TEST REPORT

Transcript

TEST REPORT
Independent Testing Laboratory
CMC Centro Misure Compatibilità S.r.l.
Via dell’Elettronica, 12/C
36016 Thiene (VI) – ITALY
Tel./Fax +39 0445 367702
www.cmclab.it - [email protected]
LAB N° 0168
Accredited by ACCREDIA according to UNI CEI EN ISO/IEC 17025 cert. nr. 0168
TEST REPORT nr. R13136301
Electromagnetic Compatibility (EMC)
Test item
Description ........................ : PROTECTION RELAYS
Trademark ......................... : CPT ENGINEERING
Model/Type ...................... : DPLM01561 (firmware version V.7.xxR3)
DPLM01963 (firmware version V.7.xxR3)
Test Specification
Standard ........................... : PPV 13-16 TCS rev. 2 date 15.07.13
PPV 13-23 TCS rev. 2 date 15.07.13
Client’s name .............. : CPT ENGINEERING S.r.l.
Address .............................. : Via Morolense, km 2,8 - 03010 Patrica (FR) – ITALY
Manufacturer’s name : Same as client
Address .............................. : --
Report
Tested by ........................... : G. Gandini – Technician
Approved by .................... : R. Beghetto – Laboratory Manager
Date of issue ..................... : 30.08.13
Contents ............................ : 18 pages
This test report shall not be reproduced except in full without the written approval of CMC.
The test results presented in this report relate only to the item tested.
Test report R13136301
Rev. 1.0
Order M131363
page 1 of 18
CMC
Centro Misure Compatibilità S.r.l.
Via dell’Elettronica, 12/C
36016 Thiene (VI)
LAB N° 0168
Index
1.
SUMMARY..................................................................................................................................................3
2.
DESCRIPTION OF EQUIPMENT UNDER TEST (EUT) .....................................................................................4
3.
TESTING AND SAMPLING ..........................................................................................................................4
4.
OPERATIVE CONDITIONS..........................................................................................................................4
4.1
5.
EVALUATION CRITERIA FOR IMMUNITY TESTS .................................................................................................. 5
PHOTOGRAPH(S) OF EUT ..........................................................................................................................6
5.1
5.2
PHOTOGRAPH(S) OF EUT ........................................................................................................................... 6
PHOTOGRAPH(S) OF SETUP ......................................................................................................................... 7
6.
EQUIPMENT LIST .........................................................................................................................................8
7.
MEASUREMENT UNCERTAINTY ................................................................................................................11
8.
REFERENCE DOCUMENTS........................................................................................................................12
9.
DEVIATION FROM TEST SPECIFICATION.................................................................................................13
10.
TEST CASE VERDICTS ...........................................................................................................................13
11.
RESULTS ................................................................................................................................................14
11.1
11.2
OSCILLATORY WAVE IMMUNITY TEST .......................................................................................................... 15
ADDITIONAL DPL-M01 TEST WITH TCS * ................................................................................................... 18
ANNEX 1: component list
Test report R13136301
Rev. 1.0
Order M131363
page 2 of 18
CMC
Centro Misure Compatibilità S.r.l.
Via dell’Elettronica, 12/C
36016 Thiene (VI)
1.
LAB N° 0168
Summary
Immunity Test:
PPV 13-16 TCS rev. 2 date 15.07.13
PPV 13-23 TCS rev. 2 date 15.07.13
Test specifications
Environmental Phenomena
Port
Tests
sequence
Result
EN 61000-4-18
Oscillatory wave immunity
test
Mains terminal
1
Complies
Additional DPL-M01 test with
TCS *
--
1
Complies
PPV 13-23 TCS rev.
2
Tests reported in this report marked by wording: “Not accredited by ACCREDIA” are not part of the
ACCREDIA accreditation of this laboratory.
* Not accredited by ACCREDIA
This document aims to report the compatibility test results according to the 2004/108 EC Directives.
