Manuale MT8000IE_XE

Transcript

Manuale MT8000IE_XE
MT8050iE series
3 Installation Instructions
Installation Instruction
Secure the operator panel in position, using all the fastening holes and the provided brackets
and screws:
(A)
This document covers the installation of MT8050iE Series HMI, for the detailed specifications and
operation, please refer to Brochure and EasyBuilder Pro User Manual.
Install Environment:
NEMA Rating
Electrical
Environment
Environmental
Considerations
Cutout
(B)
1 Installation and Startup Guide
Type
A(mm)
B(mm)
MT8050iE
119
93
MT8050iE Series HMI is NEMA 4 rated (Indoor Only).
The MT8050iE Series has been tested to conform to European CE requirements.
This means that the circuitry is designed to resist the effects of electrical noise.
This does not guarantee noise immunity in severe cases. Proper wire routing and
grounding will insure proper operation.
(1) Make sure that the displays are installed correctly and that the operating
limits are followed. Avoid installing units in environments where severe
mechanical vibration or shocks are present.
(2) Do not operate the unit in areas subject to explosion hazards due to
flammable gases, vapors or dusts.
(3) Do not install the unit where acid gas, such as SO2 exists.
(4) This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5) Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in
Pollution Degree 2 Environment.
2 Unpacking the Unit
Unpack and check the delivery. If damage is found,
notify the supplier.
(1)
NOTE:
Place the operator panel on a stable
surface during installation. Dropping it or
letting it fall may cause damage.
(1) Installation Instruction, 2-sided A4 *1
4 Power Connections
2. Please do not connect HMI with PLC and PC
simultaneously to prevent potential difference
from destroying USB ports of HMI and PC.
To make a connection, strip about 3/8” of
insulation off the end of the wire, turn the
connector screw counterclockwise until the gap
is wide open, insert the wire all the way in, and
turn the screw clockwise until it’s tight.
5 System Settings
When HMI powered up and displays image,
click the system setting button.
(Default System Password: 111111)
It is necessary to connect the HMI to
your network through a RJ-45 cable.
(2) Human Machine Interface *1
(2)
(3) Power Connector *1
(3)
(4) Brackets & Screws V3.0 *1 pack
(4)
NOTE:
1. Connect positive DC line to the ‘+’ terminal
and the DC ground to the ‘-’ terminal.
( Note 1: For the details of HMI
DIP SW function settings please
refer to Part 8 in this guide. )
Go to the Network tab, you may choose
to auto get DHCP IP, or designate your
own IP.
NOTE: Make sure that all local and national electrical standards are met when
installing the unit. Contact your local authorities to determine which codes apply.
CAUTION
6 EasyBuilder Pro Software
Settings
The HMI can be powered by DC power only, voltage range: 24±20% Volts DC, compatible with
most controller DC systems. The power conditioning circuitry inside the unit is accomplished by a
switching power supply. The peak starting current can be as high as 2A.
Power
Launch EasyBuilder Pro software, select your
project file, press F7 shortcut key to open
the download dialog box:
A Hard-wired EMERGENCY STOP should be fitted in any system using HMI to comply with ICS
Safety Recommendations.
Supply
Voltage
Condition
7 Communication Connections
NOTE: 1. COM1 and COM3 [RS485] 2W support MPI 187.5K, please use one at one time.
2. COM1 [RS485] / COM3 [RS485] with isolation protection.
COM1 [RS485]
PIN#
An Internal fuse will prevent damage for overcurrent condition however it isn’t guaranteed. DC
voltage sources should provide proper isolation from main AC power and similar hazards.
High
Voltage
Emergency
Stop
9 Pin, Male, Sub-D
COM1 [RS232]
COM1 [RS485]
COM3 [RS485]
If the display does not come on within 5 seconds of power up, remove power. An internal fuse will
prevent damage if the polarity of the DC power is incorrect. Check wiring for proper connections
and try to power up again.
