
0 ... 240 Hz
Output frequency for V/f control
0 ... 650 Hz
Number of phases
3 AC
Rated voltage
Relative humidity
Max. operation
95 % a 40 °C (104 °F), condensa e
formazione di ghiaccio non ammesse
A causa delle disposizioni di legge, a partire dal firmware V4.7 la
frequenza max. di uscita è limitata a 550 Hz.
Overload capability
Low Overload (LO)
150 % corrente di carico base IL per 3 s, successivamente 110 % corrente di carico base IL per 57 s in un tempo di ciclo di 300 s
High Overload (HO)
200 % corrente di carico base IH per 3 s, successivamente 150 % corrente di carico base IH per 57 s in un tempo di ciclo di 300 s
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Page 1 of 2
generiert / generated Thu Mar 26 16:24:47 CET 2015
Data sheet for SINAMICS G120C
Ordering data
6SL3210-1KE15-8AB1
Mechanical data
Connections
Signal cable
Degree of protection
IP20 / UL open type
Size
FSA
Net weight
1,70 kg
Width
73,0 mm
Version
Morsetti a vite innestabili
Height
196,0 mm
Conductor cross-section
1,00 ... 2,50 mm² (16 ... 14 AWG)
Depth
203,0 mm
Inputs/ outputs
Standard digital inputs
Conductor cross-section
0,15 ... 1,50 mm² (28 ... 16 AWG)
Line side
Motor end
Version
Morsetti a vite innestabili
Conductor cross-section
1,00 ... 2,50 mm² (16 ... 14 AWG)
DC link (for braking resistor)
Number
6
Switching level: 0→1
11 V
Version
Morsetti a vite innestabili
Switching level: 1→0
5V
Conductor cross-section
1,00 ... 2,50 mm² (16 ... 14 AWG)
Max. inrush current
15 mA
PE connection
Sulla custodia con vite M4
Fail-safe digital inputs
Number
Max. motor cable length
1
Digital outputs
Number as relay changeover contact
1
Output (resistive load)
DC 30 V, 1 A
Number as transistor
1
Output (resistive load)
DC 30 V, 1 A
Analog/ digital inputs
Number
1 (Ingresso differenziale)
Analog outputs
Number
1 (Uscita non isolata)
PTC/ KTY interface
1 ingresso per sensore di temperatura, sensori collegabili PTC, KTY e
Thermo-Click, con precisione ±5 °C
Shielded
50 m
Unshielded
100 m
Communication
Communication
RS485
Closed-loop control techniques
V/f linear / square-law / parameterizable
Sì
V/f with flux current control (FCC)
Sì
V/f ECO linear / square-law
Sì
Sensorless vector control
Sì
Vector control, with sensor
No
Encoderless torque control
No
Torque control, with encoder
No
Standards
Compliance with standards
CE, cULus, c-tick
CE marking
Direttiva EMC 2004/108/CE, Direttiva
sulla bassa tensione 2006/95/CE
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Page 2 of 2
generiert / generated Thu Mar 26 16:24:47 CET 2015