The Test Report was given to the Client representatives for necessary documentation of ratification of the tested
equipment and it is valid for the CE marking.
Test report R13136301
Rev. 1.0
Order M131363
page 3 of 18
CMC
Centro Misure Compatibilità S.r.l.
Via dell’Elettronica, 12/C
36016 Thiene (VI)
2.
LAB N° 0168
Description of Equipment under test (EUT)
Power supply of model DPLM01561 ......................... : 230 V ~ 50 Hz single-phase
Power supply of model DPLM01963 ......................... : 24 Vdc
Power cable ................................................................... : Unshielded
Serial Number ................................................................. : -Components list ............................................................. : Annex 1
3.
Testing and sampling
Date of receipt of test item ....................................... : 22.07.13
Testing start date ........................................................... : 09.08.13
Testing end date ........................................................... : 09.08.13
Samples tested nr.......................................................... : 1
Sampling procedure. ................................................... : Equipment used for testing was picked up by
the manufacturer, at the end of the production
process with random criterion
Internal identification ................................................... : adhesive label with the product number
P130759
4.
Operative conditions
EUT exercising ................................................................. : See documents PPV 13-16 TCS rev. 2 and PPV 1323 TCS rev. 2
Auxiliary equipment ...................................................... : Stimulation device AUX-P16
Performance check for immunity test ...................... : See documents PPV 13-16 TCS rev. 2 and PPV 1323 TCS rev. 2
Test report R13136301
Rev. 1.0
Order M131363
page 4 of 18
CMC
Centro Misure Compatibilità S.r.l.
Via dell’Elettronica, 12/C
36016 Thiene (VI)
4.1
LAB N° 0168
Evaluation criteria for immunity tests
Criterion A
See document PPV 13-16 TCS rev. 2
Criterion B
See document PPV 13-16 TCS rev. 2
Criterion C
See document PPV 13-16 TCS rev. 2
Criterion D
See document PPV 13-16 TCS rev. 2
Test report R13136301
Rev. 1.0
Order M131363
page 5 of 18
CMC
Centro Misure Compatibilità S.r.l.
Via dell’Elettronica, 12/C
36016 Thiene (VI)
5.
5.1
LAB N° 0168
Photograph(s) of EUT
Photograph(s) of EUT
Test report R13136301
Rev. 1.0
Order M131363
page 6 of 18
CMC
Centro Misure Compatibilità S.r.l.
Via dell’Elettronica, 12/C
36016 Thiene (VI)
5.2
LAB N° 0168
Photograph(s) of setup
Oscillatory wave
Test report R13136301
Rev. 1.0
Order M131363
page 7 of 18
CMC
Centro Misure Compatibilità S.r.l.
Via dell’Elettronica, 12/C
36016 Thiene (VI)
6.
LAB N° 0168
Equipment list
Id. number
CMC S001
CMC S002
CMC S003
CMC S004
CMC S005
CMC S006
CMC S007