Fusing
Requirements
Select Ethernet > IP tab > Enter your HMI IP
> Click Download to download this project
file to HMI..
( Please refer to EasyBuilder Pro User Manual
for software operation details )
Symbol
4 wire
2 wire
1
Rx-
Rx-
Data-
2
Rx+
Rx+
Data+
3
Tx-
Tx-
4
TX+
TX+
5
GND
6
TxD
7
Data-
8
Data+
9
RxD
COM1
[RS232]
Wire
Routing
COM3
[RS485]
Caution
a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded).
b. Please use twisted pair cables for power wire and signal wire and conform to the impedance
matching.
c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices.
d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.
e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power
supply and the frame ground. This provides a path for static and high frequency dissipation.
Typical values to use are 1M Ohm and 4700pF.
DANGER
Hardware
Considerations
GND
Transmit
DataData+
The system designer should be aware that devices in Controller systems could fail and thereby
create an unsafe condition. Furthermore, electrical interference in an operator interface can lead to
equipment start-up, which could result in property damage and/or physical injury to the operator.
If you use any programmable control systems that require an operator, be aware that this potential
safety hazard exists and take appropriate precautions. Although the specific design steps depend on
your particular application, the following precautions generally apply to installation of solid-state
programmable control devices, and conform to the guidelines for installation of Controllers
recommended in NEMA ICS 3-304 Control Standards.
Receive
Programming
Considerations
Cable
Requirement
Do not power the HMI and inductive DC loads, or input circuitry to the controller, with the same
power supply. Note: The 24 VDC output from some controllers may not have enough current to
power the HMI.
Different cables are required for various devices.
Restrict cable length to less than 500’ (150m) for RS485/422 devices and 50’ (15m) for RS232
devices to avoid communications problems.
Shielded cable must be used for long lengths or cables run in an electrically noisy environment.
Do not run cables next to AC power lines or near sources of electrical noise.
Be sure that the cable ends have been inserted all of the way into mating connectors and are
secure.
To conform with ICS Safety Recommendations, checks should be placed in the controller to ensure
that all writable registers that control critical parts of plant or machinery have limit checks built into
the program, with an out-of-limit safe shut down procedure to ensure safety of personnel.
GME805000_MT8050iE_Installation_131011
Limited Warranty
This product is limited warranted against defects in design and manufacture.
The proven defective product will either be repaired or replaced, at Weintek’s discretion.
This warranty shall not cover any product which is
(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products.
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.
(c) Product has been repaired or taken apart by unauthorized technicians.
(d) Products whose identification markings have been removed or damaged.
MT8070/8100iE series
3 Installation Instructions
Installation Instruction
Secure the operator panel in position, using all the fastening holes and the provided brackets
and screws:
(A)
Cutout
(B)
1 Installation and Startup Guide
This document covers the installation of MT8000iE Series HMI, for the detailed specifications and
operation, please refer to Datasheet and EasyBuilder Pro User Manual.
Type
A(mm)
B(mm)
Install Environment:
MT8070iE
192
138
NEMA Rating
MT8100iE
260
202
MT8000iE Series HMI is NEMA 4 rated (Indoor Only).
Electrical
Environment
Environmental
Considerations
The MT8000iE Series has been tested to conform to European CE requirements.
This means that the circuitry is designed to resist the effects of electrical noise.
This does not guarantee noise immunity in severe cases. Proper wire routing and
grounding will insure proper operation.
(1) Make sure that the displays are installed correctly and that the operating
limits are followed. Avoid installing units in environments where severe
mechanical vibration or shocks are present.
(2) Do not operate the unit in areas subject to explosion hazards due to
flammable gases, vapors or dusts.
(3) Do not install the unit where acid gas, such as SO2 exists.
(4) This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5) Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in
Pollution Degree 2 Environment.
2 Unpacking the Unit
Unpack and check the delivery. If damage is found,
notify the supplier.