CMC S009
CMC S010
CMC S012
CMC S013
CMC S014
CMC S015
CMC S016
CMC S017
CMC S018
CMC S019
CMC S021
CMC S022
CMC S024
CMC S025
CMC S026
CMC S027
CMC S028
CMC S029
CMC S030
CMC S031
CMC S032
CMC S033
CMC S034
CMC S037
CMC S039
CMC S040
CMC S042
CMC S(51-75)
CMC S076
CMC S077
CMC S078
CMC S079
CMC S080
CMC S081
CMC S082
CMC S083
CMC S084
CMC S085
CMC S086
CMC S087
CMC S088
CMC S089
CMC S090
CMC S091
CMC S094
CMC S095
Manufacturer
Rohde & Schwarz
Rohde & Schwarz
SCHAFFNER
SCHAFFNER
XITRON
Chauvin Arnoux
Rohde & Schwarz
Rohde & Schwarz
Rohde & Schwarz
Rohde & Schwarz
Rohde & Schwarz
Rohde & Schwarz
RKB
Rohde & Schwarz
Rohde & Schwarz
SCHAFFNER
FCC
CMC
Teseo
CMC
Salmoiraghi
Chroma
Amplifier Research
FCC
Keytek
Rohde & Schwarz
Tektronix
SCHAFFNER
Tektronix
Schwarzbeck
Rohde & Schwarz
CMC
Walker Scientific
Fluke
CMC
Altitude
Fluke
Amplifier Research
AH System, Inc
AH System; Inc
AH System; Inc
AH System; Inc
AH System; Inc
AH System; Inc
AH System; Inc
CMC
CMC
CMC
CMC
CMC
CMC
Schwarzbeck
FCC
Test report R13136301
Model
ESHS30
ESVS30
NSG 2025-4
NSG 435-01
2503
CA43
SMY01
ESH2-Z5
ESH3-Z2
MDS21
EZ-17
ESH2-Z3
LOG801000
HK116
HL223
CDN 126
FCC 801-M5-25
TRBS 01
LAS 1
CTL-01
1750-1
C6530
75A250
FCC-203I
Cemaster
ESPC
TDS 210
NSG 2050
P6015
UHA 9105
NRVS
BI 01
ELF 50-D
Fluke 73
LFXXX
25438
Fluke-87
100W1000M1
SAS-200/542
SAS-200/510
SAS 200/550-1
SAS-200/560
BCP-200/510
BCP-200/511
SAS-200/530
RHCP01
RHCP01
LFAS20
CSTARTER
CSTARTER
DIPLP
NNBM 8126-A
FCC 801-M3-16
Rev. 1.0
Description
EMC interference receiver
EMC interference receiver
Burst source with CDN
ESD simulator
Harmonic & Flicker analyser
Field meter
RF signal generators
Artificial network
Impulses limiting device
Absorbing clamp
Current probe
Passive probe
Log-periodic Antenna
Biconical antenna
Log-periodic Antenna
Coupling clamp
CDN Power Line
Balance-to-unbalance transformer
Loop antenna
Voltage change for LISN
Hygro - Thermograph
Power supply source
RF Amplifier
Injection clamp
Surge, dips, burst source
EMC interference receiver
Digital oscilloscope
Surge source with CDN
High voltage probe
Dipole
Power meter
Induction coil
Magnetic field meter
Multimeter
Dummy lamp
Barometer
Multimeter
RF Amplifier
Biconical antenna
Log periodic antenna
Active Monopole Antenna
Loop Antenna
LF Current Probe
HF/VHF Current Probe
Broadband dipole
Resistance 470Kohm
Resistance 470Kohm
Dummy lamp
Capacitor 5000pF
Capacitor 5000pF
Dipole for Loop Antenna control
Artificial network
CDN power line
Order M131363
Serial number
862024/003
826638/011
1010
1166
2503592013
218541RLV
841403/038
839497/007
--838506/015
840411/009
----839472/001
825584/009
128
06
--3971
--323.601
653000095
19349
209
9609258
844006/013
B010552
200111-253AR
R0238/1
UHA 91052234
845127/023
--K71484-290
67771510
----69050353
21849
504
807
660
635
564
579
504
------------8126A161
9821
page 8 of 18
CMC
Centro Misure Compatibilità S.r.l.
Via dell’Elettronica, 12/C
36016 Thiene (VI)
Id. number
CMC S096
CMC S105
CMC S106
CMC S107
CMC S108
CMC S109
CMC S110
CMC S111
CMC S112
CMC S114
CMC S116
CMC S117
CMC S118
CMC S119
CMC S120
CMC S121
CMC S122
CMC S123
CMC S124
CMC S125
CMC S126
CMC S127
CMC S128
CMC S129
CMC S130
CMC S131
CMC S132
CMC S133
CMC S135
CMC S136
CMC S138
CMC S139
CMC S140
CMC S141
CMC S142
CMC S143
CMC S144
CMC S145
CMC S146
CMC S150
CMC S155
CMC S156
CMC S158
CMC S159
CMC S161
CMC S162
CMC S163
CMC S164
CMC S170
CMC S171
CMC S172
CMC S173
CMC S174
CMC S175
CMC S176
CMC S177
Manufacturer
B&K
Decca
Gigatronix
Hewlett Packard
Emco
Farnell
CMC
LEM HEME
Amplifier Research
Schwarzbeck
CMC
MARCONI
Hewlett Packard
Hewlett Packard
FCC
Wavetek
Fluke
Rohde & Schwarz
Spin
SCHAFFNER
LDS + Dactron
SCHAFFNER
SCHAFFNER
Rohde & Schwarz
SCHAFFNER
SCHAFFNER
CMC
RKB
LEM HEME
Schwarzbeck
Agilent
Wilcoxon
Wilcoxon
Dytran
Narda
EM TEST
Rohde & Schwarz
Hewlett Packard
Amplifier Research
RKB
Chroma
Yokogawa
CMC
Rohde & Schwarz
EM TEST
FCC
NOISEKEN
Rohde & Schwarz
Amplifier Research
Schwarzbeck
Schwarzbeck
Luthi
Luthi
Luthi
Luthi
Luthi
Test report R13136301
Model
2260
PA-50
900
HP8563E
3115
LFM4
OPS800
PR 1001
DC3010
VHA 9103
BCIP01
2019A
E3632A
HP8903B
FC130-A
LCR55
336
SML03
AMTP42-20
PNW 2003
V730-335+LASER
HLA6120
CBA9428
ESPI7
NSG 5000
CDN 500
OPS150
LOG8002500
PR 30
VULB 9136
33220A
736
732A
3023A1
ELT-400+B-sensor
DPA 500
URV5
778D
10W1000B
LOG3080
61705
DL9040
ITF
SM300
EFT 500 M4 S1
FCC 801-M2-16
ESS-2002+TC-815R
ESU26
FL7006
BBHA 9120 LF(A)
VHBD9134+BBAL9136
CDN L-801 AF4
CDN L-801 AF8
CDN L-801 T2
CDN L-801 T4
CDN L-801 T8
Rev. 1.0
LAB N° 0168
Description
Serial number
Phonometer
Log-periodic antenna
RF signal generator
Spectrum analyser
Horn antenna
LF signal generator
Open strip line 800mm
Current probes
Directional coupler
Dipole
Bulk current injection probe
RF signal generator
Programmable power supply
Audio Analyzer
Bulk Current Injection Probe
Bridge LCR
Amperometric clamp meter
RF signal generator
Horn Antenna 18-26GHz
Dips source
Vibration testing system
Loop Antenna
RF Amplifier
Receiver
Automotive Impulse Generator
Capacitive clamp
Open strip line 150mm
Log-periodic Antenna
Current Probe
Broadband Antenna
Function / Arbitrary Waveform Gen.
Accelerometer 101 mV/g
Accelerometer 9.8 mV/g
Accelerometer Triaxial
Exposure level tester
Harmonic & Flicker analyser
Power meter
Directional coupler
RF Amplifier
Log-periodic Antenna
Power supply source
Digital oscilloscope
Impedance
RF signal generator
Burst source with CDN
CDN power line
ESD simulator
EMC interference receiver
Field meter
Broadband Antenna
Broadband Antenna
CDN I/O line
CDN I/O line
CDN I/O line
CDN I/O line
CDN I/O line
1847463
34/17977 - b
323001
3846A09658
9811-5622
531
----15238
VHA 91031801
-118453/014
KR75301881
3011A09055
118
20104738
81754972
100625
103
200234-014SC
132+133+4512698
1191
1006
836.914/004
02032579-1
400-151/0128
----P04217832830
9136-205
MY44003979
12245
1424
383
D-0034+D-0032
0903 - 04
881375/004
17237
18451
--000000088
91F643771
--1006114
V0739102946
07047
ESS0787336
100052
0327425
284
9134-037
2481
2482
2473
2475
2476
Order M131363
page 9 of 18
CMC
Centro Misure Compatibilità S.r.l.