2. Please do not connect HMI with PLC and PC
simultaneously to prevent potential difference
from destroying USB ports of HMI and PC.
To make a connection, strip about 3/8” of
insulation off the end of the wire, turn the
connector screw counterclockwise until the gap
is wide open, insert the wire all the way in, and
turn the screw clockwise until it’s tight.
Place the operator panel on a stable
surface during installation. Dropping it or
letting it fall may cause damage.
5 System Settings
When HMI powered up and displays image,
click the system setting button.
(Default System Password: 111111)
It is necessary to connect the HMI to
your network through a RJ-45 cable.
(2) Human Machine Interface *1
(2)
(3) Power Connector *1
(3)
(5)
(4)
NOTE:
1. Connect positive DC line to the ‘+’ terminal
and the DC ground to the ‘-’ terminal.
NOTE:
(1) Installation Instruction, 2-sided A4 *1
(1)
4 Power Connections
(4) Brackets & Screws V3.0 *1 pack
(5) Fuse 1.25A/250V 5*20mm *1
( Note 1: For the details of HMI
DIP SW function settings please
refer to Part 8 in this guide. )
Go to the Network tab, you may choose
to auto get DHCP IP, or designate your
own IP.
Launch EasyBuilder Pro software, select your
project file, press F7 shortcut key to open
the download dialog box:
PIN#
COM1 / COM3 [RS485]
8 DIP SW Settings
The HMI can be powered by DC power only, voltage range: 24±20% Volts DC, compatible with
most controller DC systems. The power conditioning circuitry inside the unit is accomplished by a
switching power supply. The peak starting current can be as high as 2A.
If the display does not come on within 5 seconds of power up, remove power. An internal fuse will
prevent damage if the polarity of the DC power is incorrect. Check wiring for proper connections
and try to power up again.
Fusing
Requirements
( Please refer to EasyBuilder Pro User Manual
for software operation details )
COM1 [RS232]
installing the unit. Contact your local authorities to determine which codes apply.
Power
Select Ethernet > IP tab > Enter your HMI IP
> Click Download to download this project
file to HMI.
7 Communication Connections
NOTE: Make sure that all local and national electrical standards are met when
CAUTION
6 EasyBuilder Pro Software Settings
An Internal fuse will prevent damage for over voltage condition however it isn’t guaranteed. DC
voltage sources should provide proper isolation from main AC power and similar hazards.
High
Voltage
NOTE:
1. COM1 and COM3 [RS485] 2W support MPI 187.5K,
please use one at one time.
2. COM1 [RS485] / COM3 [RS485] with isolation protection.
Symbol
COM1 [RS232]
Emergency
Stop
A Hard-wired EMERGENCY STOP should be fitted in any system using HMI to comply with ICS
Safety Recommendations.
Supply
Voltage
Condition
1
Not used
2
RxD
Received Data
3
TxD
Transmitted Data
4
Not used
5
GND
6
Not used
7
RTS
Ready to send output
8
CTS
Clear to send input
9
Not used
PIN#
Symbol
Com1
[RS485]2w
Com1
[RS485]4w
1
Rx-
Data-
Rx-
2
Rx+
Data+
Rx+
3
Tx-
4
Tx+
5
GND1
6
Not used
7
Wire
Routing
Signal Ground
DANGER
Com3
[RS485]
Hardware
Considerations
Data-
Data-
Programming
Considerations
8
Data+
Data+
9
GND2
Ground2
TxTx+
Ground1
SW1
SW2
SW3
SW4
Mode
ON
OFF
OFF
OFF
Touch Screen Calibration Mode
OFF
ON
OFF
OFF
Hide HMI System Setting Bar
OFF
OFF
ON
Boot Loader Mode
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
Normal
Not supported
Do not power the HMI and inductive DC loads, or input circuitry to the controller, with the same
power supply. Note: The 24 VDC output from some controllers may not have enough current to
power the HMI.
a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded).
b. Please use twisted pair cables for power wire and signal wire and conform to the impedance
matching.
c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices.
d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.
e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power
supply and the frame ground. This provides a path for static and high frequency dissipation.