Via dell’Elettronica, 12/C
36016 Thiene (VI)
Id. number
CMC S178
CMC S179
CMC S180
CMC S181
CMC S182
CMC S183
CMC S184
CMC S185
CMC S187
CMC S190
CMC S191
CMC S193
CMC S194
CMC S195
CMC S196
CMC S197
CMC S198
CMC S199
CMC S200
CMC S201
CMC S202
CMC S203
CMC S204
CMC S205
CMC S206
CMC S207
CMC S209
CMC S210
CMC S211
CMC S212
CMC S213
CMC S214
CMC S215
CMC S216
CMC S217
CMC S218
CMC S219
CMC S220
CMC S221
CMC S222
CMC S223
CMC S224
CMC S225
CMC S226
CMC S227
CMC S228
CMC S229
CMC S230
CMC A001
CMC A002
CMC A007
CMC A008
CMC A013
CMC A014
CMC B026
CMC B087
Manufacturer
Schwarzbeck
Frankonia
Milmega
Milmega
Milmega
Minicircuits
ARRAY
EM TEST
Rohde & Schwarz
Spin
EM TEST
Solar
CMC
Schwarzbeck
EM TEST
EM TEST
FCC
EM TEST
Schwarzbeck
S.M. ELECTRONICS
Rohde & Schwarz
CMC
Amplifier Research
Schwarzbeck
Rohde & Schwarz
AlphaLab
Elettrotest
EM TEST
Luthi
Luthi
Luthi
EM TEST
FCC
Luthi
Schwarzbeck
RS
EM TEST
Minicircuits
Minicircuits
A-INFOMW
Minicircuits
Fairview microwave
Fairview microwave
Werlatone
Rohde & Schwarz
Agilent
Schwarzbeck
Werlatone
Sispe
SIDT
CMC
CMC
CMC
CMC
Angelantoni
Yokogawa
Test report R13136301
Model
STLP 9128 C
FLL-250A
RF350
AS0822-200
AS0206-50
PWR-SEN-6G+
3400A
OCS 500 M6 S4
SMB100A
AMDR-10180
UCS 500 N5
6552-1A
CDN 16 PL
VULB 9118 E sp.
BS 200N
UCS 200N
F - 55
CNI 503
NSLK 8128
SA3N150-06F
CMU200
VH
150L
NNBM 8124
ESCI 7
ASMGM
TPS40K 30K60S
PFS 200N30
CDN L-801 M1
CDN L-801 M2
CDN L-801 M3
VDS200N10
F-130A-1
MDS21
TK9420
50WCW
CNV 504 N1.2
PWR-SEN-6GHS
BW-N20W5+
ACB06-100SN
BW-N20W20+
SMC4037-20
SA3550N
C6021-10
ESR7
U3401A
CAT5 8158
C1795-10
F5123
951130
10707
BPA
TR01
PM01
UY 245 IU
WT3000
Rev. 1.0
LAB N° 0168
Description
Broadband Antenna (150 - 4000 MHz)
RF Amplifier
RF Amplifier
RF Amplifier
RF Amplifier
Power sensor
Arbitrary Waveform Generation
Oscillatory compact simulator
RF signal generator
Horn antenna
Burst/Surge/PFQ compact simulator
BF Amplifier
CDN Power line
Log-periodic Antenna (50 - 2000 MHz)
Electronic switch
Pulse generator 1/2/3a/3b/6/7
RF Current Probe
CDN for Burst and Surge
V-LISN
6 dB attenuator 150W (DC-3GHz)
Universal radio communication tester
Van der Hoofden test-head
RF Amplifier
LISN 5uH
EMC Receiver
Milligauss meter
AC Source
Power Fail simulator
CDN M line
CDN M line
CDN M line
Voltage drop simulator
BCI probe
Absorbing clamp
Voltage probe
50 ohm load 50W
Box surge
USB POWER SENSOR
20dB attenuator 5W (DC-18GHz)
6dB attenuator 100W (DC-3GHz)
20dB attenuator 20W (DC-18GHz)
Directional Coupler
Step Attenuator DC-3GHz
Dual Directional Coupler
EMI Test Receiver 7GHz
Digital multimeter
ISN 8-Wire
Dual Directional Coupler
Shield chamber
Anechoic chamber
Semi-anechoic chamber
Track for absorbing clamp
Rotary motorized table
Antenna positioning Mast
Climatic chamber
Precision Power analyzer
Order M131363
Serial number
086
1023
1031422
1031424
1031425
0809070042
TW00009164
V0915104789
102572
01-309-09
V0947105547
----827
V100510506
V0825103901
100999
V1026106843
8128-273
--104099
--10939
065
100781
584
002.11
V1130110311
2811
2812
2813
V1150111222
112166
4101
458
--V1210112161
110082250012
0612
J3081111111003
1217
JSDF568-081
201237026
99019
101121
MY52270047
CAT5-8158-0074
100140
------------1059.78
91JB15155
page 10 of 18
CMC
Centro Misure Compatibilità S.r.l.
Via dell’Elettronica, 12/C
36016 Thiene (VI)
7.
LAB N° 0168
Measurement uncertainty
Test
Expanded Uncertainty
Conducted Emission
(50/50H AMN) - (9 kHz – 150 kHz)
(50/50H AMN) - (150 kHz – 30 MHz)
(Voltage probe) - (150 kHz – 30 MHz)
(50/5H AMN) - (150 kHz – 108 MHz)
Discontinuous Conducted Emission
Conducted Emission (50/50H AMN) - (150 kHz – 30 MHz)
note
3.9 dB
3.4 dB
3.4 dB
2.8 dB
1
1
1
1
3.4 dB
1
Disturbance Power (30 MHz – 300 MHz)
Radiated Emission
(0,150 MHz – 30 MHz)
(30 MHz – 1000 MHz)
(1 GHz – 6 GHz)
3.9 dB
1
4.3 dB
4.6 dB
4.7 dB
1
1
1
Electromagnetic field EMF
15.0 %
1
Harmonic current emissions test
Voltage fluctuation and flicker test
2.7 %
2.9 %
1
1
Insertion loss test
Radiated electromagnetic disturbance test (loop antenna)
2.9 dB
2.8 dB
1
1
Radiated electromagnetic field immunity test
Pulse modulated radiated electromagnetic field immunity test
Injected currents immunity test
Bulk current
Power frequency magnetic field immunity test
0.8 V/m at 3V/m
0.8 V/m at 3V/m
0.4 V at 3V
9.7 mA at 60 mA
0.1 A/m at 10 A/m
1
1
1
1
1
Electrostatic discharge immunity test
Electrical fast transients / burst immunity test
Surge immunity test
Pulse magnetic field immunity test
Damped oscillatory magnetic field immunity test
Short interruption immunity test
2
2
2
2
2
2
Voltage transient emission test
Transient immunity test
2.2 %
1
2
Notes
Note 1:
The expanded uncertainty reported according to EN55016-4-2:2011 is based on a standard uncertainty multiplied by a
coverage factor of k=2, providing a level of confidence of p = 95%
Note 2:
It has been demonstrated that the used test equipment meets the specified requirements in the standard with at least a
95% confidence, covering factor k = 2.
Test report R13136301
Rev. 1.0
Order M131363
page 11 of 18
CMC
Centro Misure Compatibilità S.r.l.
Via dell’Elettronica, 12/C
36016 Thiene (VI)
8.
LAB N° 0168
Reference documents
Reference no.