Typical values to use are 1M Ohm and 4700pF.
The system designer should be aware that devices in Controller systems could fail and thereby
create an unsafe condition. Furthermore, electrical interference in an operator interface can lead to
equipment start-up, which could result in property damage and/or physical injury to the operator.
If you use any programmable control systems that require an operator, be aware that this potential
safety hazard exists and take appropriate precautions. Although the specific design steps depend on
your particular application, the following precautions generally apply to installation of solid-state
programmable control devices, and conform to the guidelines for installation of Controllers
recommended in NEMA ICS 3-304 Control Standards.
To conform with ICS Safety Recommendations, checks should be placed in the controller to ensure
that all writable registers that control critical parts of plant or machinery have limit checks built into
the program, with an out-of-limit safe shut down procedure to ensure safety of personnel.
GME807810_MT8070_8100iE_Installation_130402
Limited Warranty
This product is limited warranted against defects in design and manufacture.
The proven defective product will either be repaired or replaced, at Weintek’s discretion.
This warranty shall not cover any product which is
(a) Out of warranty period which is 1 year from the date of purchase.
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.
(c) Product has been repaired or taken apart by unauthorized technicians.
(d) Products whose identification markings have been removed or damaged.
MT8121/8150XE series
3 Installation Instructions
Installation Instruction
Secure the operator panel in position, using all the fastening holes and the provided brackets
and screws:
(A)
1 Installation and Startup Guide
Cutout
(B)
This document covers the installation of MT8121/8150XE Series HMI, for the detailed specifications
and operation, please refer to Brochure and EasyBuilder Pro User Manual.
Install Environment:
NEMA Rating
Electrical
Environment
Environmental
Considerations
Type
A(mm)
B(mm)
MT8121/8150XE Series HMI is NEMA 4 rated.
MT8121XE
305
231
The MT8121/8150XE Series has been tested to conform to European CE
requirements. This means that the circuitry is designed to resist the effects of
electrical noise. This does not guarantee noise immunity in severe cases. Proper
wire routing and grounding will insure proper operation.
(1) Make sure that the displays are installed correctly and that the operating
limits are followed. Avoid installing units in environments where severe
mechanical vibration or shocks are present.
(2) Do not operate the unit in areas subject to explosion hazards due to
flammable gases, vapors or dusts.
(3) Do not install the unit where acid gas, such as SO2 exists.
(4) This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5) Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in
Pollution Degree 2 Environment.
MT8150XE
352
279
2 Unpacking the Unit
Unpack and check the delivery. If damage is found,
notify the supplier.
NOTE:
Place the operator panel on a stable
surface during installation. Dropping it or
letting it fall may cause damage.
(1) Installation Instruction, 2-sided A4 *1
(1)
(2) Human Machine Interface *1
(2)
(3) Power Connector *1
(3)
(5)
(4)
(4) Brackets & Screws *1 pack
(5) Fuse 1.6A/250V 5*20mm *1
4 Power Connections
NOTE:
1. Connect positive DC line to the ‘+’ terminal
and the DC ground to the ‘-’ terminal.
2. Please do not connect HMI with PLC and PC
simultaneously to prevent potential difference
from destroying USB ports of HMI and PC.
5 System Settings
When HMI powered up and displays image,
press the system setting button.
(Default System Password: 111111)
It is necessary to connect the HMI to
your network through a RJ-45 cable.
Go to the Network tab, you may choose
to auto get DHCP IP, or designate your
own IP.
6 EasyBuilder Pro Software Settings
Please use EasyBuilder Pro ver. 4.00.01 or later
versions.
Launch EasyBuilder Pro software, select
your project file, press F7 shortcut key to
open the download dialog box:
Select Ethernet > IP tab > Enter your HMI IP >
Click Download to download this project
file to HMI.