Description
PPV 13-16 TCS rev. 2 date 15.07.13
PPV 13-23 TCS rev. 2 date 15.07.13
CEI 0-16:2012
Prove con onde oscillatorie smorzate su DPL-M01
Integrazione alle funzioni fondamentali su DPL-M01
Reference technical rules for the connection of active and
passive consumers to the HV and MV electrical networks of
distribution Company
Electromagnetic compatibility (EMC) - Part 4-18: Testing
and measurement techniques - Damped oscillatory wave
immunity test
Measure procedure
Measurement uncertainty calculation
EN 61000-4-18:2007 + /A1:2010
Internal Procedure PM001 rev. 2.0 (Quality Manual)
Internal procedure INC_M rev. 8.1 (Quality Manual)
Test report R13136301
Rev. 1.0
Order M131363
page 12 of 18
CMC
Centro Misure Compatibilità S.r.l.
Via dell’Elettronica, 12/C
36016 Thiene (VI)
9.
LAB N° 0168
Deviation from test specification
None
10.
Test case verdicts
Test case does not apply to the test object ........... : N.A.
Test item does meet the requirement ...................... : Complies
Test item does not meet the requirement............... : Does not comply
Test not performed ...................................................... : N.E.
Test report R13136301
Rev. 1.0
Order M131363
page 13 of 18
CMC
Centro Misure Compatibilità S.r.l.
Via dell’Elettronica, 12/C
36016 Thiene (VI)
11.
LAB N° 0168
Results
In this clause tests results are reported.
The evaluation of EUT performance during immunity test has been performed by members of CMC
staff.
Measurement uncertainty is in accordance with document CMC INC_M rev. 8.1.
Judgement of compliance:
Case 1
Case 2
Case 3
Case 4
The sample is
Complies.
The sample is
Complies.
The sample is Not
Complies.
The sample is Not
Complies.
The measurement
results is within the
specification limit
when the
measurement
uncertainty is taken
into account.
It is not possible to
state compliance
using a 95% coverage
probability for the
expanded
uncertainty although
the measurement
result is below the
limit.
It is not possible to
state compliance
using a 95% coverage
probability for the
expanded
uncertainty also the
measurement result is
upper the limit.
The measurement
results is outside the
specification limit
when the
measurement
uncertainty is taken
into account.
In agreement with ILAC-G8: 03/2009 Guidelines on the Reporting of Compliance with Specification.
Test report R13136301
Rev. 1.0
Order M131363
page 14 of 18
CMC
Centro Misure Compatibilità S.r.l.
Via dell’Elettronica, 12/C
36016 Thiene (VI)
11.1
LAB N° 0168
Oscillatory wave immunity test
Test set-up and execution






Test configuration and test method
PPV 13-16 TCS rev. 2
PPV 13-23 TCS rev. 2
EN 61000-4-18 cl. 7-8
CEI 0-16 cl. E.3.11.2
Internal procedure PM001
See clause 4 of this test report
Test site:
Test table “Oscillatory wave”
Auxiliary equipment:
See clause 4 of this test report
EUT exercising
Test equipment used
See clause 4 of this test report
CMC S185
Measurement uncertainty: See clause 7 of this
test report
Test specification
Test level: 3
Port
Low voltage power
port
Low voltage power
port
Frequency
Time
100 kHz
1 min
1 MHz
1 min
Level
±2,5 kV (line to earth)
±1 kV (line to line)
±2,5 kV (line to earth)
±1 kV (line to line)
Environmental conditions
Temperature
(ºC)
Atmospheric pressure
(kPa)
Relative humidity
(%)
27
100
40
Acceptance limits
Test report R13136301
Criterion B (See clause 4 of this test report)
Rev. 1.0
Order M131363
page 15 of 18
CMC
Centro Misure Compatibilità S.r.l.