COM1 [RS232]
Emergency
Stop
COM1 / COM3 [RS485] 9 Pin, Female, D-sub
PIN#
Symbol
COM1 [RS485]
2W
4W
COM3
[RS485]
1
Not used
1
Rx-
Data-
Rx-
2
RxD
Received Data
2
Rx+
Data+
Rx+
3
TxD
Transmitted Data
3
Tx-
Tx-
4
Not used
4
Tx+
Tx+
5
GND
5
GND1
6
Not used
6
Not used
7
RTS
Ready to send output
7
Data-
Data-
8
CTS
Clear to send input
8
Data+
Data+
9
Not used
9
GND2
Ground2
Signal Ground
An Internal fuse will prevent damage for overcurrent condition however it isn’t guaranteed. DC
voltage sources should provide proper isolation from main AC power and similar hazards.
High
Voltage
NOTE:
1. COM1 and COM3 [RS485] 2W support MPI 187.5K, please use one at one time.
2. COM1 [RS485] / COM3 [RS485] with isolation protection.
Symbol
If the display does not come on within 5 seconds of power up, remove power. An internal fuse will
prevent damage if the polarity of the DC power is incorrect. Check wiring for proper connections
and try to power up again.
Fusing
Requirements
7 Communication Connections
PIN#
The HMI can be powered by DC power only, voltage range: 24±20% Volts DC, compatible with
most controller DC systems. The power conditioning circuitry inside the unit is accomplished by a
switching power supply. The peak starting current can be as high as 2A.
Power
( Please refer to EasyBuilder Pro User Manual
for software operation details )
COM1 [RS232] 9 Pin, Male, D-sub
NOTE: Make sure that all local and national electrical standards are met when
installing the unit. Contact your local authorities to determine which codes apply.
CAUTION
A Hard-wired EMERGENCY STOP should be fitted in any system using HMI to comply with ICS
Safety Recommendations.
Supply
Voltage
Condition
Wire
Routing
a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded).
b. Please use twisted pair cables for power wire and signal wire and conform to the impedance
matching.
c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices.
d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.
e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power
supply and the frame ground. This provides a path for static and high frequency dissipation.
Typical values to use are 1M Ohm and 4700pF.
DANGER
Ground1
Hardware
Considerations
8 Calibration Mode
1. When HMI powered up and displays image, press the
calibration mode button.
2. Click [Yes] in the “Continue to touch panel calibration?” dialog
box.
3. A “+” sign appears on the screen, touch the center of the sign,
after all signs are touched, “+” sign disappears. At this point the
calibration is finished, and it returns to the project.
Do not power the HMI and inductive DC loads, or input circuitry to the controller, with the same
power supply. Note: The 24 VDC output from some controllers may not have enough current to
power the HMI.
Programming
Considerations
The system designer should be aware that devices in Controller systems could fail and thereby
create an unsafe condition. Furthermore, electrical interference in an operator interface can lead to
equipment start-up, which could result in property damage and/or physical injury to the operator.
If you use any programmable control systems that require an operator, be aware that this potential
safety hazard exists and take appropriate precautions. Although the specific design steps depend on
your particular application, the following precautions generally apply to installation of solid-state
programmable control devices, and conform to the guidelines for installation of Controllers
recommended in NEMA ICS 3-304 Control Standards.
To conform with ICS Safety Recommendations, checks should be placed in the controller to ensure
that all writable registers that control critical parts of plant or machinery have limit checks built into
the program, with an out-of-limit safe shut down procedure to ensure safety of personnel.
GME810XE0_MT8121_8150XE_Installation_131024
Limited Warranty
This product is limited warranted against defects in design and manufacture.
The proven defective product will either be repaired or replaced, at Weintek’s discretion.
This warranty shall not cover any product which is
(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products.
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.
(c) Product has been repaired or taken apart by unauthorized technicians.
(d) Products whose identification markings have been removed or damaged.