Via dell’Elettronica, 12/C
36016 Thiene (VI)
LAB N° 0168
Setup
CMC S185
Result
Line
PE – N
PE – L1
N – L1
PE – N
PE – L1
N – L1
PE – N
PE – L1
N – L1
PE – N
PE – L1
N – L1
Remarks:
Level
(kV)
Frequency
2,5
100 kHz
2,5
100 kHz
1
100 kHz
2,5
1 MHz
2,5
1 MHz
1
1 MHz
2,5
100 kHz
2,5
100 kHz
1
100 kHz
2,5
1 MHz
2,5
1 MHz
1
1 MHz
Test performed on model DPLM01561
Test report R13136301
Rev. 1.0
Result
Polarity
+
A
A
A
A
A
A
A
A
A
A
A
A
Remarks
A
A
A
A
A
A
A
A
A
A
A
A
Order M131363
Channel L1
Channel L1
Channel L1
Channel L1
Channel L1
Channel L1
Channel NO
Channel NO
Channel NO
Channel NO
Channel NO
Channel NO
page 16 of 18
CMC
Centro Misure Compatibilità S.r.l.
Via dell’Elettronica, 12/C
36016 Thiene (VI)
Line
PE – N
PE – L1
N – L1
PE – N
PE – L1
N – L1
PE – N
PE – L1
N – L1
PE – N
PE – L1
N – L1
Remarks:
Level
(kV)
LAB N° 0168
Frequency
2,5
100 kHz
2,5
100 kHz
1
100 kHz
2,5
1 MHz
2,5
1 MHz
1
1 MHz
2,5
100 kHz
2,5
100 kHz
1
100 kHz
2,5
1 MHz
2,5
1 MHz
1
1 MHz
Test performed on model DPLM01963
Result
Polarity
+
A
A
A
A
A
A
A
A
A
A
A
A
Remarks
A
A
A
A
A
A
A
A
A
A
A
A
Channel L1
Channel L1
Channel L1
Channel L1
Channel L1
Channel L1
Channel NO
Channel NO
Channel NO
Channel NO
Channel NO
Channel NO
Result: The requirements are met
Test report R13136301
Rev. 1.0
Order M131363
page 17 of 18
CMC
Centro Misure Compatibilità S.r.l.
Via dell’Elettronica, 12/C
36016 Thiene (VI)
11.2
Additional DPL-M01 test with TCS *
Test set-up and execution



LAB N° 0168
Test configuration and test method
PPV 13-23 TCS rev. 2
Internal procedure PM001
See clause 4 of this test report
Test site:
Laboratory
Auxiliary equipment:
See clause 4 of this test report
EUT exercising
Test equipment used
See clause 4 of this test report
--
Test specification
Connect the DPL-M01-P16 to the device AUX-P16 using the connector marked TCS, place the
selector switch on 24Vdc or 230Vac depending on the VPR-P16 model.
Turn on the DPL-M01-P16 and verify that the KNO LED on AUX-P16 lights up immediately (TCS
section on the right) and after 1 or 2 seconds to turn on the ER LED, the latter will always remain
ON until the DPL-M01 will be supplied. Verify that the DPL-M01 is in automatic mode, reading AUT
on the frontal display (otherwise set as described in the manual). Press the switches 52a and 52b to
verify that the DPL-M01 light up the LED OPEN and CLOSE respectively, for the normal operation of
DPL-M01 one of these two switches must be pressed. In the case in which both are pressed or both
are turned off, after about 3 appears on the display the 52ER signaling. Verify that the reporting is
done in both cases and then reset it by pressing SHIFT on the front of DPL-M01.
On the front of the DPL-M01 press OK to check the setting of the COIL logic on CC, at the coil
shunt (otherwise set as described in the manual). Push the TCS switch on AUX-P16 and wait; verify
that after about 10 seconds, the display shows the TCS word, indicating the interruption of
continuity on the coil shunt. Switch off the TCS and after 10 seconds reset the signal on the display
by pressing the SHIFT key on the DPL-M01. If the TCS signal is properly reset, the verification is
completed.
* Not accredited by ACCREDIA
Result: The requirements are met
Test report R13136301
Rev. 1.0
Order M131363
page 18 of 18